• Title/Summary/Keyword: ACSR conductor

Search Result 67, Processing Time 0.029 seconds

A Study on Surface Characteristics of ACSR Transmission Line due to a Flame (화염에 의한 ACSR 송전선의 표면 특성에 관한 연구)

  • 김영달
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.17 no.6
    • /
    • pp.173-180
    • /
    • 2003
  • This paper deals with the experimental results that apply to a new wire by an artificial flame-maker because it's difficult to directly analyze the characteristic of deterioration by a forest fire. Those results include surface characteristics for a conductor. In addition, there's been an experiment and analysis about the surface characteristics of the wire of ACSR 480$\textrm{mm}^2$ which was removed from Pohang area by a forest fire. Then, the database will be made to predict the state of deteriorated wires by a forest fire using those two data, and data necessary to diagnose the life state of an ACSR wire affected by a forest fire will be given.

Reliance analysis for Mechanical characteristics of ACSR Transmission Line due to a Flame (화염에 의한 ACSR 송전선의 기계적 특성에 관한 신뢰성 분석)

  • Kim, Young-Dal;Shim, Jae-Myung;Kim, Jong-Suk
    • Proceedings of the KIEE Conference
    • /
    • 2004.11d
    • /
    • pp.71-76
    • /
    • 2004
  • This paper deals with the experimental results that apply to a new wire by an artificial flame-maker because it's difficult to directly analyze the characteristic of deterioration by a forest fire. Those results include tension load, extension rate and torsion number for a conductor. In addition, there's been an experiment and analysis about the mechanical characteristics of the wire of ACSR $48mm^2$ which was removed from Pohang area by a forest fire. Then, the database will be made to predict the state of deteriorated wires by a forest fire using those two data, and data necessary to diagnose the life state of an ACSR wire affected by a forest fire will be given.

  • PDF

Mechanical characteristic of ACSR Transmission lines by forest fires (산불에 열화된 ACSR 전선의 기계적 특성 검토)

  • Kang, J.W.;Jang, T.I.;Hong, D.S.;Park, C.G.;Bang, H.K.;Kim, Y.D.
    • Proceedings of the KIEE Conference
    • /
    • 2003.07a
    • /
    • pp.506-508
    • /
    • 2003
  • In the case of a fire in the mountains, steel wires coated with zinc and aluminum wires of those power cables exposed to the fire or near around will be deteriorated by the blaze and the high temperature. This paper shows the experimental results that apply to a new wire by an artificial flame-maker and results including the intensity of extension and wrench for a conductor. In addition, there's been an experiment and analysis about the mechanical characteristics of the wire of ACSR $480mm^2$ which was removed from A T/L by a forest fire. Then, the database will be made to predict the state of deteriorated wires by a forest fire using those two data, and data necessary to diagnose the life state of an ACSR wire affected by a forest fire will be given.

  • PDF

Reliance Analysis for Mechanical Characteristics of ACSR Transmission Line due to a Flame (화염에 의한 ACSR 송전선의 기계적 특성에 관한 신뢰성 분석)

  • 김영달
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.17 no.6
    • /
    • pp.138-146
    • /
    • 2003
  • This paper deals with the experimental results that apply to a new wire by an artificial flame-maker because it's difficult to directly analyze the characteristic of deterioration by a forest fire. Those results include tension load, extension rate and torsion number for a conductor. In addition, there's been an experiment and analysis about the mechanical characteristics of the wire of ACSR 480$\textrm{mm}^2$ which was removed from Pohang area by a forest fire. Then, the database will be made to predict the state of deteriorated wires by a forest fire using those two data, and data necessary to diagnose the life state of an ACSR wire affected by a forest fire will be given.

The Development of ACNR Conductor( I ) - Mechanical Properties (ACNR가공송전선의 개발( I ) - 기계적 특성)

  • Kim, Shang-Shu;Kim, Byung-Geol;Lee, Hee-Woong;Park, Joo-Hwan
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2005.07a
    • /
    • pp.635-636
    • /
    • 2005
  • 최근에 미국이나 러시아를 중심으로 가공승전선의 승전효율을 증대시키고자 하는 연구가 활발히 이루어지고 있으며 어느 정도 성과를 거두고 있다. ACSR가공송전선에서 교류전류의 흐름에 의하여 코어 (Core)에 자기장이 발생되어 투자율이 증가되고 이로 인하여 알루미늄층에서 전류밀도의 재 분포, skin effect 등으로 인하여 전력손실이 발생된다. 본 연구에서는 기존의 ACSR가공송전선의 코어 (Core)인 고탄소강선 대신에 비자성이면서 고강도인 새로운 강선을 코어재료로 채택한 ACNR(Aluminum Conductor Nonmagnetic Steel Reinforced)가공송전선을 개발하여 전력손실을 감소시켰다.

  • PDF

Temperature and Load Change behavior of Overhead Conductor under loading current due to Forest Fire (통전 중 산불에 노출된 가공송전선의 온도 및 장력 변화 거동)

  • Kim, Byung-Geol;Jang, Young-Ho;Kim, Shang-Shu;Han, Se-Won
    • Journal of the Korean Institute of Electrical and Electronic Material Engineers
    • /
    • v.22 no.4
    • /
    • pp.366-371
    • /
    • 2009
  • The authors have published several technical reports on the deterioration of conductor due to forest fire in series so far. This is because even we have been experiencing hundreds of forest fires every year, no systematic research on conductor which is very vulnerable to fire have been fulfilled. This paper describes the sag-tension behavior of conductor under loading current normally when only partial area of a long conductor is exposed to fire. Temperatures of Overhead Conductor were different with measurement position. When the partial area of conductor was heated up to $500^{\circ}C$, 20 % of permanent tension loss was observed. This results in the increase of sag of 1.5 m when span is 300 m. The other results will be presented in the text.

Mechanical Deterioration Characteristics of ACSR due to a Flame (화염으로 인한 ACSR의 기계적 열화 특성)

  • 박창기;이광식;강지원;김영달
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.17 no.6
    • /
    • pp.160-168
    • /
    • 2003
  • In Korea, a large portion of aerial power-transmission cables is installed in the mountains. In the case of a fire in the mountains, steel wires coated with zinc and aluminum wires of those power cables exposed to the fire or near around will be deteriorated by the blaze and the high temperature. Deterioration proceeds by interactions of a variety of factors like quality, manufacturing process, the condition of installation and exposure environment of a wire, and so on. Generally, the characteristic of a conductor affect by a forest fire can not be analyzed without the effect through simulating a forest fire. However, there are little research accomplishments of that kind of simulation about it, and there's been no analysis of a sample exposed to an actual forest fire. This thesis shows the experimental results that apply to a new wire by an artificial flame-maker because it's difficult to directly analyze the characteristic of deterioration by a forest fire. Those results include the intensity of extension and wrench for a conductor. In addition, there's been an experiment and analysis about the mechanical characteristics of the wire of ACSR 480[$\textrm{mm}^2$] which was removed from Pohang area by a forest fire. Then, the database will be made to predict the state of deteriorated wires by a forest fire using those two data, and data necessary to diagnose the life state of an ACSR wire affected by a forest fire will be given.

산불에 노출된 가공송전선의 열화특성연구

  • Jang, Yong-Ho;Kim, Byeong-Geol;Kim, Sang-Su;Han, Se-Won;Lee, Won-Gyo
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2009.11a
    • /
    • pp.282-282
    • /
    • 2009
  • Forest Fire can cause a serious damage to overhead conductors. Therefore, the detailed investigation for the changes of mechanical and electrical properties of damaged conductors should be carried out to understand the effect of forest fires on conductors. This is very important to maintain transmission line safely. Specimenes for this study were Al conductores of ACSR $410mm^2$, ACSR 480 R and ACSR $240mm^2$. This paper describes the changes of mechanical and electrical properties of same flame exposed Al conductor. The detailed will be given in the text.

  • PDF

A Study on Maximum Tensile Strengths of Overhead Distribution Conductor Tensioned by Standard Sag of KEPCO in (가공배전선로의 기준이도 적용시 상정최대장력에 관한 연구)

  • Wong, Yoon-Chan;Sun, Sang-Jin;Kim, Chang-Wan
    • Proceedings of the KIEE Conference
    • /
    • 2009.07a
    • /
    • pp.307_308
    • /
    • 2009
  • 본 연구에서는 아연도강연선을 인류주에 보통지선으로 시설할 때 전선의 불평균장력을 지지할 수 있는 최대허용불평균장력을 계산 후 현재의 가공배전선 중 가장 많이 사용하는 ACSR/AW-TR/OC 전 규격에 대하여 기준이도로 시설시 최악조건의 상정최대장력과 비교함으로써 기준이도의 재설정 필요성 여부를 검토하고자 하였다. 연구 결과 ACSR/AW- TR/OC $160mm^2$$240mm^2$은 장경간 개소의 고온계 강화 지역 상정최대장력보다 단경간 개소의 저온계 상정최대장력이 큼을 발견하였고, 지선을 아연도강연선 7/3.5mm이하로 시설 가능하도록 ACSR/AW- TR/OC $160mm^2$$240mm^2$의 기존이도를 재설정하는 연구를 진행할 필요성이 있음을 확인하였다.

  • PDF

The Changes of Mechanical and Electrical Properties in ACSR Overhead Conductor with Aging (경년에 따른 ACSR가공송전선의 기계적 및 전기적특성 변화)

  • Kim, Byung-Geol;Kim, Shang-Shu;Jang, Tae-In;Kang, Ji-Won;Lee, Dong-Il;Min, Byung-Uk
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2005.07a
    • /
    • pp.619-620
    • /
    • 2005
  • 가공송전선의 수명은 가설 후 경과된 기간(약 36년)으로 정하는 것이 일반적이나 가설된 지역의 환경적 요인이나 전선의 재질상의 특성, 전력공급량 등에 의하여 열화상태가 다양하게 진행된다. 따라서 현재와 같이 모든 전선에 대하여 일정기간으로 정해진 교체 시기는 현실적이지 못하다. 실제로 전선의 단선사고는 경년과 같은 전선의 이력보다는 부식 환경에 노출된 전선의 취약성으로 인하여 초래되는 경우가 많다. 정확한 전선의 수명을 진단하기 위해서는 가공송전선이 노출되어 있는 환경 하에서 경년에 따른 기계적, 전기적 특성의 변화를 조사하여 복합적 인자들을 정량적으로 처리하는 것이 필수적이다.

  • PDF