A Study on Pump Selecting for Oil Direct Cooling Type Power Transformer (강제송유 냉각방식 변압기 펌프선정 기준 정립에 관한 연구)

  • Kim, Seong Eon
    • Proceedings of the KIPE Conference
    • /
    • 2014.11a
    • /
    • pp.62-63
    • /
    • 2014
  • 전력용 변압기에서 강제송유 냉각방식을 채택할 경우 절연유 강제 순환을 위한 펌프가 필요한데, 매 설계 시 마다 유동해석 혹은 설계 프로그램을 통해 펌프를 선정하게 되면 상당한 시간이 소요된다. 이러한 시간적 손실을 줄이고자 유동해석 및 유체 이론에 근거하여 간단하게 엑셀 시트로 프로그램화 하였다.

  • PDF

An Experimental Study on Oil Effect of CO2 in Heat Pump Outdoor Heat Exchanger (CO2용 실외열교환기의 오일 영향에 따른 성능변화에 대한 실험적 연구)

  • Lee, Jin-Gwan;Chang, Young-Soo;Kim, Seo-Young;Kim, Yong-Chan
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.23 no.4
    • /
    • pp.243-250
    • /
    • 2011
  • In order to investigate the effects of PAG oil concentration on heat transfer performance and pressure drop during gas cooling process of $CO_2$, the experiments on fin-tube heat exchanger of $CO_2$ heat pump were performed. The experimental apparatus consists of a gas cooler, a heater, a chiller, a mass flow meter, a pump and measurement system. Experiments were conducted in various experimental conditions, which were inlet temperature($110^{\circ}C$), mass flow rates (50, 55, 60, 65, 70 g/s) and PAG oil concentration(0 to 2.6 wt%). Heat transfer rate decreased with the increase of the oil concentration and the decrease of inlet pressure. And pressure drop increased with the increase of the oil concentration and mass flow rate of refrigerant. The COP reduction by deterioration of gas cooler performance with oil concentration was analyzed. When inlet pressure of gas cooler is 100 bar, the COP reduction was estimated by 6% under 1 wt% of oil concentration.

Cooling Performance Test of 2-stage Heat Pump System Using River Water as a Heat Source (하천수율원이용 2단압축 열펌프시스템 냉방성능평가)

  • Kim, J.R.;Lee, Y.S.;Jang, K.C.;Ra, H.S.
    • Proceedings of the KSME Conference
    • /
    • 2004.04a
    • /
    • pp.2129-2134
    • /
    • 2004
  • The present study has been conducted to develop a heat pump system using river water of temperature energy which not only belongs to unutilized energy but is a kind of good heat source due to maintain its temperature in a certain degree regardless of seasonal variation. The system did not meet the proposed performance after setup. In this paper, the system performance affected by refrigerant Oil, by pressure drop, or by other factors has been discussed. The followings were obtained : (1) Refrigerant Oil mixture rate was 2.5 in weight percentage, (2) Pressure drop through evaporator was 29.1kPa($3.1^{\circ}C$ in saturated tempearture) (3) Pressure drop from the end of evaporator to compressor inlet was 39.8kPa($4.0^{\circ}C$ in saturated tempearture). (4) The system performance can to be improved by modifying a part of pipe line to compressor, and reducing pressure drop through heat exchangers.

  • PDF

The Field Test of bankfiltration(including alluvial and riverbed deposits) Source Heat Pump Cooling & Heating System (강변여과수(충적층 및 하상)를 이용한 열펌프 냉난방시스템의 실증연구)

  • Hwang, Ki-Sup;Jung, Woo-Sung;Ahn, Young-Sub
    • Proceedings of the SAREK Conference
    • /
    • 2006.06a
    • /
    • pp.1186-1190
    • /
    • 2006
  • Rising in important of alternative energy due to the recenfly high oil price and environment problem. Application of alternative energy has become higher than before. In this study, facility test of Geothermal energy to bankfiltration was examined appliying changwon pumping well. Initial installation cost was efficiently saved by connecting a heat pump system to pumping well in changwon bankfiltration site. A falling-off in efficiency of heat pump was free due to the bankfiltration that is rare for the temperature fluctuation. Therefore, Heat soure as bankfiltration system solve the existing facilities problems of geothermal heat pump system.

  • PDF

A Study on the Operating Control of a 2-Stage Heat Pump System with Screw Compressors (스크류 2단 압축 열펌프 시스템의 운전 제어 방안에 관한 연구)

  • Kim, Ji-Young;Baik, Young-Jin;Lee, Young-Soo;Ra, Ho-Sang
    • Proceedings of the SAREK Conference
    • /
    • 2006.06a
    • /
    • pp.501-505
    • /
    • 2006
  • A preliminary performance test of a 30RT 2-stage screw heat pump was carried out in order to develop a high performance large-scale unutilized energy source heat pump, which will be used in district heating and cooling. Two issues on the system control were investigated in this study, A stable 2-stage heating operation is guaranteed only if the load-side water inlet temperature is over a certain value, to where the 1-stage heating operation should be done first from a cold start. An oil shortage problem in low stage compressor, which depends on the degree of suction superheat, was solved by the proper oil level control scheme.

  • PDF

A Study on the Thermal Characteristics of Dry Vacuum Pump with Vertical Screws (수직형 건식 진공 스크류 펌프의 열특성에 대한 연구)

  • Chang, Moon-Suk;Park, Jae-Hyun;Kim, Soo-Tae;Kim, Il-Gon;Cho, Seong-Jin
    • Journal of the Korean Society of Manufacturing Process Engineers
    • /
    • v.14 no.2
    • /
    • pp.67-74
    • /
    • 2015
  • In this study, analysis and experiments were carried out on temperature distributions and thermal deformations in a dry vacuum pump with vertical screws for safe operation. When a vacuum pump is working, it is necessary to get rid of the heat generated by the friction of bearings and the compression of air to prevent the vacuum pump from being damaged by interference between two screws and housing through thermal deformation. Additional cooling was proposed by using oil flow through the inner channel of the rotating axis for lower temperature control of the vacuum pump. Analysis and experimental results were compared in terms of temperature distribution and thermal deformation of the vacuum pump, and two sets of results matched reasonably well. These results for a dry vacuum pump with vertical screws can be used in similar model development and can minimize errors in design and manufacture by providing reasonably accurate prediction in advance.

A Study on Performance and Reactor Behavior of Chemical Refrigerator (화학식 냉동기의 성능 및 반응기 거동에 관한 연구)

  • Park, Seung-Hoon;Lee, Jong-Ho
    • Journal of Energy Engineering
    • /
    • v.6 no.1
    • /
    • pp.87-95
    • /
    • 1997
  • A chemical heat pump based on the reversible reactions between metal chlorides and ammonia gas is attractive alternative to compression system and liquid absorption systems in cooling and refrigerating fields. The advantages of chemical heat pump are no regulatory constants due to CFC refrigerants, utilization of gas, industrial waste heat, electricity, fuel oil etc. as heat sources and wide applications to energy storage system, large-scale energy managements for industrial process. The scale-up of chemical heat pump from laboratory prototype to pilot plants necessitates the interpretation of system performance and evaluation of dynamic behavior in the chemical reactor. This study contains the prediction of performance of chemical refrigerator according to operating condition, the dynamic simulations through reactor modelling, which is used for the calculation of reactive medium temperature and the conversion variation with reactor cooling temperature, and the effect survey of block parameters on the power of refrigerator.

  • PDF

Installation and Monitoring of Bankfiltration (including alluvial and riverbed deposits) Source Heat Pump Cooling System (강변여과수(충적층 및 하상)를 이용한 냉방시스템 설치 및 모니터링)

  • Jung, Woo-Sung;Hwang, Ki-Sup;Ahn, Young-Sub
    • 한국신재생에너지학회:학술대회논문집
    • /
    • 2006.11a
    • /
    • pp.5-8
    • /
    • 2006
  • The Alternative energy has lately attracted considerable attention due to the high oil price and environment problem. In this study, pilot test facility for using the geothermal energy source from riverbank filtration was constructed and monitoring devices are installed to estimate the efficiency of this system. Initial installation cost can be saved efficiently by connect ing a heat pump system into the exist ing pumping well in Changwon riverbank filtration site. One set of monitoring results during summer was presented and analyzed.

  • PDF

The Field Test of Heat Pump Cooling & Heating System using the water-purifying device (수도시설을 이용한 지열냉난방시스템의 실증연구)

  • Hwang, Ki-Sup;Jung, Woo-Sung;Ahn, Young-Sub
    • Proceedings of the SAREK Conference
    • /
    • 2007.11a
    • /
    • pp.629-634
    • /
    • 2007
  • The Alternative energy has lately attracted considerable attention due to the high oil price and environment problem. In this study, field test of facility for using the geothermal energy source from water-purifying device was constructed and monitoring devices are installed to estimate the efficiency of this system. Initial installation cost can be saved efficiently by connecting a heat pump system into the existing pumping well in site of water-purifying in Cheongju. One set of monitoring results during summer was presented and analyzed.

  • PDF

Design for Increasing Displacement Volume of Gerotor Pumps using Virtual Design Environment (가상 설계 환경을 활용한 지로터 펌프의 배제용적 증량 설계 사례)

  • Dae Kyung Noh;Dong Won Lee;Jeong Bae Jeon;Joo Sup Jang
    • Journal of Drive and Control
    • /
    • v.21 no.2
    • /
    • pp.15-22
    • /
    • 2024
  • The objective of this study was to examine whether a gerotor pump used in a transmission could be converted into an electric vehicle thermal management system pump using a virtual design environment. To achieve this objective, we first built an environment that could analyze the performance of a gerotor pump in heat transfer fluid. Flow rate, pressure, and volumetric efficiency were then analyzed when using heat transfer fluid in a gerotor pump. Finally, how large the displacement volume of the pump should be designed when using a heat transfer fluid other than oil was determined. Based on results of this study, it is expected that gerotor pumps will be applied to new business fields such as electric vehicle cooling systems.