• 제목/요약/키워드: Breakdown voltages

검색결과 248건 처리시간 0.03초

$SF_6-N_2$ 혼합가스에서 과도임펄스전압에 대한 V-t특성 (V-t Characteristics in $SF_6-N_2$ Mixtures for Transient Impulse Voltages)

  • 이복희;이경옥
    • 대한전기학회논문지:전기물성ㆍ응용부문C
    • /
    • 제50권9호
    • /
    • pp.456-465
    • /
    • 2001
  • In this paper, breakdown voltages in $SF_6-N_2$ mixtures were experimentally investigated to understand characteristics of dielectric strength and physical phenomena in nonuniform field disturbed by a needle shape protrusion. The test voltages are the lightning impulse$(\pm1.2/44 \mus)$ and the damped oscillatory impulse$(\pm400 ns / 0.83 MHz)$ voltages which can be occurred by the operation of disconnecting switches in gas-insulated switchgears(GIS). The effects of the polarity and wave shape of the test voltages, and the gas pressure on the V-t characteristics were in detail examined. The V-t characteristic curves were measured in different two ways : (1) one is the method by taking the maximum voltage recorded at or prior to breakdown against the time to breakdown, that is, the Procedures recommended in IEC 60060-1, (2) the other is the method by taking the voltage at the instant of chopping against the time to breakdown. As a result, the V-t characteristics of $SF_6-N_2$ mixtures in nonuniform electric field were significantly affected by the polarity and wave shape of the applied voltages. The positive breakdown voltages resulted in lower breakdown voltages in the time ranges considered, and the V-t curves for the negative oscillatory impulse voltage were extended over the longer time range. For the lightning impulse voltages, the V-t curves obtained by IEC Pub. 60060-1 were nearly same with the V-t curves obtained by the voltage at the instant of chopping against the time to breakdown. It is clear that the actual breakdown voltages were much lower than the maximum voltages appearing at or prior to breakdown because of the displacement current produced as a result of the dV/dt during the oscillatory transient voltage app1ication. The scattering of the negative actual breakdown voltages was much larger than that of the positive.

  • PDF

평등전계에서 AC 및 표준 뇌 임펄스 전압의 $SF_6/CF_4$ 혼합 가스 절연 파괴 특성 (Breakdown Characteristics of $SF_6/CF_4$ Mixtures Under AC and Standard Lightning Impulse Voltages in Uniform Field)

  • 성허경;박신우;황청호;김남렬;허창수
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2007년도 하계학술대회 논문집 Vol.8
    • /
    • pp.227-228
    • /
    • 2007
  • Although many studies have been carried out about binary gas mixtures with $SF_6$, few studies were presented about breakdown characteristics of $SF_6/CF_4$ mixtures. At present study the breakdown characteristics of SFJCF4 mixtures in uniform field was performed. The experiments were carried out under AC and standard lightning impulse (SLI) voltages. The sphere-sphere electrode whose gap distance was 1 mm was used in a test chamber. $SF_6/CF_4$ mixtures contained from 0 to 100% $SF_6$ and the experimental gas pressure ranged from 0.1 to 0.4 MPa. The results show that addition of $SF_6$ to $CF_4$ increase AC and SLI breakdown voltages. Under AC voltages the breakdown voltages of each mixture were linearly increased according to the quantity of $SF_6$. However under SLI voltages the breakdown voltages of each mixture were similar.

  • PDF

전력 반도체 $p^{+}n$ 접합의 해석적 항복전압 (Analytical Breakdown Voltages of $p^{+}n$ Junction in Power Semiconductor Devices)

  • 정용성
    • 대한전자공학회논문지SD
    • /
    • 제42권10호
    • /
    • pp.9-18
    • /
    • 2005
  • Si, GaAs, InP 및 $In_{0.53}Ga_{0.47}AS$ 계단형 $p^{+}n$ 접합에서의 항복전압을 위한 해석적 표현식을 유도하였다. 해석적 항복전압을 위해 각 물질에 대한 Marsland의 lucky drift 파라미터를 이용하여 유효이온화계수를 각각 추출하였고, 이의 이온화 적분을 통해 얻은 해석적 항복전압 결과는 $10^{14}cm\;^{-3}\~5\times10\;^{17}cm\;^{-3}$도핑 농도 범위에서 실험 결과와 $10\%$ 오차 범위 이내로 잘 일치하였다.

수직배치 구대평판 공기 갭에서 연소화염 존재시의 절연파괴 특성 (Breakdown Characteristics of a Vertical Sphere-Plane Air Gap in the Presence of Combustion Flame)

  • 김인식
    • 조명전기설비학회논문지
    • /
    • 제25권5호
    • /
    • pp.79-84
    • /
    • 2011
  • In this study, breakdown characteristics of a vertical sphere-plane air gap in the presence of combustion flame were examined under the application of a.c. and d.c. high-voltages in order to investigate the effect of flame on the dielectric strength of air. Propane gas is used as the fuel of the flame, and the temperature distribution of air around the flame is measured. The polarity effects for the d.c. voltages and breakdown voltages of air when applied both of a.c. and d.c. voltages were examined in the case of the variation of the gap length and the horizontal distance between the flame and the high-voltage sphere electrode. The influence of relative air density, electrification and shape changes of the flame as factors that affect the breakdown voltages were discussed.

임펄스전압에 대한 N2가스의 절연파괴특성 (Electrical Breakdown Characteristics of N2 Gas under Impulse Voltages)

  • 신희경;김동규;이복희
    • 조명전기설비학회논문지
    • /
    • 제25권2호
    • /
    • pp.131-136
    • /
    • 2011
  • This paper aims to examine the possibility of using an environmentally friendly $N_2$ as an alternative gas to $SF_6$. For this purpose, we have investigated breakdown characteristics of $N_2$ under impulse voltages in a quasi-uniform electric field gap. The 1.2/50[${\mu}s$] lightning impulse voltage, switching impulse voltages and oscillatory impulse voltages were applied at the test gap. The electric field utilization factor ranges from 0.5 to 0.8. The experimental data of $SF_6$ and $N_2$ acquired in the same experimental condition are presented in parallel for comparison. As a result, the breakdown voltages in $SF_6$ and $N_2$ are linearly increased with the gas pressure, also the breakdown voltages in $N_2$ are increased with increasing the gap distance and electric field utilization factor. The positive breakdown voltages are higher than the negative breakdown voltages. The nagative basic lightning impulse withstand level of 150[kV] in $N_2$ of about 0.5[MPa] is nearly equal to that in $SF_6$ of 0.15[MPa]. It is seen from the results obtained in this work that $N_2$ can be used as an eco-friendly alternative gas to $SF_6$ in distribution power equipment.

평등, 불평등 전계에서 AC전압의 $SF_6/CF_4$ 혼합가스 절연내력 특성 (Breakdown Characteristics of $SF_6/CF_4$ Mixtures under AC Voltages in Uniform, Nonuniform Field)

  • 성허경;황청호;김남렬;허창수
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2008년도 제39회 하계학술대회
    • /
    • pp.1334-1335
    • /
    • 2008
  • Although many studies have been carried out about binary gas mixtures with $SF_6$, few studies were presented about breakdown characteristics of $SF_6/CF_4$ mixtures. At present study the breakdown characteristics of $SF_6/CF_4$ mixtures in uniform and nonuniform field was performed. The experiments were carried out under AC voltages. The sphere-sphere electrode whose gap distance was 1 mm was used and the point-plane electrode whose gap distance was 3 mm was used in a test chamber. $SF_6/CF_4$ mixture contained 20% $SF_6$ and 80% $CF_4$ and the experimental gas pressure ranged from 0.1 to 0.5 MPa. The results show that addition of $SF_6/CF_4$ mixtures increase AC breakdown voltages. In uniform field the breakdown voltages of gas were linearly increased according to the pressure. However in nonuniform field the breakdown voltages of gas were increased nonlinearly.

  • PDF

III-V족 반도체에서 계단형 pn 접합의 해석적 항복전압 모델 (Analytical Model of Breakdown Voltages for Abrupt pn Junctions in III-V Binary Semiconductors)

  • 정용성
    • 대한전자공학회논문지SD
    • /
    • 제41권9호
    • /
    • pp.1-9
    • /
    • 2004
  • III-V족 반도체 GaP GaAs 및 InP의 계단형 pn 접합에서의 항복전압을 위한 해석적 식을 유도하였다. 해석적 항복전압을 위해 각 물질에 대한 이온화계수 파라미터를 이용하여 유효 이온화계수를 추출하였고, 이의 이온화 적분을 통해 얻은 해석적 항복전압 결과는 수치적 결과 및 실험 결과와 10% 오차 범위 이내로 잘 일치하였다.

InP 다이오드에서 항복전압의 해석적 모델 (Analytical Model for Breakdown Voltages of InP Diodes)

  • 정용성
    • 전자공학회논문지 IE
    • /
    • 제44권1호
    • /
    • pp.10-14
    • /
    • 2007
  • InP의 전자와 정공의 이온화계수로부터 추출한 유효이온화계수를 이용하여 InP 다이오드의 항복전압을 위한 해석적 표현식을 유도하였다. 해석적 항복전압 결과를 $N_D=6\times10^{14}cm^{-3}\sim3\times10^{17}cm^{-3}$의 도핑 농도에서 수치적 결과 및 실험 결과와 비교하였다. 각 농도에 따른 해석적 항복전압은 수치 해석적 결과와 매우 잘 일치하였고, 실험 결과와는 10% 이내의 오차로 잘 일치하였다.

불평등전계 중에서 $SF_{6}-N_{2}$ 혼합기체의 절연파괴 특성 (Breakdown Characteristics of $SF_{6}-N_{2}$ Mixtures in Nonuniform electric Field)

  • 이복희;이경옥
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2000년도 하계학술대회 논문집 C
    • /
    • pp.1999-2001
    • /
    • 2000
  • Impulse breakdown voltage characteristics of sulphur-hexafluoride/nitrogen ($SF_{6}-N_{2}$) mixtures were presented. The applied voltages were the positive and negative lightning impulse (1.2/44${\mu}s$) and oscillating impulse ($0.4{\mu}s$/2.08MHz) voltages. The predischarge current was observed to clarify the breakdown mechanism. The electrode system was consisted of plane to plane configuration with a needle-shaped protrusion whose length and diameter are 10mm and 1mm. The measurements were carried out at the gas pressure of mixtures up to 0.5MPa with nitrogen concentrations varying from 5 to 20%. The electrical breakdown in $SF_{6}-N_{2}$ mixtures develops with steplike pulses in leader mechanism. The minimum breakdown voltages for the negative lightning and oscillating impulse voltages were higher than those for the positive.

  • PDF

Evaluation on the Lightning Breakdown Voltages of Palm Oil and Coconut Oil under Non-Uniform Field at Small Gap Distances

  • Thien, Yee Von;Azis, Norhafiz;Jasni, Jasronita;Kadir, Mohd Zainal Abidin Ab;Yunus, Robiah;Ishak, Mohd Taufiq;Yaakub, Zaini
    • Journal of Electrical Engineering and Technology
    • /
    • 제11권1호
    • /
    • pp.184-191
    • /
    • 2016
  • In recent years, there are a number of studies that have been carried out to explore the alternative for Mineral Oil (MO) as dielectric insulating fluid in transformers due to the increasing tight regulation on safety and environment. Vegetable oils have been identified as suitable candidate since it is biodegradable, non-toxic and high flash/fire points which ensure more in-service safety. Among the types of vegetable oils considered for transformers application are Palm Oil (PO) and Coconut Oil (CO). This paper presents an experimental study on the lightning breakdown voltages of PO and CO under non-uniform electric field based on needle-sphere electrodes configuration at 3 small gap distances. The type of PO used in this study is Refined Bleached and Deodorized Palm Oil (RBDPO) Olein. The main focus of this study is to examine the lightning breakdown performance of RBDPO and CO under different test conditions and assess its suitability as dielectric insulating fluid in transformers. The effect of voltage polarities (positive and negative) and testing methods (rising-voltage, up-and-down and multiple-voltage) were investigated. The data obtained from all tests were analysed by Weibull distribution in order to determine the withstand voltages for each type of oils. It was found that the breakdown voltages of RBDPO and CO are comparable with MO under positive lightning impulse. Under negative lightning impulse, the breakdown voltage of MO is slightly higher than RBDPO and CO. There is no significant effect of testing methods and voltage polarities on lightning breakdown voltages of RBDPO and CO. Based on the statistical analysis, it is found that the breakdown voltages of RBDPO and CO at 1% probability are slightly lower than MO.