• Title/Summary/Keyword: EMTP/MODELS

Search Result 65, Processing Time 0.035 seconds

Modeling and Switching Overvoltage Analysis for Reclosing Analysis in Combined Transmission Systems (혼합송전계통에서 재폐로 해석을 위한 모델수립 및 개폐과전압해석)

  • Lim, Kwang-Sik;Lee, Jong-Beom;Kang, Ji-Won;Jung, Chae-Kyun
    • Proceedings of the KIEE Conference
    • /
    • 2008.07a
    • /
    • pp.442-443
    • /
    • 2008
  • This paper describes modeling using the EMTP/ATPDraw for reclosing analysis in 154kV combined transmission systems, and analyzes switching overvoltage. Current transformer established at lead-in area and lead-out area in transmission line and circuit breaker were modeled using TACS in the EMTP/ATPDraw. And also MODELS was constructed by signal processing of the operating reclosing. The simulation was carried out the switching overvoltage according to the length of overhead and underground transmission line, overvoltage between sheath and earth, and voltage between joint boxes.

  • PDF

A Study On Operation Characteristic Of Recloser with Energy Storage System (ESS를 고려한 재폐로 차단기의 동작 특성에 관한 연구)

  • Jung, Ho-Chul;Rhee, Sang-Bong;Seo, Hun-Chul;Kim, Soo-Bae
    • Proceedings of the KIEE Conference
    • /
    • 2015.07a
    • /
    • pp.599-600
    • /
    • 2015
  • This paper presents study of recloser operation in distribution system with Energy Storage System(ESS). However, interconnecting of ESS influence power flow and increasing/decreasing of fault current. Recloser provides stability of system and improves power transmitting ability by reclosing in fault current. The single-line to ground fault current simulated by Electromagnetic Transients Program (EMTP). The simulation is implemented for the three different situations about by using EMTP MODELS.

  • PDF

The Adequacy Analysis for Installation of High Speed Grounding Switches on the Korean 765kV Single Transmission Line

  • Ahn, Sang-Pil;Kim, Chul-Hwan;Park, Nam-Ok;Ju, Hyung-Jun;Shim, Eung-Bo
    • Journal of Electrical Engineering and Technology
    • /
    • v.1 no.4
    • /
    • pp.427-434
    • /
    • 2006
  • This paper analyzes arc phenomena including the secondary arc's elongation in the Korean 765kV single transmission line (79km) between Sin-Ansung S/S and Sin-Gapyeong S/S, which will be installed in Korea in June 2006. In particular, both frequency independent and frequency dependent line models are compared to make our final decisions. As well, the significant simulation results are investigated by the EMTP program. As a result, there is no need of HSGS in the Korean 765kV single transmission line from both a practical and an economical point of view.

A New Modeling Technique for Secondary Arc on Single-Pole Switching Transmission Lines (단상재폐로 선로의 2차아크랜 대한 새로운 모델링 기법)

  • Park, Pyung-Chul;Lee, Uk-Hwa;Shin, Joong-Rin
    • Proceedings of the KIEE Conference
    • /
    • 1997.07c
    • /
    • pp.880-882
    • /
    • 1997
  • The secondary arcing phenomenon can be hardly modeled for computer simulation due to its particularly-nonlinear characteristics. This paper describes a new computer modeling technique for the secondary arc which can be implemented with the EMTP MODELS. The computer model proposed is based on realistic arc conduction behaviors through newly designed variable resistor modules which can be supported in the EMTP. In this Paper, for the variable resister modules, a new variable arc resistance formula is proposed. Simulation results using the proposed technique are compared with some previous studies.

  • PDF

An Electric Arc Furnaces Load Model for Transient Analysis (과도현상 해석을 위한 EAFs 부하 무델의 개발)

  • Jang, Gilsoo;Venkata, S.S.;Kwon, Sea-Hyuk
    • The Transactions of the Korean Institute of Electrical Engineers A
    • /
    • v.48 no.3
    • /
    • pp.197-202
    • /
    • 1999
  • Electric arc furnaces (EAFs) use bulk electrical energy to create heat in metal refining industries. The electric arc process is a main cause of the degradation of the electric power quality such as voltage flicker due to the interaction of the high demand currents of the load with the supply system impedance. The stochastic models have described the aperiodic physical phenomena of EAFs. An alternative approach is to include deterministic chaos in the characterization of the arc currents. In this parer, a chaotic approach to such modeling is described and justified. At the same time, a DLL(Dynamic Link Library) module, which is a FORTRAN interface with TACS (Transient Analysis of Control Systems), is developed to implement the chaotic load model in the Electromagnetic Transients Program (EMTP). The details of the module and the results of tests performed on the module to verify the model and to illustrate its capabilities are presented in this paper.

  • PDF

An Analysis of Recloser Operation According to Recovery Characteristics of Superconducting Fault Current Limiter (초전도 한류기의 회복특성에 따른 재폐로 동작 분석)

  • Rhee, Sang-Bong;Kim, Chul-Hwan;Kim, Kyu-Ho;Kim, Jae-Chul;Hyun, Ok-Bae
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.58 no.5
    • /
    • pp.905-910
    • /
    • 2009
  • For proper application and operation of a SFCL(Superconducting Fault Current Limiter) in distribution systems, the prior investigation of fundamental characteristics and its effects analysis to the systems are very important. A point of view in coordination with recloser in distribution systems, characteristic about quenching and recovering of SFCL should be studied. Especially, its detailed study of recovery characteristic is particularly important to avoid conflict between the SFCL and the recloser. In this paper, the resistive type SFCL and recloser, which used in distribution system, were implemented using EMTP/ATPDraw and MODELS language. To analyze the recovery characteristics of SFCL according to recloser operation in distribution systems, case studies have been simulated and investigated.

Three-phase Transformer Model and Parameter Estimation for ATP

  • Cho Sung-Don
    • Journal of Electrical Engineering and Technology
    • /
    • v.1 no.3
    • /
    • pp.302-307
    • /
    • 2006
  • The purpose of this paper is to develop an improved three-phase transformer model for ATP and parameter estimation methods that can efficiently utilize the limited available information such as factory test reports. In this paper, improved topologically-correct duality-based models are developed for three-phase autotransformers having shell-form cores. The problem in the implementation of detailed models is the lack of complete and reliable data. Therefore, parameter estimation methods are developed to determine the parameters of a given model in cases where available information is incomplete. The transformer nameplate data is required and relative physical dimensions of the core are estimated. The models include a separate representation of each segment of the core, including hysteresis of the core, ${\lambda}-i$ saturation characteristic and core loss.

Transformer Core Model and Parameter Estimation for ATP

  • Cho Sung-Don
    • KIEE International Transactions on Power Engineering
    • /
    • v.5A no.4
    • /
    • pp.385-389
    • /
    • 2005
  • Power transformers would appear to be simple. However, due to their nonlinear and frequency-dependent behaviors, they can be one of the most complex system components to model. It is imperative that the applied models be appropriate for the range of frequencies and excitation levels that the system experiences. Transformer modeling is not a mature field and newer improved models must be made available in ATP packages. Further, there is a lack of published guidance on recommended modeling approaches. And there is typically not enough detailed design or test information available to determine the parameters for a given model. The purpose of this paper is to develop improved transformer core models for ATP and parameter estimation methods that can efficiently utilize the limited available information such as factory test reports.

Effect on Transient Stability According to Application of Adaptive Autoreclosure Using THD (THD를 이용한 적응형 재폐로 방법 적용 시 과도 안정도에 미치는 영향)

  • Kang, Sung-Bum;Seo, Hun-Chul;Lee, Myong-Hee;Kim, Chul-Hwan
    • Proceedings of the KIEE Conference
    • /
    • 2011.07a
    • /
    • pp.201-202
    • /
    • 2011
  • This paper compares the effect on transient stability by according to application of adaptive autoreclouse using THD with the one of conventional autoreclosure. These two autoreclousure methods are modeled by EMTP/MODELS and simulated according to various fault locations and fault clearing times. This paper analyzes transient stability using simulation results.

  • PDF

A Power Factor Analysis due to Interconnecting Photovoltaic Resource (계통연계형 태양광전원 투입에 따른 역률 분석)

  • Kim, Sang-Hyub;Rhee, Sang-Bong;Lyu, Seung-Heon
    • Proceedings of the KIEE Conference
    • /
    • 2008.11a
    • /
    • pp.503-505
    • /
    • 2008
  • Photovoltaic(PV) resource connected in the power system can be affect to the power quality. To analyze the power quality, this paper simulate the variation of power factor by PV resource connected to the low voltage system. The power factor calculator and full-bridge inverter of PV system are modeled by EMTP/MODELS. Simulation results according to the PV capacity and load are presented.

  • PDF