• 제목/요약/키워드: CV Cable

검색결과 63건 처리시간 0.033초

도체 수밀형 전력케이블의 가교잔사 가스에 의한 직선접속재 부풀음 현상 방지 대책 (The solution for preventing the expansion of cable joint caused by methane($CH_4$) gas to Water proof type of power cable)

  • 김종원;이기수;백흠수;최봉남;박희철
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2000년도 하계학술대회 논문집 C
    • /
    • pp.2020-2022
    • /
    • 2000
  • The cross-linked polyethylene(herein after XLPE) insulated power cable emit the methane($CH_4$)gas in the course of chemical cross-linking process. The general stranded conductor easily discharge this methane gas through the gap of each stranded wires. But the special stranded conductor that filled with semi-conducting rubber compound to prevent water penetration which is applied to water proof type of cable(22.9kV CN/CV-W), disturb the methane gas emission. The pre-mold type cable joint shall be expanded gradually by emit of gas left in XLPE insulation. For example, sometimes the corona problem outbreak on a new power distribution line, resulted from the gap between the sleeve and semi-conductive layer of cable joint. If above mentioned problem especially happened on the way of operating. We have to shut down the line and try to discharge the methane gas in cable joint. In this point, we would like to explain the mechanism of methane gas & cable joint and our test result briefly. At last, we are pleased to introduce the solution for preventing reoccurrence of this problem.

  • PDF

배전선로 가공인입 케이블 중성선 운영방법 개선에 관한 연구 (A Study on Neutral Conductor Improvement for 0.6/1kV XLPE insulated Power Cable)

  • 장정일
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2015년도 제46회 하계학술대회
    • /
    • pp.1473-1474
    • /
    • 2015
  • 0.6/1kV CV 전선은 저압 지중선용 또는 가공저압배전선로 및 복잡한 인입선 정비를 위한 가공인입 간선용으로 사용한다. CV 전선은 내열성이 높고 내약품성 및 내유성이 우수하며 시공에 따른 미관성이 우수하여 가공인입용으로 적용이 증가하는 추세이다.[10] 가공인입용 CV 전선내 전압선과 중성선 단면적은 동일하게 제작, 현장에 적용되고 있다. 본 논문에서는 3상4선식 0.6/1kV CV 전선을 가공인입선에 적용시 중성선의 단면적을 전압선 단면적보다 평균 47%를 축소 개발, 현장에 적용하여 최적으로 중성선을 운영하는 방안을 제시하였다.

  • PDF

직류내전압 시험이 전력케이블(CV) 절연체에 미치는 영향연구 (A Study on the DC Voltage Withstand test for the Ageing of XLPE Power Cable)

  • 이준;임용배;김종서
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 1999년도 추계학술대회 논문집
    • /
    • pp.613-616
    • /
    • 1999
  • Polyehtylene[PE] in polymer insulation materials of used power cable have carried out in abundance of experiment and study for electrical conduction, insulation breakdown, dielectric character and so on. when apply to field for power cable to make PE, application of DC withstand test to put in practice for inspection is get to effect accumulated space charge. In this paper, to make use of Pulsed Electro-Acoustic(PEA), It is analysis to take shape space charge under AC and DC, clear up the point at issue for DC withstand test impressing

  • PDF

지중송전케이블의 불완전 순환전류에 관한 연구 (A Study on unperfected circuiting current of undergrounded cable)

  • 이관우;이용성;김보경;박복기;박대희
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2004년도 춘계학술대회 논문집 방전 플라즈마 유기절연재료 초전도 자성체연구회
    • /
    • pp.3-6
    • /
    • 2004
  • In this paper, we studied on permissible current of unperfected earthing for cross-bond system. The factors of unperfected earth were jacket damage, cross-bonding mistake, arrestor damage, effect of other circuit but we only studied permissible current of arrestor or jacket damage. In the result, we earned that permissible current of normal 154[[kV]] CV $1C{\times}400SQMM$ cable is 760[A] but current of unperfected earthing cable is 76[A], unperfected earthing confirmed that accident of underground cable could occur. So, we could confirmed that Earthing resistance of unperfected earthing need to limit.

  • PDF

초초고압 CV Cable용(用) 조립형 직선 접속함에서의 Stress Relief Cone 계면압력 최적화에 관한 연구 (A Study on the Optimization of Interfacial Pressure for the Stress Relief Cone in the Ultra-High Voltage Level Prefabricated Type Joint Box)

  • 백주흠;백승엽;이수길;허근도;박완기
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1998년도 하계학술대회 논문집 E
    • /
    • pp.1614-1616
    • /
    • 1998
  • Insulation performance of major components of prefabricated joint such as epoxy insulation unit and premolded rubber cone are guaranteed by material selection design and proper manufacturing. On the other hand insulation performance of the interfaces between the premolded rubber cone and the epoxy insulation unit and the cable insulation is maintained by keeping the premolded rubber cone to close contact with such insulation by spring. Electric characteristics of a interface depend on the contact pressure, but the required characteristics are assured so far as a proper contact pressure is maintained. In this report, the interfacial pressure by pressure sensors both in the early stage and after heating cycle were measured and the simulation by FEM program were presented. The comparison of these two results show that interfacial pressure could be controlled optimally by changing the spring length and lubricant state of the interface.

  • PDF

전력 케이블 절연재에 대한 DC절연파괴강도특성 고찰 (Investigation on DC Breakdown Strength Characteristics of Power Cable Insulation)

  • 이한주;정의환;조성훈;윤재훈;임기조
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2010년도 하계학술대회 논문집
    • /
    • pp.86-86
    • /
    • 2010
  • Recently, CV, CNCV, CNCV-W cable are used to transmit and distribute electric power. And a lot of researchers put more effort to realize high performance. The dielectric breakdown strength characteristic is a standard to design insulators. Examination of that is a main factor to determine long term insulation performance, which is used to diagnose Insulation deterioration. In this paper, we prepared XLPE, XLPE/nano-filler, LDPE/nano-filler for comparing each of the dielectric breakdown strength characteristics.

  • PDF

실리콘 처리에 의한 수트리 열화케이블의 절연회복 (Insulation rehabilitation of water tree aged cables by silicone treatment)

  • 김주용;송일근;한재홍;이동영;문재덕
    • 조명전기설비학회논문지
    • /
    • 제14권1호
    • /
    • pp.14-21
    • /
    • 2000
  • 본 논문은 수트리 열화된 가교폴리에틸렌(XLPE) 절연 지중케이블의 절연회복을 위해 개발된 실리콘 처리 기법의 현장적용 가능성을 검토하기 위해 수트리 열화된 325 $\textrm{mm}^2$ CN/CV 케이블을 수거하여 실리콘 처리하고, 시간의 경과에 따른 절연성능 향상도를 분석한 것이다. 시료 케이블의 절연회복을 평가하기 위해 교류절연파괴시험을 실시했다. 또 실리콘 처리케이블의 평가를 위해 진단시험 및 케이블 특성평가를 수행했다. 실리콘 처리후 1년 경과 시료 케이블올 분석한 결과, 실리콘액(silicone fluid)과 수분이 효과적으로 결합해 절연파괴강도가 상당히 증가한 것으로 나타났다. 실험결과를 종합해 볼 때 수트리로 열화된 케이블의 절연성능 향상에 실리콘 처리가 효과적인 것으로 나타났다.

  • PDF

활선 고전력 케이블의 절연저항을 측정하기 위한 시스템 설계 및 측정결과 (Development of System and Measured Results for Measuring Insulation Resistance of High-Power Cables in Operation)

  • 엄기홍;김보경
    • 한국인터넷방송통신학회논문지
    • /
    • 제16권4호
    • /
    • pp.165-170
    • /
    • 2016
  • 우리 나라에서 발전소가 전기를 생산하고 고전압 전력을 공급하기 위하여 채택한 XLPE 케이블(또는 CV케이블)은 포설된지 40년에 이르고 있다. 설치환경 및 사용조건에 다르겠지만, 설치 후 운전 상태에 있는 CV 케이블은 6~8년의 기간이 경과하면 열화가 발생하기 시작하고, 상태가 나빠지는 경우, 절연 파괴현상으로 인한 휴전 및 화재 사고가 발생한다는 많은 사례 보고가 있다. 근래에 포설한 케이블이라 할지라도 시공 불량이나 기타의 열악한 주변 환경으로 인한 악조건 상태에 노출되는 경우, 6~8년 미만의 시점에서도 사고가 발생할 수가 있다. 사고를 미연에 방지하기 위하여 케이블의 동작상 태를 정기적으로 감시 확인하여야 한다. 우리는 케이블의 사고를 체계적으로 감시 및 예방하기 위하여 측정 장비를 개발하였다. 이 논문에서 케이블의 절연 상태의 열화 상태를 감시하기 위하여 한국서부발전 주식회사(Korean Western Power Co. Ltd.)에 설치하여 운영 중에 있는 장비의 설계와 그 장비를 사용하여 측정한 결과즉, 케이블의 열화 과정을 나타내는 결과를 제시한다.

화력 발전소의 터빈 발전기 부하단에 설치된 XLPE 케이블의 부하전류 측정 (Measurements of Load Current of XLPE Cables Installed at the Load Terminal of Turbine Generator in Operation at Thermoelectric Power Station)

  • 엄기홍;김보경
    • 한국인터넷방송통신학회논문지
    • /
    • 제17권1호
    • /
    • pp.207-212
    • /
    • 2017
  • 화력 발전소의 터빈 발전기에서 생산된 전기를 운반하기 위하여 부하 측에 설치된 케이블은 XLPE 케이블(또는 CV케이블)이다. 사고 발생시 저압 시스템을 포함하는 대부분의 설비들에 정전사고가 발생하여 막대한 경제적 손실을 초래한다. 설계부터 시공 및 관리를 더욱 철저히 해야 한다. 설치환경 및 사용 조건 부하량 등에 따라 차이가 있겠지만, 증설과정, 부적절한 설계 등으로 인하여 케이블의 단면적이 부족할 경우가 발생하며, 운전 전류에 의하여 초과된 허용온도는 케이블의 열화 상태를 초래한다. 우리는 케이블의 사고를 체계적으로 감시 및 예방하기 위한 측정 장비를 개발, 한국서부발전 주식회사(Korean Western Power Co. Ltd.)에 설치하여 활선상태에서 케이블에 흐르는 부하전류를 측정하였다. 이 논문에서 우리는 케이블에 흐르는 부하전류를 측정하고, 측정된 부하전류에 의한 부하특성의 파악 및 IEC규정에 의한 허용전류와 비교하여 케이블의 도체온도를 파악하기 위한 기초자료를 제시한다.

국내 지중 케이블 고장현황 분석 (Failure Analysis of Underground Transmission Cable Systems)

  • 강연욱;조성배;곽방명;임헌의;윤형희
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1999년도 하계학술대회 논문집 E
    • /
    • pp.2377-2379
    • /
    • 1999
  • In order to analyze failure rates of underground transmission power cable systems in Korea, the survey has been performed for the failure cases of cables, joints, and terminations in CV, OF and POF cable systems which occurred from 1983 to 1998. During 16 years, the failure cases due to trips of the systems were 47 among the total 108 cases, These 47 cases could be divided into internal reasons(manufacture/installation, corrosion and degradation) of 16 cases and external reasons (external mechanical damages, lightning, fire. etc.) of 31 cases. For the 154 kV cable systems during 12 years from 1987 to 1998, total failure rate was 0.0057 [case/100C-km/year] and internal reason failure rate was 0.0020 [case/100C-km/Year], which is similar to those of foreign countries. Also, the many cases of internal reason failures occurred in the early stage after the operations due to incorrect installations. This implies that the installation process is very important and some diagnostic tests such as PD measurement are needed besides after laying test.

  • PDF