• 제목/요약/키워드: Air Control

검색결과 5,862건 처리시간 0.032초

일산화탄소 농도 예측 기능을 사용한 터널 환기 제어 알고리즘 (A Tunnel Ventilation Control Algorithm by Using CO Density Prediction Algorithm)

  • 한도영;윤진원
    • 설비공학논문집
    • /
    • 제16권11호
    • /
    • pp.1035-1043
    • /
    • 2004
  • For a long road tunnel, a tunnel ventilation system may be used in order to reduce the pollution level below the required level. To control the tunnel pollution level, a closed loop control algorithm may be used. The feedforward prediction algorithm and the cascade control algorithm were developed to regulate the CO level in a tunnel. The feedforward prediction algorithm composed of the traffic estimation algorithm and the CO density prediction algorithm, and the cascade control algorithm composed of the jet fan control algorithm and the air velocity setpoint algorithm. The verification of control algorithms was carried out by dynamic models developed from the actual tunnel data. The simulation results showed that control algorithms developed for this study were effective for the control of the tunnel ventilation system.

Economizer cycle을 채용한 전열교환형 환기시스템의 에너지 절감 효과 분석 -국내 학교를 대상으로- (Energy Saving Effect of ERV(Energy Recovery Ventilator) with Economizer Cycle - Focused on the School Buildings -)

  • 김주욱;박재형;송두삼;주의성;권영철
    • 대한설비공학회:학술대회논문집
    • /
    • 대한설비공학회 2009년도 하계학술발표대회 논문집
    • /
    • pp.695-700
    • /
    • 2009
  • Maintaining an IAQ with fresh in school building is very important because the good IAQ can be possible to improve the academic performance. Since school buildings are very dense and require a lot of fresh air, the need for ERV(Energy Recovery Ventilator) has become obvious. While opening a window does provide ventilation, the building's heat and humidity will then be lost in the winter and gained in the summer, both of which are undesirable for the indoor climate and for energy efficiency. ERV technology offers an optimal solution: fresh air, better climate control and energy efficiency. However, when the outdoor air condition is favorable to control the indoor environment such as spring and autum in Korea, heat exchange in ERV would rather increase the cooling load than diminish. Economizer cycle control which using the outdoor air in controlling the indoor thermal environment has many benefit in terms of energy saving and IAQ control. In this study, the ERV with economizer cycle control will be suggested. And then the system control characteristics and energy saving effect will be analyzed through the TRSNSYS Simulation.

  • PDF

바닥복사 난방공간의 효율적인 난방제어방법 (The Effective Heating Control Method of the Radiant Floor Heating System)

  • 조성환;태춘섭
    • 설비공학논문집
    • /
    • 제8권3호
    • /
    • pp.317-329
    • /
    • 1996
  • By describing the floor slab of a radiant heating system as a one dimensional transient heat exchanger problem, a dynamic analysis model to incorperate with TRNSYS program was developed and their results were compared with experimental results. Results showed that the both of TPOC(Two Parameter On-off Control) and TPSC(Two Parameter Switching Control) method using room air temperature and floor surface temperature as the control parameters does not maintain room air and floor surface temperature exactly at the setting temperatures. But TPSC method is a better candidate for the temperature regulations of room air and floor surface temperature than TPOC method which can keep on the upper and lower limit temperature according to outside temeperature and wall structure etc. And better thermal circumstance can be given by TPSC method than On-off and TPOC method and the overheating which can be occured at the radiant floor heating system with on-off heating control will be reduced.

  • PDF

PI와 피드포워드 제어를 이용한 공작기계용 오일쿨러의 핫가스 바이패스 방식 정밀 온도 제어 (Precise Temperature Control of Oil Coolers with Hot-gas Bypass Manner for Machine Tools Based on PI and Feedforward Control)

  • 정석권;변종영;김상호;윤정인
    • 설비공학논문집
    • /
    • 제23권2호
    • /
    • pp.111-119
    • /
    • 2011
  • Recently, the performances of speed and accuracy are enhanced in machine tools. The high speed of the machine tools usually causes harmful thermal displacements on the objects. To reduce the thermal displacements, machine tools generally adopt oil coolers with precise temperature control function. This study aims at precise control of oil outlet temperature in the oil coolers with hot-gas bypass manner based on PI control logic. The control system was designed for obtaining steady state error within ${\pm}0.1^{\circ}C$ and maximum overshoot with 0.8% even though abrupt disturbances are added to the system. We showed that the PI gains could be easily decided by numerical simulations using practical transfer function which got experiments. Also, transient characteristics could be improved significantly by reflecting the inlet temperature of an evaporator to the output of a controller feedforwardly considering periodic abrupt disturbances. Through some experiments, excellent control performances were established by the suggested control.

전축열방식 빙축열 시스템의 최적제어 알고리즘 (Optimal Control Algorithms for the Full Storage Ice Cooling System)

  • 한도영;이준호
    • 설비공학논문집
    • /
    • 제14권4호
    • /
    • pp.350-357
    • /
    • 2002
  • Optimal control algorithms for the full storage ice cooling system were developed by using a dynamic simulation program. Control algorithms for the storage charging mode were developed for the chiller outlet temperature setpoint control and the chiller capacity control. Control algorithms for the storage discharging mode were developed for the proper mode selection, the storage-only mode control, and the storage-priority chiller-shared mode control. Two different cases of the expected outdoor air temperature profile and the expected cooling load profile were used to analyze the effectiveness of these algorithms. Simulation results show the energy savings and the satisfactory controls of the ice storage system. Therefore, control algorithms developed for this study may effectively be used for the improved control of the ice storage cooling system.

온돌을 이용한 바닥복사냉방의 제어성능에 관한 실험적 연구 (An Experimental Study on Control Performance of Radiant Floor Cooling Using Ondol)

  • 김용이;임재한;한여명;김광우
    • 설비공학논문집
    • /
    • 제13권11호
    • /
    • pp.1165-1173
    • /
    • 2001
  • The objectives of this study are to analyze the application of radiant floor cooling and to evaluate the control methods through experiments when the radiant heating system is used for cooling. Through the experiment analysis the control methods such as on/off control, variable flow control and outdoor reset with indoor temperature feedback control are evaluated and compared. The cooling curve (reset ratio) is found for radiant cooling, which shows tole relation between outside air temperature and supply water temperature. Comparison of cooling methods shows that outdoor reset with indoor temperature feedback control is more appropriate than on/off control and variable flow control with regard to prevention of the condensation and thermal comfort.

  • PDF

가변 풍량 유닛에 의한 실내 공간의 온도제어를 위한 공간의 분할 모델과 상태궤환 제어기의 개발에 관한 연구

  • 박세화;신승철
    • 설비공학논문집
    • /
    • 제13권10호
    • /
    • pp.947-959
    • /
    • 2001
  • We propose a control scheme to control the indoor zone temperature via variable air volume (VAV) unit. To control the room temperature, state space model of the conditioned zone which is partitioned into nine artificial sectional regions is derived. The nonlinearity of the damper motion and actuator are considered for the practical use in the state space system description. The temperature control of the room temperature is performed by manipulating the degree of openness of the damper in relation to the local room temperature and the supplied air flow rate. In general, since a local temperature in the conditioned zone is measured, it is required to estimate the temperature values in each regions for the precise temperature control. We thus design a state observer to estimate the regional temperature, and use these values in the controller. The overall control system consists of the state observer based state feedback with the integral control. We compared the control results of the proposed scheme with those of cascade proportional and integral (PI) control, and showed that the scheme achieved precise control of the conditioned system.

  • PDF

대기오염측정망 정도관리의 문제점과 개선방향 (Problems and Improvements in the Quality Control of the Air Monitoring Network)

  • 김덕승;박정호
    • 한국환경과학회지
    • /
    • 제29권8호
    • /
    • pp.847-855
    • /
    • 2020
  • This study presented problems and improvements in the quality control of an air monitoring network, using Gyeongnam as an example. 1) The effective utilization rate of the air monitoring was 95%, which showed good management, but the maximum of 2% was indicated by zero or detection limit among measurement data. 2) In the equivalence evaluation of PM2.5, the slope and intercept satisfy the evaluation criteria; however, 1% of the PM2.5/PM10 ratios were outliers. 3) All air monitoring stations meet the quality control standards; however, the management status is added to the quality inspection, management system is unified and the related budget is expanded, and systematic commission management is required.

공조 시스템용 DDC의 온라인 최적제어에 관한 연구

  • 안병천
    • 설비공학논문집
    • /
    • 제13권11호
    • /
    • pp.1072-1078
    • /
    • 2001
  • The real time optimal control algorithm of the DDC controller for chilled water and supply air temperature set-point of heating, ventilating, air-conditioning and refrigeration systems has been researched for minimization of the total power which is consumed by the chiller, chilled water pump and air handing unit fan. The study has been done by using TRNSYS program in order to analyze the central cooling system in terms of the environmental variables such as indoor cooling lead and wet-bulb temperature. This optimal control alogorithm saves more energy and is suitable for real time on-line control in comparison with conventional method.

  • PDF