• Title/Summary/Keyword: Arcing current

Search Result 114, Processing Time 0.026 seconds

The Flow Analysis of Arc in LG Hybrid Interrupter Using PHOENICS Code (PHOENICS Code를 이용한 자력팽창 소호부 내 아크유동해석)

  • Lee, J.C.;Lee, B.W.;Oh, I.S.
    • Proceedings of the KIEE Conference
    • /
    • 2001.04a
    • /
    • pp.44-46
    • /
    • 2001
  • This paper describes the use of the PHOENICS CFD package for the simulation of the high-current period of the arcing process in a hybrid rotating arc/auto expansion by interrupter. The operating principle of this device depends on rapid arc rotation due to the magnetic field created by the fault current through a coil which is mounted on contacts and also relies on the principle of thermal expansion created by arc energy in extinguishing chamber and finally causes pressure rise in expansion volume. This paper is divided into three main sections. The first gives a brief overview of the interrupter. The second section gives a full description of the methods used in the calculation. The final section presents some sample results for the hybrid interrupter.

  • PDF

A Simulation of Lightning Faults Reducing Effects on the 154 kV Transmission Tower by Auxiliary Grounding (보조접지선 시공에 의한 송전선로의 내뢰성 향상효과 모의)

  • Kwak, Joo-Sik;Shim, Jeong-Woon;Shim, Eung-Bo;Choi, Jong-Gi
    • Proceedings of the KIEE Conference
    • /
    • 1997.07e
    • /
    • pp.1843-1846
    • /
    • 1997
  • This paper describes the fault reducing effects of the 154 kV transmission tower by auxiliary grounding from the top of the tower to ground. The grounding surge impedance of the auxiliary grounding system is calculated by CDEGS(:Current Distribution Electromagnetic Interference Grounding and Soil Structure Analysis), and the critical lightning back flashover current and arcing horn dynamic characteristics are simulated by EMTP/TACS(:Electromagnetic Transient Program/Transient Analysis of Control Systems). The calculated results of total LFOR(Lightning Flashover Rate) shows that the LFOR can be reduced from 5.2(count/100km. year) to 3.4 by auxiliary grounding on the 154 kV transmission tower with one ground wire shielding system.

  • PDF

CAE Analysis of $SF_6$ Arc Plasma for a Gas Circuit Breaker Design (가스차단기 최적설계를 위한 $SF_6$ 아크 플라즈마 CAE 해석)

  • Lee Jong C.;Ahn Heui-Sub;Kim Youn J.
    • Proceedings of the KSME Conference
    • /
    • 2002.08a
    • /
    • pp.365-368
    • /
    • 2002
  • The design of industrial arc plasma systems is still largely based on trial and error although the situation is rapidly improving because of the available computational power at a cost which is still fast coming down. The desire to predict the behavior of arc plasma system, thus reducing the development cost, has been the motivation of arc research. To interrupt fault current, the most enormous duty of a circuit breaker, is achieved by separating two contacts in a interruption medium, $SF_{6}$ gas or air etc., and arc plasma is inevitably established between the contacts. The arc must be controlled and interrupted at an appropriate current zero. In order to analyze arc behavior in $SF_{6}$ gas circuit breakers, a numerical calculation method combined with flow field and electromagnetic field has been developed. The method has been applied to model arc generated in the Aachen nozzle and compared the results with the experimental results. Next, we have simulated the unsteady flow characteristics to be induced by arcing of AC cycle, and conformed that the method can predict arc behavior in account of thermal transport to $SF_{6}$ gas around the arc, such as increase of arc voltage near current zero and dependency of arc radius on arc current to maintain constant arc current density.

  • PDF

The Study of the Design Tests for Current Capability according to ANSI (ANSI 규격에 의한 주상 변압기의 동압력 내력시험에 관한 연구)

  • Kim, Sun-Koo;Kim, Won-Man;La, Dae-Ryeol;Roh, Chang-Il;Lee, Dong-Jun;Jung, Heung-Soo
    • Proceedings of the KIEE Conference
    • /
    • 2003.07b
    • /
    • pp.909-911
    • /
    • 2003
  • The almost pole transformers are constructed with tank, cover, clamp etc., that contains the insulation oil, core, coil, terminals, bus and the other accessories. If some fault current will be flown by some trouble or accident, interior pressure of the transformer shall be very quickly rise, and mechanical components or insulation oil from the transformer enclosure shall be propelled or dropped from the tank. For the prevention of the above accident, recently the pole transformers should be done 'the Design Tests for Fault Current Capability' according to ANSI C57.12.20(1997) There are two tests method in this standard, Test Number I with a high current arcing fault, without internal fusible elements, shall be conducted on rack enclosure with its minimum designed air space. Test Number II with an internal fusible element, shall be conducted on each enclosure diameter utilizing the internal fusible elements. KEPCO recently request to be done the 'Design Tests for Fault Current Capability' for pole transformers according to KEPCO's standard ES141-$533{\sim}545$, PS141-$482{\sim}518$ and RS141-$611{\sim}628$ that is same with Test Number I of ANSI C57.12.20.

  • PDF

S-Transform Based Time-Frequency Analysis of Leakage Current Signals of Transmission Line Insulators under Polluted Conditions

  • Natarajan, A.;Narayanan, Suthanthiravanitha
    • Journal of Electrical Engineering and Technology
    • /
    • v.10 no.2
    • /
    • pp.616-624
    • /
    • 2015
  • Flashover of power transmission line insulators due to contamination is a major threat to the reliable operation of power system. This paper deals with the analysis of leakage current characteristics of polymeric insulator using S-Transform technique in order to develop a better diagnostic tool to identify the surface condition of outdoor polymeric insulators. In this work, experiments were carried out on 11 kV silicone rubber insulator under AC voltage at different pollution levels. Moving average technique was adopted to find the trend followed by LC peak at different relative humidity conditions. S-Transform was used to find the relationship between energy and frequency content of the leakage current signal with respect to increase in pollution level over a period of time. From the S-Transform time-frequency contour analysis, point of transition to severe arcing due to increase in pollution and its thershold limit were evaluated. Reported results show that the surface condition of insulators could be easily identified from the S-Transform time-frequency analysis of leakage current signals.

Detection of High Impedance Fault Using Adaptive Neuro-Fuzzy Inference System (적응 뉴로 퍼지 추론 시스템을 이용한 고임피던스 고장검출)

  • 유창완
    • Journal of the Korean Institute of Intelligent Systems
    • /
    • v.9 no.4
    • /
    • pp.426-435
    • /
    • 1999
  • A high impedance fault(HIF) is one of the serious problems facing the electric utility industry today. Because of the high impedance of a downed conductor under some conditions these faults are not easily detected by over-current based protection devices and can cause fires and personal hazard. In this paper a new method for detection of HIF which uses adaptive neuro-fuzzy inference system (ANFIS) is proposed. Since arcing fault current shows different changes during high and low voltage portion of conductor voltage waveform we firstly divided one cycle of fault current into equal spanned four data windows according to the mangnitude of conductor voltage. Fast fourier transform(FFT) is applied to each data window and the frequency spectrum of current waveform are chosen asinputs of ANFIS after input selection method is preprocessed. Using staged fault and normal data ANFIS is trained to discriminate between normal and HIF status by hybrid learning algorithm. This algorithm adapted gradient descent and least square method and shows rapid convergence speed and improved convergence error. The proposed method represent good performance when applied to staged fault data and HIFLL(high impedance like load)such as arc-welder.

  • PDF

PEO Film Formation Behavior of Al1050 Alloy Under Direct Current in an Alkaline Electrolyte

  • Moon, Sungmo;Kim, Yeajin
    • Journal of Surface Science and Engineering
    • /
    • v.50 no.1
    • /
    • pp.17-23
    • /
    • 2017
  • This work demonstrates arc generation and anodic film formation behaviors on Al1050 alloy during PEO (plasma electrolytic oxidation) treatment under a constant direct current in an alkaline electrolyte containing silicate, carbonate and borate ions. Only one big arc more than 2 mm diameter was generated first at the edges and it was moving on the fresh surface or staying occasionally at the edges, resulting in the local burning due to generation of an extremely big orange colored arc at the edges. Central region of the flat surface was not fully covered with PEO films even after sufficiently long treatment time because of the local burning problem. The anodic oxides formed on the flat surface by arcing once were found to consist of a number of small oxide nodules with spherical shape of $3{\sim}6{\mu}m$ size and irregular shapes of about $5{\sim}10{\mu}m$ width and $10{\sim}20{\mu}m$ length. The anodic oxide nodules showed uniform thickness of about $3{\mu}m$ and rounded edges. These experimental results suggest that one big arc observed on the specimen surface under the application of a constant direct current is composed of a number of small micro-arcs less than $20{\mu}m$ size.

Operating Characteristics of Arc-induction Type DC Circuit Breaker (아크유도형 DC 차단기의 동작 특성)

  • Park, Sang-Yong;Choi, Hyo-Sang
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.67 no.7
    • /
    • pp.981-986
    • /
    • 2018
  • AC(alternating current) CB(circuit breaker) at the fault occurred in the existing AC distribution system is limiting the fault current through zero cross-point. However, DC(direct current) CB does not have zero cross-point. Therefore, arc occurred by on-off operation of DC CB is very huge. Nowadays, many research team are studying the way to decrease breaking time, which is one of the essential conditions in DC CB. We suggested novel arc-induction type DC CB in this paper. The proposed arc-induction type DC CB is composed of the mechanical Arc ring and DC CB. We confirmed the operation of arc-induction type DC CB through the HFSS(High Frequency Structure Simulator) 3D simulation program and performed the experiment for operation characteristics. Results showed that arcing time of the arc-induction type DC CB by using induction ring was faster than existing mechanical DC CB. On the transient system, we confirmed stable operation characteristics of the arc-induction type DC CB through the simulation and experimental results. We expect that the proposed arc-induction type DC CB technology is will go to stay ahead of the existing DC CB technology.

A Study on the High Speed Interruption of Parallel Arcing (병렬아크의 고속차단에 관한 연구)

  • Kil, Gyung-Suk;Ji, Hong-Keun;Park, Dae-Won;Kim, Il-Kwon;Kim, Young-Il;Cho, Young-Jin
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.22 no.12
    • /
    • pp.95-100
    • /
    • 2008
  • Conventional Earth Leakage Circuit Breakers (ELCBs) have defects of a breaking failure or a long breaking-time against parallel arc current. In this paper, breaking characteristics of conventional ELCBs were analyzed by simulation of parallel arc in a low-voltage indoor wiring system, and an air-core current sensor and a signal converter being most available for parallel arc detection were developed and applied to a conventional ELCB. The proposed tripped the ELCB regardless of the location of parallel arc. The breaking-time was in ranges of $1.74{\sim}8.3[ms]$ depending on the phase of arc generation, which is about 5 times as fast as conventional ELCBs with the breaking-time of 50[ms].

Analysis on Waveform of Leakage Current of Contaminated EPDM Insulators by Salt Fog (Salt fog에 의한 오손된 EPDM애자의 누설전류 파형 분석)

  • Park, Jae-Jun;Song, Young-Chul;Kim, Jeong-Boo;Lee, You-Min;Lee, Hyun-Dong;Jung, Young-Ho
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2003.11a
    • /
    • pp.36-41
    • /
    • 2003
  • This paper presents the results of power spectra using the fundamental and low frequency harmonic components of leakage current waveform to study aging on contaminated EPDM insulator(was serviced during 1997-2001, region Pohang, korea) under salt fog conditions. Experiments have been conducted in the chamber salt fog and at the 16KVrms. The salt contents adjusted as 0g,25g,50g and 75g per liter of deionized water. The onset of dry-band arcing on polymer insulators could be determined by signal processing the low frequency harmonics components. A correlation has been found between the fundamental and low harmonic components of power spectra on leakage current. Where aging could be associated with an increase in the level of both the fundamental and low frequency harmonics components of leakage current. Surface aging for contaminated EPDM insulators occurred when the fundamental component of leakage current was greater then some level On the other hand, when the polymer insulator approached failure, the fundamental component of leakage current reached relatively high values and low frequency harmonics components of the leakage current trended to decrease. The results suggest that both the fundamental and low frequency harmonics of leakage current can be used as a tool to determine both the beginning of aging and before flashover, end of life EPBM insulator in salt fog.

  • PDF