• Title/Summary/Keyword: Air conditioning control method

Search Result 202, Processing Time 0.032 seconds

An Experimental Study on the Control Methods of Radiant Floor Heating Systems (바닥복사 난방시스템의 제어방식에 관한 실험적 연구)

  • 김오봉;이진영;여명석;석호태;김광우
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.13 no.12
    • /
    • pp.1297-1305
    • /
    • 2001
  • In this study, existing control methods that are suggested or applied until now are classified by control parameters, and stability of in the room and floor surface temperatures of each control method is compared through experiments. Then, the control performance of these control methods are analyzed to evaluate the applicability to Korean apartment housing. From the result of the applicability analysis, the outdoor reset with on/off PWM control is found to be desirable for district heating systems and flux modulation is found to be applicable for decentralized heating systems. In the case of independent control systems for each room, on/off PWM control is desirable.

  • PDF

Wafer Motion Control of Clean Tube System (클린튜브 시스템의 웨이퍼 운동 제어)

  • 신동헌;최철환;정규식
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.16 no.5
    • /
    • pp.475-481
    • /
    • 2004
  • This paper presents a force model of the clean tube system, which was developed as a means of transferring air-floated wafers inside a closed tube filled with super clean air. The recovering force from the holes for floating wafers is modeled as a linear spring and thus the wafers motion is modeled as a mass-spring-damper system. The propelling forces are modeled as linear along with the wafer location. The paper also proposes a control method to emit and stop a wafer at the center of a control unit. It reveals the minimum value of the propelling force to leave from the control unit. In order to stop the wafer, it utilizes the exact time when the wafer arrives at the position to activate the propelling force. Experiments with the clean tube system built for the 12 inch wafer shows the validity of the proposed model and the algorithm.

Comfort Control Algorithm Development of Car Air Conditioner using Thermal Comfort Evaluation of The Driver : Part II-Physiological Response of Driver (자동차 에어컨 쾌적제어 알고리즘 개발을 위한 운전자 온열감성 평가 : 제 2보-운전자의 생리반응)

  • Kim, Minsoo;Kim, Donggyu;Park, Jongil;Kum, Jongsoo
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.28 no.6
    • /
    • pp.217-223
    • /
    • 2016
  • In this study, we investigated the operating method of a driver for an air conditioning system according to the temperature difference between the indoor and outdoor environments of a car parked outside during the summer. Researchers of this study suggest the comfort mode of a car air conditioner to improve the thermal comfort of the driver, thereby maintaining longer comfort. This study separately, analyzed temperatures on a cloudy day and sunny day. The results showed the car indoor heat environment and physiological results (EEG, ECG) of the subject. It showed a difference of the car indoor heat environment by weather with the difference also appearing in the physiological response of the subject. In conclusion, in this paper, on the basis of the physiological response of a subject, a comfortable algorithm of automobile air conditioner is being suggested.

A Study on GRNN Control Strategies for Floor Radiant Heating System in Residential Apartments (공동주택 바닥복사 난방시스템의 GRNN 제어 적용에 관한 연구)

  • Song, Jae-Yeob;Ahn, Byung-Cheon
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.24 no.12
    • /
    • pp.830-836
    • /
    • 2012
  • In this study, the effects of heating control methods on heating control performance and energy consumption in the floor radiant heating control system of residential apartments were research by computer simulation. A general regression neural network(GRNN) control method for reducing indoor temperature overshoot and saving energy in floor radiant heating system is suggested. The GRNN control method shows good responses in comparison with the conventional and outdoor reset control methods for improving indoor thermal environment and reducing energy consumption.

Capacity Modulation of a Multi-Type Heat Pump System using PID Control with Fuzzy Logic (퍼지 로직 적용 PID 제어를 이용한 멀티형 열펌프의 용량조절)

  • 김세영;김민수
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.13 no.9
    • /
    • pp.810-817
    • /
    • 2001
  • Performance of a water-to-water multi-type heat pump system using R22 which has tow indoor units has been investigated experimentally. The refrigerant flow rate of each indoor unit was regulated by an electronic expansion valve and the total refrigerant flow rate of the system was controlled by a variable speed compressor. In the system, evaporator outlet pressure of refrigerant and outlet temperatures of secondary fluid from indoor units were selected as control variables. Experiments were executed for both cooling and heating modes using PID control method with fuzzy logic, and results of the test are compared with a classical PID method. In the case of PID control with fuzzy logic, the fuzzy control rules corrects PID parameters each time. Results show that PID control with fuzzy logic has the merits of quick response and reduced overshoot.

  • PDF

Energy Analysis for Variable Air Volume System (변풍량(變風量)시스템의 에너지해석(解析)에 관(關)한 연구(硏究))

  • Park, B.K.;Cho, D.W.;Shin, H.J.
    • The Magazine of the Society of Air-Conditioning and Refrigerating Engineers of Korea
    • /
    • v.17 no.5
    • /
    • pp.575-582
    • /
    • 1988
  • This paper presents an energy analysis on the VAV system of 10-story building in Seoul using DOE-2 program and Modified Bin Method. The use of VAV system is an excellent means of saving energy in new buildings and/or retrofit. The fan control techniques considered are cycling, discharge dampers, inlet vanes, and motor speed control. The monthly and annual energy consumption is calculated for fan control techniques, components, and chiller types. The results of annual fan electricity use are compared using DOE-2 and Modified Bin Method, and show fairly good agreement. In addition, factors affecting energy consumption are also described.

  • PDF

The energy-saving effect by controlling the number of operating chillers in university facility (대학시설에 대한 열원기기 대수 운전 제어의 에너지 절약 효과)

  • Lee, Je-Hyeon;Akashi, Yasunori;Kum, Jong-Soo;Kim, Dong-Gyu
    • Proceedings of the SAREK Conference
    • /
    • 2009.06a
    • /
    • pp.1043-1048
    • /
    • 2009
  • This paper proposes the new operation control method that let heat source system stop and circulate only hot water at low load, and verified the introduction effect. At first, we constructed simulation model of heat source system and examined the proposing method by using simulation model. At last, we examined the introduction effect of proposing method with actual building. As a result, the primary energy consumption of heat source system was reduced by about 13%.

  • PDF

Operating characteristics of 3RT heat pumps

  • Moon, Chang-Uk;Choi, Kwang-Hwan;Yoon, Jung-In;Jeon, Min-Ju;Heo, Seong-Kwan;Sung, Yo-Han;Park, Sung-Hyeon;Lee, Jin-Kook;Son, Chang-Hyo
    • Journal of Advanced Marine Engineering and Technology
    • /
    • v.41 no.2
    • /
    • pp.140-145
    • /
    • 2017
  • Newly designed vapor-injection heat pumps have been proposed and analyzed in the present study. An economizer-type vapor-injection (V-I) system has been employed as the standard system because of its reliability and simple control method. The V-I system has a re-cooler and re-heater for cooling and heating, respectively. Solar panels have been installed in the V-I heat pump as well as in the re-heater in order to enhance heating capacity and performance. R410A has been employed as a working fluid and performance analysis has been conducted under various conditions. Results are summarized as follows: (1) The V-I system with the re-cooler yielded a marginally higher coefficient of performance (COP) than the conventional V-I refrigeration system. (2) By increasing the re-cooler cooling capacity, enhanced system performance as compared to the conventional V-I system was observed. (3) The re-heater negatively affected the system performance; hence, the V-I heat pump with the re-heater yielded a lower COP than that of the conventional V-I heat pump used for heating. (4) Although the solar panels increased the system performance, this increase could not offset performance degradation by the re-heater.

Feasibility of the Defrost Control by Photoelectric Technology via Comparison with the Temperature Differential Defrosting Method (온도차 감지 제상법과의 비교를 통한 광센서 제상법의 타당성 검증을 위한 연구)

  • Jeon, Chang-Duk;Kim, Dong-Seon
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.26 no.9
    • /
    • pp.434-440
    • /
    • 2014
  • Experiments were performed to verify if performance and characteristic curves obtained from the temperature differential defrosting method, where surface temperature is measured to judge defrosting condition, can be reproduced by the photoelectric technology where defrosting condition is judged by photoelectric sensors. The output voltage of a phototransistor and heating capacity, power consumption, and surface temperature of the outdoor heat exchanger are compared. The results showed that the photoelectric sensors can be used as a defrost control device. On-off control timings in temperature differential defrosting method are in good agreement with those predicted by the high and low threshold output voltages of the photoelectric sensor.

Optimization of a PI Controller Design for an Oil Cooler System with a Variable Rotating Speed Compressor (가변속 압축기를 갖는 오일쿨러의 최적 PI 제어기 설계)

  • Kwon, Taeeun;Jeong, Taeyoung;Jeong, Seokkwon
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.28 no.12
    • /
    • pp.502-508
    • /
    • 2016
  • An optimized PI controller design method is presented to promote the control performance of an oil cooler system for high precision machine tools. First, a transfer function model of the oil cooler system with a variable rotating speed compressor was obtained by the perturbation method as the first order system with a negligible dead time. Then, the closed-loop control system was described as the second order system with a zero. Its dynamic behaviors are mostly governed by characteristic parameters, the damping ratio, and the natural frequency which is incorporated in PI gains. Next, an optimum integral of the time-weighted absolute error (ITAE) criterion was applied to the second order system. The characteristic parameters can be determined by the given design specifications, percent overshoots and settling times and comparisons with the ITAE criterion. Hence, the PI gains were plainly identified in a deterministic way. Finally, the PI gains were fine-tuned to obtain desirable dynamics in real systems, considering the zero effect and parameter variations. The validity of the proposed method was proven by computer simulations and real experiments for selected cases.