• Title/Summary/Keyword: Cables

Search Result 1,577, Processing Time 0.034 seconds

Lightning protection in an 154kV GIS connected by oil-filled cables (O.F. Cable에 연결된 154kV GIS의 뇌보호)

  • 정태호
    • 전기의세계
    • /
    • v.29 no.5
    • /
    • pp.315-320
    • /
    • 1980
  • It has been appeared and widely used today SF6 Gas Insulated Substation(Hereafter called GIS) for the power supply to the densely populated area due to the superior insulation withstand ability of SF6 Gas. And to maximize the compact effect of this substation, it is normal practice to connect underground cables. If it is possible to elieminate the redundant lightning arresters using the physical characterestics of travelling waves in underground cables, economical advantages can be obtained together with easy maintenances. It is presented in this paper the possiblity of eliminating the transformer protection lightning arresters under some conditions for the 154kV GIS's (BIL:750kV) which Korea Electric Co. plans to construct using the general purpose digital computer program.

  • PDF

A Permissible Current-Carrying Capability Calculation of Power Cables Installed in Thermally Dissimilar Soil Materials (이종매질에서의 지중 송전케이블 허용전류 계산)

  • Jeong S. H.;Choi S. B.;Choi S. B.;Lee J. D.;Ryoo H. S.;Kim D. K.;Kim H. S.
    • Proceedings of the KIEE Conference
    • /
    • summer
    • /
    • pp.467-469
    • /
    • 2004
  • When power cables cross regions with unfavorable thermal conditions, conductor temperatures higher than the design value can occur. This paper proposes the calculation algorithms of the permissible current-carrying capability using the algorithm of calculating the longitudinal conductor temperature distribution of power cables installed in thermally dissimilar soil materials.

  • PDF

A Study on the Effect of Low Thermal Resistivity Backfill for the Permissible Current-Carrying Capability of Underground Power Cables (지중 송전케이블의 되메움재 효과에 관한 연구)

  • Jeong, S.H.;Kim, D.K.;Choi, S.B.;Lee, D.I.;Kang, J.W.
    • Proceedings of the KIEE Conference
    • /
    • 2002.07a
    • /
    • pp.256-258
    • /
    • 2002
  • This paper analyzes the sensitivity of the permissible current-carrying capability of underground power cables according to the thermal property of backfill materials and construction size of backfill materials. It is helpful for operators to determine the operating current and to design the construction of underground power cables.

  • PDF

Evaluation of Jacket Compounds for Underground Distribution Power Cables (지중 배전케이블용 자켓 컴파운드의 특성평가)

  • 한재홍;송일근;김동명;이재봉;정창수
    • Journal of the Korean Institute of Electrical and Electronic Material Engineers
    • /
    • v.15 no.8
    • /
    • pp.687-694
    • /
    • 2002
  • In order to replace the jacket material for URD power cables, the 6 kinds of polyethylene compounds were manufactured and evaluated. The characteristics of the compounds were investigated by water vapor transmission (WVT) test, thermal and mechanical test. In WVT test, all the polyethylene compounds showed the superior water resistance to conventional PVC. The molecular structure and density of polyethylene play an important role in WVT. Also, the polyethylene compounds showed the suitable characteristics in thermal and mechanical test. Especially, the linear polyethylene compounds showed the superior characteristics to LDPE ones. Due to the fillers in compounds, the abrasion resistance was decreased and the cut-through resistance was increased. From this study, it can be considered that the polyethylene compounds may be suitable to jacket material for URD power cables.

A Study on the Analysis of Conductor Temperature Distribution of Underground Power Cables Buried in Ducts (관로부설 지중 전력 케이블 도체 온도 해석에 관한 연구)

  • Jeong, Seong-Hwan;Kim, D.K.;Choi, S.B.;Lee, D.I.;Kang, J.W.;Kim, H.S.;Park, J.H.
    • Proceedings of the KIEE Conference
    • /
    • 2001.05a
    • /
    • pp.270-272
    • /
    • 2001
  • This paper proposes an algorithm of analyzing the conductor temperature distribution of underground power cables buried ill ducts. This algorithm used an equation of the permissible current-carrying capability of power cables. The algorithm will be given to an operator an ability to operate the underground power system in comfort.

  • PDF

A Study on the Thermal Circuit of Underground Tunnel Installed Power Cables (전력구 부설에 대한 지중 전력 케이블의 허용전류 계산 열 회로에 관한 연구)

  • Jeong, S.H.;Kim, D.K.;Choi, S.B.;Bae, J.H.;Ha, T.H.;Lee, H.G.;Gwag, B.M.;Yoon, H.H.;Kang, J.W.
    • Proceedings of the KIEE Conference
    • /
    • 2000.11a
    • /
    • pp.159-161
    • /
    • 2000
  • This paper examines the thermal circuit of underground tunnels installed power cables. It can be appreciated to understand the mechanism of heat transfer and to calculate the current carrying capacity of power cables in tunnel.

  • PDF

A Study on Fault Detection Method in Underground Cables using the Detecting Electro Magnetic Wave and Acoustic Signal (전자파의 음향신호측정에 의한 지중 케이블의 고장점 검출기법에 관한 연구)

  • Min, Kyoung-Rae;Kim, Hun;Yoon, Yong-Han;Kim, Jae-Chul;Song, Ho-Yub
    • Proceedings of the KIEE Conference
    • /
    • 1999.07c
    • /
    • pp.1357-1359
    • /
    • 1999
  • This paper presents fault detection in cables. We developed the device for detecting pinpoint location of faults in power cables using acoustic method. The proposed device consists of hardware and software for the fault detection. Using the device, we explain how to detect the pinpoint of faults and introduce that the other method use the time delay between electro-magnetic and acoustic signals for the pinpoint of the faults.

  • PDF

Uniform Current Distribution among Conductor Layers in HTS Cables Using Inter-Phase Transformers (Inter-Phase Transformers를 이용한 고온 초전도 케이블의 층간 전류 등분배 방안)

  • 최용선;황시돌;현옥배;임성우;박인규
    • Progress in Superconductivity
    • /
    • v.5 no.2
    • /
    • pp.144-148
    • /
    • 2004
  • Uniform current distribution among conductor layers in HTS cables using IPTs (inter-phase transformers) was investigated. Conventional methods for current distribution, in which resistors are inserted to conductor layers, causes additional loss. In contrast, IPTs, which use magnetic coupling, make it possible that the current in parallel circuits is distributed uniformly with any load, and minimize the loss. In this study, IPTs were designed and fabricated for examination of uniform current distribution in the conductor layers of HTS cables. The ITP was designed through calculation of its impedance that can cancel the inductance of the conduction layers. The experimental setup consisted of four IPTs and four inductors that simulate the conductor layer inductance. Each layer was designed to feed 10 A. We examined the behavior of current distribution with IPTs for various layer inductances.

  • PDF

The existence of solutions of a nonlinear suspension bridge equation

  • Park, Q-heung;Park, Kyeongpyo;Tacksun Jung
    • Bulletin of the Korean Mathematical Society
    • /
    • v.33 no.4
    • /
    • pp.503-512
    • /
    • 1996
  • In this paper we investigate a relation between the multiplicity of solutions and source terms in a nonlinear suspension bridge equation in the interval $(-\frac{2}{\pi}, \frac{2}{\pi})$, under Dirichlet boundary condition $$ (0.1) u_{tt} + u_{xxxx} + bu^+ = f(x) in (-\frac{2}{\pi}, \frac{2}{\pi}) \times R, $$ $$ (0.2) u(\pm\frac{2}{\pi}, t) = u_{xx}(\pm\frac{2}{\pi}, t) = 0, $$ $$ (0.3) u is \pi - periodic in t and even in x and t, $$ where the nonlinearity - $(bu^+)$ crosses an eigenvalue $\lambda_{10}$. This equation represents a bending beam supported by cables under a load f. The constant b represents the restoring force if the cables stretch. The nonlinearity $u^+$ models the fact that cables expansion but do not resist compression.

  • PDF

Field Application of Power Cable Diagnosis System (전력케이블 열화진단기법의 현장적용)

  • Kim, Ju-Yong;Han, Jae-Hong;Song, Il-Keun;Kim, Sang-Jun;Lee, Jae-Bong;Oh, Jae-Hyung
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2002.05c
    • /
    • pp.148-151
    • /
    • 2002
  • In order to prevent the failures of underground distribution power cables we need to measure insulation condition in the field. Until now we used DC high voltage as a power source for the cable diagnosis but it was not proper method to the XLPE insulation cables because DC high voltage can affect sound insulation and can't diagnose exactly insulation degradation. For these reasons we imported isothermal relaxation current measurement system called by KDA-1 from germany but it's reliability did not proved in our URD cables. DC voltage decay measurement system was developed by domestic company but they don't have field experience. In this paper we tried to prove reliability of these two systems in the field. Through the field diagnosis and Ac breakdown test the two systems showed similar results.

  • PDF