• Title/Summary/Keyword: Breaker

Search Result 940, Processing Time 0.028 seconds

A Trip Coil Fault Detection of Circuit Breaker (차단기 트립코일 이상감지 장치)

  • Youn, Ju-Houc;Lee, Jong-Hun;Park, Noh-Sik;Lee, Dong-Hea
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.25 no.2
    • /
    • pp.61-68
    • /
    • 2011
  • The circuit breaker of power distribution board is essential part for the protection of electrical disaster from load short, trouble of power system. For the normal operation of circuit breaker, trip coil of the circuit breaker can cut the mechanical contact of circuit breaker from the detection of power system troubles. This paper presents a design and experimental results of trip coil fault detection system for the real time monitoring of the circuit breaker. The designed system is consisted by the trip coil fault detector which is connected to the each circuit breaker and remote monitoring unit. The trip coil fault detector can detect the impedance and operating voltage of the trip coil, and the detected values are compared with the normal state. And the remote monitoring unit can be connected to the 32 channels of trip coil fault detectors by serial communication. From the designed system, the fault and normal states of the trip coil can be remotely monitored in real time. The designed system is verified by the practical circuit breaker of power distribution board. And the results shows the effectiveness of the designed system.

An Empirical Study on Malfunction of the Earth Leakage Circuit Breaker (전기적 노이즈에 의한 누전차단기의 오동작에 관한 실험적 연구)

  • Kim, Tae-Man;Kwon, Yong-Jun;Kee, Do-Hyung
    • Journal of the Korean Society of Safety
    • /
    • v.17 no.1
    • /
    • pp.45-53
    • /
    • 2002
  • The purpose of this study was to investigate effect of electrical noise on malfunction of the earth leakage circuit breaker. A three-way experiment for studying its malfunction was conducted, in which electrical products such as radio, alternating current are welder and cellular phone, distance from the earth leakage breaker to electrical products, and whether or not the earth leakage breaker is contained is contained in the steel box were employed as experimental variables. Eleven earth leakage breakers frequently used in real situations were tested in each experimental treatment. The electrical products were used for generating electrical noise that is known to be able to cause malfunction of the earth leakage breaker. The results showed that except a case for one of the 11 earth leakage breakers when the radio made by M company was located 30 cm ahead of the breaker, malfunction did not occur in any other experimental treatment. Consequently, it is suggested that the breaker should be normally used for preventing electricity-related accidents without fear of its malfunction in industrial sites.

Arc Extinguishment for Low-voltage DC (LVDC) Circuit Breaker by PPTC Device (PPTC 소자를 사용한 저전압 직류차단기의 아크소호기술)

  • Kim, Yong-Jung;Na, Jeaho;Kim, Hyosung
    • The Transactions of the Korean Institute of Power Electronics
    • /
    • v.23 no.5
    • /
    • pp.299-304
    • /
    • 2018
  • An ideal circuit breaker should supply electric power to loads without losses in a conduction state and completely isolate the load from the power source by providing insulation strength in a break state. Fault current is relatively easy to break in an Alternating Current (AC) circuit breaker because the AC current becomes zero at every half cycle. However, fault current in DC circuit breaker (DCCB) should be reduced by generating a high arc voltage at the breaker contact point. Large fire may occur if the DCCB does not take sufficient arc voltage and allows the continuous flow of the arc fault current with high temperature. A semiconductor circuit breaker with a power electronic device has many advantages. These advantages include quick breaking time, lack of arc generation, and lower noise than mechanical circuit breakers. However, a large load capacity cannot be applied because of large conduction loss. An extinguishing technology of DCCB with polymeric positive temperature coefficient (PPTC) device is proposed and evaluated through experiments in this study to take advantage of low conduction loss of mechanical circuit breaker and arcless breaking characteristic of semiconductor devices.

Analysis of Electric Shock Accident on 4.16 kV Class Circuit breaker for Power Plant (발전소용 4.16 kV급 차단기에서 감전사고 사례 분석)

  • Park, Nam-Kyu;Song, Jae-Yong;Kim, Jin-Pyo;Goh, Jae-Mo
    • Journal of the Korean Society of Safety
    • /
    • v.29 no.4
    • /
    • pp.54-60
    • /
    • 2014
  • This paper describes electric shock accidents on a 4.16 kV class circuit breaker for power plant. Electric shock accidents mostly involve damage of human life, in comparison with electrical fire, rate of human death tend to be higher in electric shock accidents. Specially, in a high voltage facilities rate of human death comprised about 43.7% by electric shock accidents. If electric shock accidents happen in a 4.16 kV class circuit breaker for power plant, then the power plant discontinue power production. Electric shock accidents in a power plant have a great ripple effect such as an electric power shortage. In this paper, we analyzed electric shock accidents on a 4.16 kV class circuit breaker for power plant. From the analysis results, we confirmed a cause of electric shock accidents on a 4.16 kV class circuit breaker, it happened by defect of interlock equipment or occurrence of breakdown between first feeder contactor and shielding plate. In order to reduce electric shock accidents on a 4.16 kV class circuit breaker, the power plant should consider improvement of interlock equipment and insulation of feeder contactor in circuit breaker.

Development of Extra-large Hydraulic Breaker (초대형 유압브레이커 개발)

  • Ahn, Kyubok
    • Journal of the Korea Academia-Industrial cooperation Society
    • /
    • v.16 no.5
    • /
    • pp.3081-3086
    • /
    • 2015
  • Development of a extra-large hydraulic breaker, which could be used for a 100 ton-class excavator were carried out Hot-firing tests were carried out. Before designing a hydraulic breaker, the analysis method to predict the performance such as impact energy and impact rate were studied. Based on the analysis result, the design and manufacture of a extra-large hydraulic breaker were performed, and the breaker were confirmed to operate successfully. The data of impact energy and impact rate were measured during the operation of the breaker, and were compared with the analysis result. The analysis result of impact rate anticipated well the test data, but that of impact energy showed a large difference with the test data. The extra-large hydraulic breaker were successfully developed and the analysis method of impact energy will be updated taking into account friction, hydraulic circuit, etc.

A Study on the Physical Characteristics of the Low-voltage Circuit Breaker Based on the Accelerated Degradation Test (가속 열화 시험에 따른 저압용 차단기의 물리적 특성에 관한 연구)

  • Sin dong, Kang;Jae-Ho, Kim
    • Journal of the Korean Society of Safety
    • /
    • v.37 no.6
    • /
    • pp.1-8
    • /
    • 2022
  • This study analyzed the characteristics of insulation resistance and operating time based on an accelerated degradation test of a low-voltage circuit breaker. The experimental sample used a molded case circuit breaker (MCCB) and an earth leakage circuit breaker (ELCB). After measuring the insulation resistance of the circuit breakers, the leakage current was affected by an external rather than an internal structure. Furthermore, the insulation resistance of the circuit breakers with accelerated degradation was measured using a Megger insulation tester. In the accelerated degradation test, aging times of five, ten, 15, and 20 years were applied according to a temperature derived using the Arrhenius equation. Circuit breakers with an equivalent life of ten, 15, and 20 years had increased insulation resistance compared to those with less degradation time. In particular, the circuit breaker with an equivalent life of ten years had the highest insulation resistance. Component analysis of the circuit breaker manufactured through an accelerated degradation test confirmed that the timing of the increase in insulation resistance and the time of additive loss were the same. Finally, after analyzing the operating time of the circuit breakers with degradation, it was confirmed that the MCCB did not change, but the ELCB breaker failed.

The Development of an Analysis Tool and the Performance Analysis of a Hydraulic Breaker System (유압 브레이커의 해석용 TOOL 개발 및 성능 분석)

  • Lee, Youngkyu;Sung, Wonjoon;Song, Changseop
    • Journal of the Korean Society for Precision Engineering
    • /
    • v.17 no.4
    • /
    • pp.189-196
    • /
    • 2000
  • In this study, the hydraulic breaker system was analyzed and the analysis tool using GUI was developed. The analysis on the system with the accumulator was included. from the parametric analysis, the effects of each factor were revealed. Through the simulation with varying parameters, the method to improve the performance of the hydraulic breaker system was presented. The analysis tool will help a man without special knowledge about programming analyzse the hydraulic breaker system. The result of this study will help improve the hydraulic breaker system in sight of "Blow energy" and "Blows per minute".ws per minute".uot;.

  • PDF

A Novel DC Solid-State Circuit Breaker for DC Grid (DC Grid를 위한 새로운 구조의 DC Solid-State Circuit Breaker)

  • Kim, Jin-Young;Kim, In-Dong;Nho, Eui-Cheol
    • The Transactions of the Korean Institute of Power Electronics
    • /
    • v.17 no.4
    • /
    • pp.368-376
    • /
    • 2012
  • According to developed distributed generators, Solid State Circuit Breaker(SSCB) is essential for high power quality of DC Grid. In this paper, a simple and new structure of DC SSCB with a fast circuit breaker and fault current limiter is proposed. It can help to choice low specification of elements because of the limiting of fault current and achieve economic efficiency for minimizing auxiliary SCRs. Also all of SCRs have little switching loss because they operate under ZVS and ZCS. Through simulations and experiments of short-circuit fault, the performance characteristic of proposed circuit is verified and a guideline is so suggested that the DC SSCB is applied for a different DC grid using formulas.

Study on the spring modeling of circuit breaker with spring operating mechanism (스프링조작기를 가진 고압회로차단기의 스프링 모델링에 관한 연구)

  • Lee, Seung-Kyu;Kim, Seung-Oh;Yoo, Wan-Suk;Sohn, Jeong-Hyun
    • Proceedings of the KSME Conference
    • /
    • 2007.05a
    • /
    • pp.991-996
    • /
    • 2007
  • Since the performance of the circuit breaker mainly depends on the spring operating mechanism, the analysis of the spring operating mechanism is required. The spring, especially closing spring, stores the deformation energy due to the compression and then accelerates the big loads rapidly in the circuit breaker. To accurately carry out the kinematic and dynamic analysis of the circuit breaker, the precise modeling of the spring behavior is necessary. In this paper, the static stiffness of the spring is captured by using the tester. When the spring is used in the circuit breaker, it is installed horizontally. Therefore, Sine excitation tests are carried out horizontal and vertical direction. Three types of spring models such as a linear spring model, modal spring model, and nodal spring model are suggested and compared with the experimental results.

  • PDF

Design of Vacuum Circuit Breaker Based on Dynamic Model (동적모델에 기반한 진공 회로차단기의 설계)

  • 권병희;안길영
    • Proceedings of the Korean Society of Precision Engineering Conference
    • /
    • 2003.06a
    • /
    • pp.1418-1421
    • /
    • 2003
  • The Vacuum circuit breaker is a kind of power circuit breaker and protect electric devices from over-current. In this paper we built a dynamic model of VCB driving mechanism using ADAMS. The development of the new circuit breaker with less energy and more compactable mechanism is focused. Through the dynamic model, the concept design of the new circuit breaker with less energy and more compactable mechanism is proposed, and then the detailed design is carried out through the design process based on the dynamic model.

  • PDF