• 제목/요약/키워드: 8/20[${\mu}s$] Impulse Current

검색결과 38건 처리시간 0.028초

$8/20{\mu}s$ 임펄스전류의 크기와 인가횟수가 ZnO 바리스터의 수명에 미치는 영향 (Effects of injected number and amplitude of $8/20{\mu}s$ impulse current on the life of ZnO varistor)

  • 이복희;이봉;이수봉;강성만
    • 한국조명전기설비학회:학술대회논문집
    • /
    • 한국조명전기설비학회 2005년도 학술대회 논문집
    • /
    • pp.275-279
    • /
    • 2005
  • This paper presents leakage current characteristics as a function of injected number and magnitude of impulse current, when$8/20{\mu}s$ lightning impulse current is injected to ZnO varistor. The life of ZnO varistor against $8/20{\mu}s$ lightning impulse current was evaluated. The injected number of the test current to breakdown was inversely proportional to the amplitude of impulse current.

  • PDF

뇌서지가 ZnO바리스터에 미치는 영향 (Effects of Lightning Surges on the Life of ZnO Varistors)

  • 이봉;이수봉;강성만;이복희
    • 대한전기학회논문지:전기물성ㆍ응용부문C
    • /
    • 제55권5호
    • /
    • pp.257-262
    • /
    • 2006
  • To evaluate the change in protective levels of zinc oxide (ZnO) varistors after the surge absorption, this paper investigated the effects of the number of injection and amplitude of lightning surges on the life of ZnO varistors for low voltages. Leakage currents flowing through ZnO varistors subjected to the $8/20{\mu}s$ impulse currents under 60 Hz AC voltages were measured. The surge simulator system ECAT that can generate $8/20{\mu}s$ impulse currents with a peak short-circuit of 5 $[kA_p]$ was used. The ZnO varistor leakage current increases with exposure to impulse current, and the number of injection of $8/20{\mu}s$ impulse currents to breakdown was inversely proportional to the amplitude of the test current. Behaviors of ZnO varistor leakage currents were strongly dependent on the number of injection and amplitude of $8/20{\mu}s$ impulse currents. ZnO varistors degrade gradually when subjected to impulse current, and the resistive leakage current flowing through ZnO varistors subjected to the $8/20{\mu}s$ impulse currents under 60 Hz AC voltages was significantly increased after a certain number of injection that is dependent on the amplitude of the test impulse current. As a result, the life of ZnO varistors mainly depends on the amplitude and occurrence frequency of lightning surges.

서지전류에 의한 누전차단기의 의도하지 않은 트립에 대한 신뢰성 (Reliability on the Unintended Trips of Residual Current Operated Circuit Breakers due to Surge Currents)

  • 이복희;김상현;김유하
    • 조명전기설비학회논문지
    • /
    • 제26권5호
    • /
    • pp.79-84
    • /
    • 2012
  • As the huge economical loss and function paralysis of information technology-based systems can be caused by the misoperation of residual current devices(RCDs) due to surge voltages and currents, RCDs shall not operate by surge currents. In this paper, in order to evaluate the reliability of residual current operated circuit-breakers with integral overcurrent protection for household and similar uses((RCBOs) stressed by surges, the unintended trip characteristics of RCBOs under surge currents were experimentally investigated using the combination wave generator. Seven different types of single-phase RCBOs being present on the domestic market were investigated according to KS C IEC 61009-1 standard. As a result, all kinds of specimens were satisfied the requirements for 0.5 [${\mu}s$]/100[kHz] ring wave impulse currents. Most of specimens stressed by the 8/20[${\mu}s$] impulse current tripped at least one or more, and some of them were broken down during consecutive tests. It was found that only one type of specimens meets the L-N mode immunity to the combination wave of 1.2/50[${\mu}s$] impulse voltage and 8/20[${\mu}s$] impulse current.

8/20 [μs] 임펄스전류의 인가횟수와 크기가 ZnO바리스터의 수명에 미치는 영향 (Effects of the Injected Number and Amplitude of 8/20 [μs] Impulse Current on the Life of ZnO Varistors)

  • 이복희;이봉
    • 조명전기설비학회논문지
    • /
    • 제21권1호
    • /
    • pp.118-124
    • /
    • 2007
  • 본 논문에서는 임펄스전류의 크기와 인가횟수가 ZnO바리스터의 수명에 미치는 영향에 관한 것으로 뇌임펄스전류가 ZnO바리스터의 성능에 미치는 영향을 분석하기 위하여 $8/20[{\mu}s]$임펄스전류가 인가되기 전후 ZnO바리스터의 상용주파수 교류전압에 대한 저항성 누설전류와 손실전력을 측정하였다. 그 결과 $8/20[{\mu}s]$임펄스전류의 인가횟수가 증가함에 파라 ZnO바리스터에 흐르는 저항성 누설전류는 증가하고 통과시간은 길어졌다. ZnO바리스터의 수명은 뇌임펄스전류의 크기와 인가횟수에 대해서 평가하는 것이 바람직하다.

충격전류용 shunt의 직각파 특성 (Step Response Characteristics of Shunts for Impulse Current)

  • 김익수;김민규;허대행
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2009년도 제40회 하계학술대회
    • /
    • pp.1445_1446
    • /
    • 2009
  • This paper represents the step response characteristics of shunts for impulse current. This work is aimed at the development of the reference measuring system(RMS) for impulse current rated 10 kA at 1/$20{\mu}s$, 100 kA at 4/$10{\mu}s$, 20 kA at 8/$20{\mu}s$, 40 kA at 30/$80{\mu}s$. According to the IEC 60060-2, the step response characteristics was assessed. As results of the test, the step response characteristics of newly developed shunts for impulse current satisfied requirements of RMS.

  • PDF

서지전류가 입사된 ZnO 바리스터에 흐르는 누설전류의 특성 (Characteristics of leakage currents flowing through ZnO varistor exposed to surge currents)

  • 이복희;이봉;이수봉
    • 한국조명전기설비학회:학술대회논문집
    • /
    • 한국조명전기설비학회 2006년도 춘계학술대회 논문집
    • /
    • pp.338-341
    • /
    • 2006
  • This paper presents the leakage current characteristics of ZnO varistors exposed to the $8/20{\mu}s$ lightning impulse currents as functions of the number of injection and amplitude of impulse currents. The surge simulator system ECAT that can generate $8/20{\mu}s$ impulse currents with a peak short-circuit of $5[kA_p]$ was used. Leakage currents flowing through ZnO varistors subjected to the $8/20{\mu}s$ impulse currents were measured under 60 Hz AC voltages. The trend curves of resistive leakage current of ZnO varistors were analytically calculated.

  • PDF

비선형 부하를 고려한 감쇠 진동형 임펄스 전류발생기의 설계 기법 (Optimum Design Methodology of the Damped Oscillatory Impulse Current Generator Considering a Nonlinear Load)

  • 장석훈;이재복;;명성호;조연규
    • 전기학회논문지
    • /
    • 제57권12호
    • /
    • pp.2255-2262
    • /
    • 2008
  • This paper presents a design parameter calculation methodology and its realization to construction for the damped oscillatory impulse current generator(ICG) modelled as damping factor $\alpha$. Matlab internal functions, "fzero" and "polyfit" are applied to find a which are solutions of second order nonlinear equation related with three wave parameters $T_{1},T_{2}$ and $I_{os}$. The calculation results for standard impulse current waveforms such as 4/10${\mu}s$, 8/20${\mu}s$ and 30/80${\mu}s$ show very good accuracy and this results make it possible to extend to generalization in the design of damped oscillatory lCG with any capacitor. 8/20${\mu}s$ ICG based on the calculated design circuit parameters is fabricated in consideration of the nonlinear load(MOV) variation. Comparisons of the tested waveforms with the designed estimation show error within 10% for the waveform tolerance recommended in IEC 60060-1 and IEEE std. C62.45.

송변전급(up to class 5) Impulse current test system의 설계 및 특성 (Design & characteristics of impulse current test system for station class(up to class 5))

  • 김석수;최익순;강영식;박병락;박태곤
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2004년도 하계학술대회 논문집 Vol.5 No.2
    • /
    • pp.1146-1149
    • /
    • 2004
  • A new developed impulse current test system(100kV, 250kJ)is presented, which can carry out all impulse current and performance tests on surge arrester sections with rated voltage up to 12kV according to IEC 60099-4(2001). The maximum achievable peak value is 200kA for the impulse current $4/10{\mu}s$ and 60kA for the $30/80{\mu}s$ and $8/20{\mu}s$. The long duration current impulse is realized from class 1 to class 5. The digital transient recorder(4 channels 60MS/S 10bit) is used for measuring AC voltage, impulse current, reference voltage and leakage current. The complex control, measuring, evaluation and data storage system is controlled by one industrial PC system.

  • PDF

산화아연형 피뢰기 소자의 뇌충격전류에 의한 특성 변화 (Change of the Characteristics of ZnO Arrester Blocks by Lightning Impulse Current)

  • 한주섭;송재용;길경석
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1998년도 추계학술대회 논문집 학회본부 C
    • /
    • pp.907-909
    • /
    • 1998
  • This paper describes the effect of impulse current on degradation of ZnO blocks. In this study, an impulse current generator which can produce 8/20 [${\mu}s$], 3 [kA] and 4/10 [${\mu}s$], 5 [kA] waveform is designed and fabricated to simulate the lightning impulse current. The residual voltage, reference voltage, and leakage current flowing to the ZnO blocks are observed. The experimental results show that the leakage current increases continuously with the number of applied impulse current, but no significant changes in residual voltage and in operating voltage are observed until the ZnO block is destroyed. Also, it is confirmed that the main factor on degradation of ZnO blocks is rather the total energy applied to ZnO blocks than the peak value of the impulse current.

  • PDF

임펄스전류에 의한 배전용 ZnO 피뢰기 소자의 열화특성 (Deterioration Characteristics of ZnO Surge Arrester Blocks for Power Distribution Systems Due to Impulse Currents)

  • 이복희;조성철;양순만
    • 조명전기설비학회논문지
    • /
    • 제27권3호
    • /
    • pp.79-86
    • /
    • 2013
  • In order to analyze the electrical performance of ZnO surge arresters stressed by the combined DC and AC voltages that are generated in DC/AC converter systems, the leakage current properties of ZnO surge arrester blocks deteriorated by impulse currents were investigated. The test specimens were deteriorated by the 8/$20{\mu}s$ impulse current of 2.5kA and the leakage currents flowing into the deteriorated zinc oxide(ZnO) arrester blocks subjected to the combined DC and power frequency AC voltages are measured. As a result, the leakage currents flowing through deteriorated ZnO surge arrester blocks were higher than those flowing through the fine ZnO surge arrester blocks and the larger the injection number of 8/$20{\mu}s$ impulse current of 2.5kA is, the greater the leakage current is. The leakage current-voltage curves(I-V curves) of the fine and deteriorated ZnO surge arrester blocks stressed by the combined DC and AC voltages show significant difference in the low conduction region. Also the cross-over phenomenon is observed at the voltage close to the knee of conduction on plots of I-V curves.