• Title/Summary/Keyword: Cooling tower fan

Search Result 34, Processing Time 0.023 seconds

The Effects of Operational Conditions of Cooling Water System on Energy Consumption for Central Cooling System (냉각수 계통의 운전변수가 중앙냉방시스템의 에너지소비량에 미치는 영향)

  • Ahn, Byung-Cheon
    • Journal of the Korean Society for Geothermal and Hydrothermal Energy
    • /
    • v.13 no.4
    • /
    • pp.8-13
    • /
    • 2017
  • The effects of operational conditions of cooling water system on energy consumption for central cooling system are researched by using TRNSYS program. Cooling tower water pump flow rate, cooling tower fan flow rate, and condenser water temperature with various dry-bulb and wet-bulb temperatures are varied and their effects on total and component power consumption are studied. If the fan maximum flow rates of cooling tower is decreased, cooling tower fan and total power consumptions are increased. If the cooling tower water pump maximum flow rates is decreased, chiller and total power consumptions are increased. If condenser water set-point temperature is increased, chiller power consumption is increased and cooling tower fan power consumption is decreased, respectively.

The Diagnosis of Cooling Tower System (Cooling Tower System 진동 진단)

  • Lee, Sun-Hwi
    • Proceedings of the Korean Society for Noise and Vibration Engineering Conference
    • /
    • 2007.11a
    • /
    • pp.1090-1094
    • /
    • 2007
  • The aim of this study is to estimate the cause of Cooling Tower vibration and eliminate the faults of fan with high vibration in spite of overhaul. The cause of high vibration was that the natural frequency of fan blade coincide with second blade pass frequency. To achieve reduction of Cooling Tower vibration, change motor speed from 1784rpm to 1714rpm, and then the vibration has reduced conspicuously.

  • PDF

Program Development for Design of Counter-flow Cooling Tower (향류형 냉각탑의 기본설계 프로그램 개발)

  • Ko, Kwang-Ho;In, Jong-Soo;Oh, Tae-Il
    • Journal of the Korean Society of Industry Convergence
    • /
    • v.7 no.4
    • /
    • pp.383-389
    • /
    • 2004
  • This paper is to develop the program for sizing of a counter-flow cooling tower. Air flow, air exit tmperature, fan power are calculated from design coditions of cooling tower by using this program. The basic equations and solutions of the heat transfer and pressure drop of cooling tower are descrived and the algorithm development for design of cooling tower is performed. The variation of fan power of cooling tower in acoording to variation of cell area and fill height is performed by using this program. This result shows that the optimal design for install and running cost of cooling tower can be performed by using this program.

  • PDF

A Model-Based Fault Detection and Diagnosis Methodology for Cooling Tower

  • Ahn, Byung-Cheon
    • International Journal of Air-Conditioning and Refrigeration
    • /
    • v.9 no.3
    • /
    • pp.63-71
    • /
    • 2001
  • This paper presents a model-based method for detecting and diagnosing some faults in the cooling tower of healing, ventilating, and air-conditioning systems. A simple model for the cooling tower is employed. Faults in cooling tower operation are detected through the deviations in the values of system characteristic parameters such as the heat transfer coefficient-area product, the tower approach, the tower effectiveness, and fan power. Three distinct faults are considered: cooling tower inlet water temperature sensor fault, cooling tower pump fault, and cooling tower fan fault. As a result, most values of the system characteristics parameter variations due to a fault are much higher or lower than the values without faults. This allows the faults in a cooling tower to be detected easily using above methods. The diagnostic rules for the faults were also developed through investigating the changes in the different parameter due to each faults.

  • PDF

The Characteristics of Energy Consumption with Operational Conditions for the Central Cooling System (냉방시스템의 운전조건에 따른 에너지 소비특성 연구)

  • Park, Gi-Tae;Ahn, Byung-Cheon
    • Journal of the Korean Society for Geothermal and Hydrothermal Energy
    • /
    • v.15 no.4
    • /
    • pp.39-45
    • /
    • 2019
  • The operational conditions such as cooling tower water pump flow rate, cooling tower fan flow rate, and chiller capacity in heat source equipment, and supply air temperature and chilled water temperature in air conditioner are considered to study the effects on energy consumption for central cooling system by using TRNSYS program. As a result, the optimal values of supply air temperature and chilled water temperature for minimal total energy consumption are 12℃ and 8℃. And if maximum values of cooling tower water pump and fan flow rate is decreased from 100% to 40%, energy consumptions are increased 170MJ/day and 63.2MJ/day, respectively.

Numerical Investigation of Performance Characteristics for Cooling Tower Axial Fans with Sweep (스윕을 가진 냉각탑용 축류홴의 성능 특성에 관한 수치해석적 연구)

  • Oh, K.J.
    • Journal of Power System Engineering
    • /
    • v.13 no.4
    • /
    • pp.31-37
    • /
    • 2009
  • The purpose of this numerical study was to investigate performance characteristics for cooling tower axial fans with sweep. Performance data for the fans with various sweep angles were obtained in terms of the setting angle at a constant flow rate. Viscous flow calculations were carried out to obtain Performance data of the total pressure rise and hydraulic efficiency. A solution of the Ffowcs Williams-Hawkings equations was used to calculate the sound pressure level at three times fan diameter away from the fan. The calculated performance data well represented performance characteristics of the cooling tower axial fan. The total pressure rise and hydraulic efficiency at the same setting angle decreased with sweep angle. Sound pressure level slightly decreased for the fan with a sweep angle of 10 degree. No significant effect of the sweep geometry was found on the sound pressure level.

  • PDF

A Study on the Noise Characteristics of Cooling Tower (냉각탑의 방사소음특성에 관한 연구)

  • Park, B.Y.;Kim, I.S.;Lee, S.H.
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.8 no.3
    • /
    • pp.361-374
    • /
    • 1996
  • In general, a cooling tower has two major noise sources, one is the fan and the other is the falling water. The fan noise is produced by passage of its blades through the air and radiates from the fan stack. Noises from the falling water are caused by splashing and dropping of water cascading over the internal filler of the cooling tower and into the basin and radiate from the louvered face. In this paper, the noise measurements and its frequency analysis are carried out for the locations facing the louvered side and near the fan stack referring the related code and standards in order to study the noise characteristics of the induced-draft cooling tower, especially for the buildings. As a result, it is found that for every doubling of distance from the noise source the noise level decreases by 2~4dBA in the near field with reflect surfaces and decreases by about 6dBA also in the far field without reflect surfaces. As a supplement to the noise measurements, a computer program with simple algorithm is developed in order to estimate the noise level at a distance from the cooling tower, so that the user could apply and modify it for the particular boundary conditions easily.

  • PDF

Development of an Axial F.R.P. Fan for Cooling Tower (냉각탑용 축류형 F.R.P. 팬의 개발)

  • Oh, Keon-Je;Kim, Sun-Sook
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.19 no.10
    • /
    • pp.735-741
    • /
    • 2007
  • An axial F.R.P. fan model for cooling tower is developed. The fan is designed using the equations for one dimensional inviscid flow through the fan blade. Fan shape is swept forward with a parabolic function. Calculations of the three dimensional turbulent flow around the fan are carried out to investigate performance of the fan. Data of the total pressure rise and hydraulic efficiency can be obtained for the various setting angles. Calculated values of the total pressure rise and hydraulic efficiency at the design point are less than those of the design specification. The prototype of the F.R.P. fan is made by laminating of the fiberglass and epoxy resins on the mold of fan shape.

Effects of Inlet Water Temperature and Heat Load on Fan Power of Counter-Flow Wet Cooling Tower (입구 물온도와 열부하가 냉각탑의 팬동력에 미치는 영향 분석)

  • Nguyen, Minh Phu;Lee, Geun Sik
    • Transactions of the Korean Society of Mechanical Engineers B
    • /
    • v.37 no.3
    • /
    • pp.267-273
    • /
    • 2013
  • In order to provide effective operating conditions for the fan in a wet cooling tower with film fill, a new program to search for the minimum fan power was developed using a model of the optimal total annual cost of the tower based on Merkel's model. In addition, a type of design map for a cooling tower was also developed. The inlet water temperature and heat load were considered as key parameters. The present program was first validated using several typical examples. The results showed that for a given heat load, a three-dimensional graph of the fan power (z-axis), mass flux of air (x-axis, minimum fan power), and inlet water temperature (y-axis, maximum of minimum fan power) showed a saddle configuration. The minimum fan power increased as the heat load increased. The conventionally known fact that the most effective cooling tower operation coincides with a high inlet water temperature and low air flow rate can be replaced by the statement that there exists an optimum mass flux of air corresponding to a minimum fan power for a given inlet water temperature, regardless of the heat load.

Surface Profile Measuring System for Axial Fan of Cooling Towers (냉각탑용 축류팬 형상 정밀도 측정 시스템)

  • Kang Jae-Gwan;Lee Kwang-Il
    • Journal of the Korean Society for Precision Engineering
    • /
    • v.22 no.4
    • /
    • pp.151-158
    • /
    • 2005
  • An important component of a cooling tower is an axial fan, and there happens distortion in its shape which brings significant loss of efficiency. In this paper, a surface profile measuring system for large size axial fan of cooling towers is developed. A laser sensor is used as a measuring device and aluminum profiles and stepping motors are engaged into the system as frame structure and driving devices respectively. The measuring data are compared to the design data to compute the distortion of the axial fans. Two types of errors, axial and twist errors, are used to represent the precision of axial fan distortion. Genetic algorithm is used to solve the optimization problem during computing the precision. Results are displayed three dimensionally in a solid-modeler as well as 2-D drawings to help users find it with ease.