• 제목/요약/키워드: Doubly fed induction generator system

검색결과 98건 처리시간 0.032초

Comparative study of control strategies for the induction generators in wind energy conversion system

  • Giribabu, D.;Das, Maloy;Kumar, Amit
    • Wind and Structures
    • /
    • 제22권6호
    • /
    • pp.635-662
    • /
    • 2016
  • This paper deals with the comparison of different control strategies for the Induction generators in wind energy conversion system. Mainly, two types of induction machines, Self excited induction generator (SEIG) and doubly Fed Induction generators (DFIG) are studied. The different control strategies for SEIG and DFIG are compared. For SEIG, Electronic load Controller mechanism, Static Compensator based voltage regulator are studied. For DFIG the main control strategy namely vector control, direct torque control and direct power control are implemented. Apart from these control strategies for both SEIG and DFIG to improve the performance, the ANFIS based controller is introduced in both STATCOM and DTC methods. These control methods are simulated using MATLAB/SIMULINK and performances are analyzed and compared.

이중여자 유도발전 풍력시스템의 정상상태 특성 해석 (Analysis of Steady State Characteristics of Doubly-Fed Induction Generator in Wind Turbine system)

  • 장보경;노경수
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2009년도 제40회 하계학술대회
    • /
    • pp.460_461
    • /
    • 2009
  • This paper analyzes the steady state characteristics for variable speed wind power system with doubly-fed induction generator(DFIG). This paper explains the equivalent circuit and phasor diagram of DFIG for different operating conditions. It also simulates the torque-slip characteristics with respect to changes of different parameters. Simulation results show the torque-slip characteristics, stator power factor-rotor voltage and stator current-rotor voltage.

  • PDF

이중여자 유도형 풍력발전기 제어를 위한 PCS 개발 (Development of PCS for Doubly-fed Induction-type Wind Turbine)

  • 정병창;정용호;김성환
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2008년도 제39회 하계학술대회
    • /
    • pp.1182-1183
    • /
    • 2008
  • In this paper, we develop PCS for doubly-fed induction-type wind generator(DFIG). PCS consists of a converter set and a controller. PCS controls the active power of wind generator and the reactive power of wind turbine system according to rotating speed, instantaneous power, grid quality, and order by transmission system operator.

  • PDF

이중권선 유도발전기로 구동되는 유도전동기의 수동성기반제어기 설계 (Passivity-based Controller Design for Induction Motor Driven by Doubly-fed Induction Generator)

  • 이상철;김종현
    • 전력전자학회:학술대회논문집
    • /
    • 전력전자학회 2003년도 춘계전력전자학술대회 논문집(2)
    • /
    • pp.639-643
    • /
    • 2003
  • We are interested in this paper on the control of an electromechanical system consisting of a doubly-fed induction generator(DFIG), driven by a prime mover that can supply or extract mechanical power, e.g., a flywheel inertia, and an induction motor(IM). The stator of the Induction machine is connected to the stator of the generator whose rotor voltage is regulated by a bidirectional converter. The main interest of this configuration is that it permits a bidirectional power flow between the motor, which may operate in regenerative mode, and the generator We propose a passivity-based controller to regulate the motor mechanical speed. Since this kind of controllers achieve stabilization via energy balancing, regulation of the power flow in the system is naturally incorporated. Simulation results are presented to illustrate the main points of our paper.

  • PDF

권선형 유도발전기의 CVCF 발전을 위한 2자여자제어법에 관한 연구 (A Study on the 2nd Exitation for CVCF Generation of Doubly-fed Induction Generator)

  • 안진우;황영문
    • 대한전기학회논문지
    • /
    • 제40권7호
    • /
    • pp.656-663
    • /
    • 1991
  • This paper deals with the control strategy for the constant voltage, constant frequency (CVCF) generation of doubly -fed induction generator. Since induction machine is a nonlinear and multivariable one, the influential factors for CVCF generation of induction generator are the magnitude of output voltage, load current and its power factor, slip of the machine, etc. To get appropriate control scheme and study the effect of its parameters, the control equation of induction machine is derived and tested. The simulation and test results show that suggested equation and control system are very useful strategy for the CVCF control of induction generator.

  • PDF

권선형 유도발전기 CVCF를 위한 2차 여자제어법에 관한 연구 (II) (A Study on the 2nd Excitation Method for CVCF Generation of Doubly-fed Induction Generator (II))

  • 안진우;황영문
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1990년도 추계학술대회 논문집 학회본부
    • /
    • pp.45-48
    • /
    • 1990
  • This paper deals with the control strategy for constant voltage, constant frequency (CVCF) generation of doubly-fed Induction generator. As induction machine is a nonlinear and multivariable machine, so, the influential factors for CVCF generation of induction generator are the magnitude of output voltage, load current and its power factor, slip of the machine, etc. To get appropriate control scheme and to research the effect of its parameters, the control equation of induction machine is derived and tested. The derived condition is very useful for the CVCF control of the machine and for determing the characteristics of the system. The simulation results show that magnetizing reactance and rotor resistance is a very important parameter in this control system.

  • PDF

이중여자 유도발전기를 이용한 가변속운전과 정속운전 풍력발전시스템의 운전특성 비교 (Comparison of Characteristics for Variable Operation using Doubly-fed Induction Generator and Fixed Speed Operation in Wind Turbine System)

  • 노경수;김태호
    • 전기학회논문지
    • /
    • 제58권7호
    • /
    • pp.1313-1320
    • /
    • 2009
  • This paper analyzes the steady-state operating characteristics of doubly-fed induction generator(DFIG) and fixed-speed induction generator(FSIG) in wind turbine system. It also presents a modeling and simulation of a grid-connected wind turbine generation system for dynamics analysis on MATLAB/Simulink, and compares the responses between DFIG and FSIG wind turbine systems with respect to wind speed variation, 3-phase fault and 1-phase ground fault of the network. Simulation results show the variations of generator's active/reactive output, rotor speed, terminal voltage, fault current, etc. Case studies demonstrate that DFIG illustrates better performance compared to FSIG.

Characteristics on Stand-alone Operation of a Doubly-fed Induction Generator Applied to Adjustable Speed Gas Engine Cogeneration System

  • Daido, Tetsuji;Miura, Yushi;Ise, Toshifumi;Sato, Yuki
    • Journal of Power Electronics
    • /
    • 제13권5호
    • /
    • pp.841-853
    • /
    • 2013
  • An application of doubly-fed induction generator (DFIG), which is one of adjustable speed generators, to a gas engine cogeneration system has been investigated. To operate during a blackout as an emergency power supply is one of important roles for the gas engine cogeneration system. However, the DFIG requires initial excitation for startup during a blackout because the DFIG has no excitation source. In this paper, we propose the "blackout start" as a new excitation method to generate a rated voltage at the primary side during a blackout. In addition, a stand-alone operation following a blackout has been investigated by using experimental setup with a real gas engine. Power flows in the generating set with the DFIG at the stand-alone operation have been investigated experimentally. Experimental investigation of the power flow suggests that the generating set with DFIG has optimal speed in minimizing whole system losses.

New Control Scheme for the Wind-Driven Doubly Fed Induction Generator under Normal and Abnormal Grid Voltage Conditions

  • Ebrahim, Osama S.;Jain, Praveen K.;Nishith, Goel
    • Journal of Power Electronics
    • /
    • 제8권1호
    • /
    • pp.10-22
    • /
    • 2008
  • The wind-driven doubly fed induction generator (DFIG) is currently under pressure to be more grid-compatible. The main concern is the fault ride-through (FRT) requirement to keep the generator connected to the grid during faults. In response to this, the paper introduces a novel model and new control scheme for the DFIG. The model provides a means of direct stator power control and considers the stator transients. On the basis of the derived model, a robust linear quadratic (LQ) controller is synthesized. The control law has proportional and integral actions and takes account of one sample delay in the input owing to the microprocessor's execution time. Further, the influence of the grid voltage imperfection is mitigated using frequency shaped cost functional method. Compensation of the rotor current pulsations is proposed to improve the FRT capability as well as the generator performance under grid voltage unbalance. As a consequence, the control system can achieve i) fast direct power control without instability risk, ii) alleviation of the problems associated with the DFIG operation under unbalanced grid voltage, and iii) high probability of successful grid FRT. The effectiveness of the proposed solution is confirmed through simulation studies on 2MW DFIG.

Neural network based direct torque control for doubly fed induction generator fed wind energy systems

  • Aftab Ahmed Ansari;Giribabu Dyanamina
    • Advances in Computational Design
    • /
    • 제8권3호
    • /
    • pp.237-253
    • /
    • 2023
  • Torque ripple content and variable switching frequency operation of conventional direct torque control (DTC) are reduced by the integration of space vector modulation (SVM) into DTC. Integration of space vector modulation to conventional direct torque control known as SVM-DTC. It had been more frequently used method in renewable energy and machine drive systems. In this paper, SVM-DTC is used to control the rotor side converter (RSC) of a wind driven doubly-fed induction generator (DFIG) because of its advantages such as reduction of torque ripples and constant switching frequency operation. However, flux and torque ripples are still dominant due to distorted current waveforms at different operations of the wind turbine. Therefore, to smoothen the torque profile a Neural Network Controller (NNC) based SVM-DTC has been proposed by replacing the PI controller in the speed control loop of the wind turbine controller. Also, stability analysis and simulation study of DFIG using process reaction curve method (RRCM) are presented. Validation of simulation study in MATLAB/SIMULINK environment of proposed wind driven DFIG system has been performed by laboratory developed prototype model. The proposed NNC based SVM-DTC yields superior torque response and ripple reduction compared to other methods.