• Title/Summary/Keyword: CV Underground Cable

Search Result 17, Processing Time 0.037 seconds

Effect of the Capacitance for 600V CV Cable Applying Outdoor Electricity Facilities (옥외전기시설물에 사용되는 600V CV케이블 정전용량의 영향)

  • Lee, H.G.;Ha, T.H.;Bae, J.H.;Him, D.K.;Kim, S.W.;Lee, J.I.
    • Proceedings of the KIEE Conference
    • /
    • 2002.11b
    • /
    • pp.323-325
    • /
    • 2002
  • Because of the progress of civilization, outdoor electricity facilities as a street light, signal light and standing signboard etc. have being increased rapidly. Therefore the application of underground distributing wires is largely expended. In this paper, capacitance for the kinds of 600V CV cable is measured and leakage current for underground cable is calculated. The measurement of capacitance is done which there are defects of cable sheath or not Calculated leakage current is applied to choose the circuit breaker and the like.

  • PDF

A Study on the Remain Life with Aging in 22kV CV cable (22kV 전력케이블의 열화 판정에 관한 연구)

  • Lee, Kwan-Woo;Mok, Young-Soo;Kim, Bo-Kyeong;Park, Bok-Ki;Park, Dae-Hee
    • Proceedings of the KIEE Conference
    • /
    • 2003.10a
    • /
    • pp.19-21
    • /
    • 2003
  • In this paper, we studied on life-decision of underground cable of live-lines state. As all equipments have been wear, underground cables decided design-life on the whole 30 years because underground cable have been occurred aging as time goes. CV cable has been become about 30 years after installation in the South Korea, is come to a important point of time with estimation about life. Study target cable is 22 kV CV cables in this point of view and installation cable is about 10 years before and behind. Measurement method used dc leakage method of live-lines state that applied voltage of 50V in neutral point and data is analyzing result that is measured during 5 years. In this result, insulation resistance could confirm that change according to season and cause is effect of humidity, seasons and load current. Also, according as data is gone aging, insulation resistance by Weibull distribution could confirm functionally its decrease. As a result, the aging speed of cable that water tree is gone could confirm fastness very. Numerical analysis result, cable that water tree is not gone could confirm that life of cable that has passed 10 years remains about $10{\sim}20$ years.

  • PDF

APPLICATION OF DIRECT LEAKAGE CURRENT METHOD FOR AGING DIAGNOSIS EVALUATION (열화 진단 평가를 위한 직류 누설법의 활용)

  • Lee, Kwan-Woo;Park, Dae-Hee
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2001.11b
    • /
    • pp.149-152
    • /
    • 2001
  • In this paper, aging diagnosis method of CV cable was investigated. CV cable was designed for the sake of using during 30 years. Therefore it was important to evaluate the cable's remaining life because CV cable used for power transmission line since 1970's. CV cable was mainly installed at the underground owing to the environmental condition. If the cable accident occurred, it needs the much time for the accident recovery and the much damage at the industrial activity. therefore, this paper should study the direct leakage current method, a sort of the cables' aging test method

  • PDF

APPLICATION OF DIRECT LEAKAGE CURRENT METHOD FOR AGING DIAGNOSIS EVALUAT10N (열화 진단 평가를 위한 직류 누설법의 활용)

  • 이관우;박대희
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2001.11a
    • /
    • pp.149-152
    • /
    • 2001
  • In this paper, aging diagnosis method of CV cable was investigated. CV cable was designed for the sake of using during 30 years. Therefore it was important to evaluate the cable's remaining life because CV cable used for power transmission line since 1970's. CV cable was mainly installed at the underground owing to the environmental condition. If the cable accident occurred, it needs the much time for the accident recovery and the much damage at the industrial activity. therefore, this paper should study the direct leakage current method, a sort of the cables'aging test method.

  • PDF

AC Breakdown Characteristics for 22.9kV CV Power Cable Before and After Cyclic Aging for 14days (22.9kV CV 전력케이블의 14주기 고온 열화에 대한 교류파괴특성)

  • 윤대혁;김위영;박민호;박태곤
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2001.07a
    • /
    • pp.601-604
    • /
    • 2001
  • 22.9 kV CV power cable is very important factor of underground distribution power line. Cyclic aging for 14days is performed to remove a large amount of the volatiles found in freshly manufactured cable. In this paper, we examined AC breakdown characteristics of CV power cable before and after cyclic aging for 14days. As the result, even if there were some exceptions, the AC breakdown voltage before aging was lower than that after aging, but most of the results were that the AC breakdown voltage after aging was lower than that before aging.

  • PDF

Determination of Proto Type for 345kV CV Cable Accessories (345kV CV 케이블 접속함의 Proto Type 선정)

  • Lee, S.K.;Kim, I.T.;Son, S.H.;Choi, S.G.;Huh, G.D.;Park, W.K.
    • Proceedings of the KIEE Conference
    • /
    • 1998.07e
    • /
    • pp.1629-1631
    • /
    • 1998
  • Crosslinked polyethylene (XLPE) insulated cables are now widely used all over the world for extra-high voltage underground transmission systems. Prefabricated type (compression type) joint has developed in order to shorten the assembly time and lower the possibility of contamination at site by many companies in the world. For outdoor termination, to control the electric field distribution as uniform as possible, especially for the use of extra-high voltage system. much of products are adopting the oil-impregnated condensor cone type instead of electric field control element which uses the permitivity of it only (not capacitance). For Gas-immersed termination, dimension of outer insulation bushing was determined by IEC Publication 859. The highest voltage of underground power cable system is 345kV now, in Korea. We have much of experiences of the development of prefabricated type accessories for CV cable systems (154kV, 161kV, 230kV level). So it was possible to inspect the proto type of accessories for 345kV CV cable system and seems that the need time for the development of products is reduced.

  • PDF

Effect of compact HTS superconduction power cable and investigation of its economical efficiency (콤팩트형 고온 초전도 전력 케이블의 도입 효과와 경제성 검토)

  • 최상봉;성기철;조전욱;정성환;김대경
    • Proceedings of the Korea Institute of Applied Superconductivity and Cryogenics Conference
    • /
    • 2001.02a
    • /
    • pp.108-111
    • /
    • 2001
  • This paper presents the possible application of a HTS superconducting power cable for transmitting electric power in metropolitan areas, reflecting its important distinction such as compactness for installation in underground ducts and considerably economical efficiency comparable to present underground cables. In this paper, we investigated characteristic and market scale compact HTS transmission cable which is possible to install in underground ducts. And reviewed its economical efficiency comparing to present existed CV cable from point of view such as cost for cable construction and duct or tunnel installation.

  • PDF

Analysis of Sheath Induced Voltage in Transmission Power Cable Connected with CCPU (방식층 보호장치의 설치에 따른 지중송전케이블 시스 유기전압 해석)

  • Lee, Jun-Sung;Lee, Jong-Beom;Kim ,Young
    • The Transactions of the Korean Institute of Electrical Engineers A
    • /
    • v.49 no.1
    • /
    • pp.19-25
    • /
    • 2000
  • This paper describes the sheath induced voltage in underground transmission cable system which will be operated with cable cover protection unit(CCPU). Simulation was carried out to analyze the sheath induced voltage in the real cable system which was installed by 154㎸ CV cable in the case with and without CCPU. The sheath induced voltage will be also analyzed according to the change of grounding method, fault resistance and fault angle. Simulation was performed using EMTP and ATP Draw, the simulation results show whether the CCPU in necessary or not in underground transmission power cable system.

  • PDF

A Study on the Calculation of Transmission Current-Carrying Capacity by Horizontal Arrangement Type in the Installation Methods of 154kV XLPE 600㎟ Power Cable Buried Ducts in Ground (154kV XLPE 600㎟ 지중관로 수평배열 형태별 허용전류용량 산정에 관한 연구)

  • Kim, Se-Dong;Yoo, Sang-Bong
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.30 no.3
    • /
    • pp.53-58
    • /
    • 2016
  • The underground transmission lines which have been built to expand the suppling facilities will be continuously accompanying with high growth of the increase of power demand in the metropolitan area in recent years. So, it is necessary to maximize the ability and reliability of power supply with the current-carrying capability of the underground transmission lines. Design criteria of KEPCO is to be presented and used frequently. But it has to be studied about the installation methods of power cable buried in ground. In this study, we used the program for calculating the current-carrying capability of underground transmission power cables. We estimated the maximum permissible current values by the horizontal arrangement in the installation methods of power cable(154kV XLPE $600mm^2$) buried ducts in ground. To see the general tendency of the analysis, we researched a statistical analysis with such parameters as the maximum permissible current values. Through the regression analysis, we analyze the most highly values of the maximum permissible current on the Ra type duct arrangement.

Estimate of Insulation thickness for EHV XLPE power cable (345kV CV케이블의 절연두께 산정)

  • Choi, Bong-Nam;Yun, Duck-hwan
    • Proceedings of the KIEE Conference
    • /
    • 2001.07c
    • /
    • pp.1801-1803
    • /
    • 2001
  • At present the under ground power transmission systems have installed until 154KV XLPE power cable in Korea But, the large capacity underground power transmission systems have been required gradually with the increasing demand of electric power. Therefore, our company has developed 345KV XLPE cable. This paper describes the estimate details of the insulation thickness according to weibull plotting for 345KV XLPE power cable.

  • PDF