덕트누기시험기용 풍량측정 오리피스의 최적위치 선정에 관한 연구 (A Study on the Optimal Orifice Location for Air flow Measurement in an Air Duct Leakage Tester)

  • 이승철
    • 설비공학논문집
    • /
    • 제18권2호
    • /
    • pp.186-191
    • /
    • 2006
  • In this study, five experiments were carried out, with an orifice located downstream of a fan in case I where upstream duct length is 6 D, and that in the downstream is 4 D and different downstream distance to the fan in the rest, so as to determine the optimal location of the orifice and reduce the duct length of airflow measurement device. The resulting flow rate-pressure drop correlations were found to satisfy the limitation of SMACNA standard, which specified an error of $\pm7.5\%$ based on the real flow rate. Also, the best one of five. cases was achieved with the orifice located midway of the orifice duct four times its diameter long.

덕트누기시험기용 풍량측정 오리피스의 최적위치 선정에 관한 연구 (Optimal Location of Orifice in Duct Leakage Tester for Air Flow Measurement)

  • 이승철;박만흥;김광추
    • 대한기계학회:학술대회논문집
    • /
    • 대한기계학회 2004년도 춘계학술대회
    • /
    • pp.2151-2156
    • /
    • 2004
  • In this study, five experiments were carried out, with an orifice located downstream of a fan in case I and upstream distance to the fan in the rest cases(case $II{\sim}$), so as to determine the optimal location of the orifice and reduce the size of airflow measurement device. The resulting flow rate-pressure drop correlations were found to satisfy the limitation of SMACNA standard, which specified an error of ${\pm}7.5%$ based on the real flow rate. The best outcome was achieved with the orifice located midway of the orifice duct 4 times its diameter long.