• Title/Summary/Keyword: Biohazard

Search Result 17, Processing Time 0.023 seconds

A Study on the Prediction of Indoor Environment in Bio Safety Level 3 Laboratory According to Biohazard Scenario (생물안전 3등급(BSL3)시설의 생물재해 시나리오에 따른 실내 공기환경예측에 관한 연구)

  • Park, Hyun-Jin;Hong, Jin-Kwan
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.22 no.11
    • /
    • pp.745-750
    • /
    • 2010
  • Since the implementation of the LMO Law in Korea, the importance of the design qualification of BSL3 lab. is emphasizing. In this study, multizone simulation for three kind of biohazard scenarios using CONTAM is performed for design qualification of BSL3 lab. Also, in the case of unexpected spread of contaminants such as Influenza A virus(H1N1) in BL3 zone, the design qualification is carried out for diffusion and decontamination of contaminants according to differential pressure of BSL3 anteroom and door area of BSL3 lab. Also, in this study, appropriateness of laboratory room differential pressure and air flow rate to maintain pressure difference between laboratory rooms, and energy consumption due to air change rate variation according to door area in BL3 lab. Simulation results show that these approach methods are used as a tool for the design and verification of BL3 lab.

Cellular Risk Assessment of Cells Exposed to Extremely Low Frequency Electromagnetic Fields (극저주파 자기장 노출에 의한 세포 유해성 평가)

  • Kang, Heungsik;Lee, Seongpyo;Noh, Myunggyu;Kim, Ki-Jung;Kim, Keekwang
    • Journal of Digital Convergence
    • /
    • v.19 no.5
    • /
    • pp.207-214
    • /
    • 2021
  • Humans are environmentally exposed to various electromagnetic fields, but the evaluation of the harmfulness of electromagnetic field and the development of a system therefor are still incomplete. We aimed to develop a system for evaluating biohazard against electromagnetic fields, and to determine biohazard through the system. An extremely-low frequency magnetic field generator was designed and manufactured, and the output reliability of the device was verified. Using this device, the effect on the formation of cellular stress-granules and the cell cycle progression of cells exposed to high magnetic fields of 6 mT and 60 Hz was confirmed. As a result, exposure to high magnetic fields of 6 hr, 12 hr and 36 hr did not affect the formation of cell stress-induced granules and the cell division cycle. These results are an important basis for the determination of biohazard to the extremely-low frequency high magnetic field.

A Study on Verification for the Design of Bio Safety Level 3 Laboratory by using Multi-zone Simulation (멀티죤 시뮬레이션을 이용한 생물안전 3등급(BSL3)시설의 설계 검증에 관한 연구)

  • Lee, Hyun-Woo;Choi, Sang-Gon;Hong, Jin-Kwan
    • Proceedings of the SAREK Conference
    • /
    • 2009.06a
    • /
    • pp.745-750
    • /
    • 2009
  • In Korea, since the implementation of the GMO Law, the intrest of biosafety level 3(BL3) lab. is increasing. In this study, using CONTAM which is applying multizone modelling, the multizone simulation for design verification of BL3 lab. was performed. In BL3 lab., because required air change rate is greater than general estimated air-conditioning load and it is difficult to maintain room pressure difference efficiently, to maintain pressure difference between laboratory rooms is important through sealing condition of doors and proper airflow control of laboratory rooms. In this study, about BL3 lab.(M. tuberculosis research lab.), the multizone simulation for four kind of biohazard scenarios was performed in the case of unexpected spread of contaminants in the laboratory room, anteroom, corridor and inside of BSC. Multizone simulation results show that these approach methods are used as a tool for the design and verification of BL3 lab.

  • PDF

An Analytical Study on the Prediction of Indoor Air Quality and the Reduction of Air Conditioning Load in Bio Safety Level 3 Laboratory (생물안전 3등급시설의 공기환경 예측 및 공조부하 절감에 대한 해석)

  • Hong, Jin Kwan;Park, Hyun Jin
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.24 no.11
    • /
    • pp.813-822
    • /
    • 2012
  • In this study, the multizone simulation for biosafety of BSL3 lab. and energy simulation are carried out simultaneously by using linked model of CONTAM and TRNSYS. In BSL3 lab., annual energy consumption is approximately five to ten times more than the magnitude of the office building. This is because required air change rate is extremely large and it is difficult to maintain room pressure difference efficiently. To maintain pressure difference between laboratory rooms through sealing condition of doors and proper airflow control is significant. In this study, to predict indoor environment of the BSL3 lab.(Influenza A research lab.), the multizone simulation for four kinds of biohazard scenario is also performed as part of risk assessment. Multizone and energy simulation results by using linked model show that these approaches are used as a tool for the energy efficient design and operation method for the safer BSL3 lab. facilities.

A Study on Verification for the Design of Bio Safety Level 3 Laboratory by using Multi-zone Simulation (멀티죤 시뮬레이션을 이용한 생물안전 3등급(BSL3)시설의 설계 검증에 관한 연구)

  • Lee, Hyun-Woo;Choi, Sang-Gon;Hong, Jin-Kwan
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.21 no.12
    • /
    • pp.671-677
    • /
    • 2009
  • In Korea, since the implementation of the LMO Law, the interest of biosafety level 3(BL3) lab. is increasing. In this study, using CONTAM which is applying multizone modelling, the multizone simulation for design verification of BL3 lab. is performed. In BL3 lab., because required air change rate is greater than general estimated air-conditioning load and it is difficult to maintain room pressure difference efficiently, to maintain pressure difference between laboratory rooms is important through sealing condition of doors and proper airflow control of laboratory rooms. In this study, about BL3 lab,(M. tuberculosis research lab.), the multizone simulation for four kind of biohazard scenarios is carried out in the case of unexpected spread of contaminants in the laboratory room, anteroom, corridor and inside of BSC. Multizone simulation results show that these approach methods are used as a tool for the design and verification of BL3 lab.

A Study on the Risk Assessment and Reduction of Initial Construction Cost in a Biosafety Laboratory According to Improvement of Supply and Exhaust Method (급배기 방식 개선에 따른 생물안전 밀폐시설의 Risk Assessment와 초기 건설비 저감에 대한 연구)

  • Hwang, Ji Hyun;Hong, Jin Kwan;Ju, Young Duk
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.25 no.10
    • /
    • pp.534-539
    • /
    • 2013
  • In general, entire supply air of the BSL3 laboratory should be vented to the outside for its biosafety and the air conditioning system should always be operating to maintain a room pressure difference. In this regard, annual energy consumption is approximately five or ten times greater than the magnitude of the office building. In addition, to adjust room pressure difference to the set value efficiently, the supply and exhaust duct system are installed in each room of the BSL3 lab. Thus, initial construction cost is extremely high. In this study, multizone simulation is performed to estimate maintaining the appropriate room pressure difference in the case of changing model A (each room supply and exhaust system) to model B (each zone supply and exhaust system) for verification of the BSL3 lab biosafety. Also, in the case of these two models, the multizone simulation for three kinds of biohazard scenario is performed as part of risk assessment. The analysis of initial construction cost of two models is conducted for comparison. According to the studies, initial construction cost of model B is less than about 22% of existing model A. Moreover, biosafety of the BSL3 lab is still maintaining in the case of the two models.

Properties of Extremely Low Frequency Electromagnetic Fields and their Effects on Mouse Testicular Germ Cells

  • Kim, Yeon-Sook;Lee, Suk-Keun
    • International Journal of Oral Biology
    • /
    • v.35 no.4
    • /
    • pp.137-144
    • /
    • 2010
  • To evaluate the biohazard properties of an extremely low frequency electromagnetic field (ELF-EMF), we explored the physical properties of the ELF-EMF that generates the electric current induction in the secondary coil from the chamber of a primary solenoid coil. We subsequently explored the biological effects of a strong alternating electromagnetic field (EMF), ranging from 730-960 Gauss, on the mouse testis. Mice were exposed to an alternating EMF field induced by a rectangular electric current at 1, 7, 20, 40, and 80 Hertz, for 1, 3, 5, and 7 hours. The mouse testes were examined for proliferative activity and apoptosis using the in situ terminal deoxynucleotidyl transferase (TdT) method and by immunostaining of proliferating cell nuclear antigen (PCNA), respectively. We found that the electric currentm induction increased in the 6-8 Hertz range, and that exposure to an ELF-EMF induced the apoptosis of mouse spermatocytes. In situ TdT staining was found to be most prominent in 7 Hertz group, and gradually reduced in the 20, 40, and 80 Hertz groups. These data suggest that a strong EMF can induce reproductive cell death within a short time, and the harmful effects of the EMF are maximal at low frequency alternating EMFs.