• 제목/요약/키워드: 3-phase hybrid series active power filter

검색결과 12건 처리시간 0.026초

순간전압변동 보상 기능을 갖는 3상 하이브리드형 직렬 능동전력필터 (3-Phase Hybrid Series Active Power Filter with Instantaneous Voltage Fluctuations Compensation)

  • 한석우;최규하
    • 전력전자학회논문지
    • /
    • 제5권6호
    • /
    • pp.544-551
    • /
    • 2000
  • In this paper, 3-phase hybrid series active power filter for compensate current harmonics, voltage drop and unbalanced voltage in the network presented. The proposed system is implemented with a space vector modulation voltage source inverter and a high pass filter connected in parallel to the power system. Here the load is six-pulses thyristor rectifier. The phase angle detected in order to generation reference voltage at load terminal is synchronized with the positive sequence component of the unbalanced source by using symmetrical component transformation. The proposed system has an function harmonic isolation between source and load, voltage regulation, and unbalance compensation. Therefore, what the power system is improved quality, the source current is maintained as a nearly sinusoidal waveform and the load voltage is regulated with a rated voltage regardless of the source variation condition. To verify the validity of the proposed compensating system, the computer simulation and experiment are carried out.

  • PDF

성능함수제어 알고리즘을 이용한 3상 4선식 하이브리드형 직렬능동전력필터 (Hybrid Series Active Power filter Based on Performance Function Theory for 3-Phase 4-wire System)

  • 김진선;신재화;김영석
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2003년도 하계학술대회 논문집 B
    • /
    • pp.1096-1098
    • /
    • 2003
  • In this paper, the control algorithm and control methods for a combined system of shunt passive filter and series active filter in 3-phase 4-wire system are discussed. Moreover, the 3-phase 4-wire system is widely employed in distributing electric energy to several office building and manufacturing plants. In such systems, the third harmonic and odd multiples of $3^{rd}$($9^{th}$, $15^{th}$, etc.) are termed as triple and zero sequence components that do not cancel each other in the system neutral. As a result, the triple harmonics add together creating a primary source of excessive neutral current. Regarding this concern, this paper presents a new control scheme for a series hybrid active system. This series active power filter acts not only as a harmonic compensator but also as a harmonic isolator. Hence the required rating of the series active filter is much smaller than that of a conventional shunt active filter. However, the performance of the combined system is greatly influenced by the filtering algorithm employed in the active power filter. This paper proposes a series active power filter scheme based on performance function. Some experiments was executed and experimental results from a prototype active power filter confirm the suitability of the proposed approach.

  • PDF

성능함수를 이용한 직렬형 능동전력필터의 제어알고리즘에 관한 연구 (A Study of Control Algorithm For Series Active Power Filter Using Performance Function)

  • 고수현;김진선;김영석
    • 전력전자학회:학술대회논문집
    • /
    • 전력전자학회 2002년도 추계학술대회 논문집
    • /
    • pp.199-202
    • /
    • 2002
  • This paper suggests the control algorithm of a 3-phase 3-wire series active power filters which have harmonic voltage source and harmonic current source This suggested control algorithm can compensate harmonics which are generated by nonlinear load such as diode or thyristor converter and reactive power in 3-phase 3-wire power distribution system This control algorithm extracts a compensation voltage reference from performance function without phase transformation Therefore this control algorithm is simpler than any other conventional control algorithm. 3-phase 3-wire series active power filter and hybrid active power filter is manufactured and experiments are carried out for harmonic voltage source and harmonic current source to verify the effectiveness of presented control algorithm Experimental results are presented in this Paper, as well.

  • PDF

3상 4선식 하이브리드 형 직렬 능동전력필터에 대한 새로운 성능함수 제어 이론 (A New Performance Function-Based Control Strategy for Hybrid Series Active Power Filter in Three-Phase Four-Wire Systems)

  • 신재화;김진선;김영석
    • 대한전기학회논문지:전기기기및에너지변환시스템부문B
    • /
    • 제52권11호
    • /
    • pp.563-571
    • /
    • 2003
  • In this paper, the control algorithm and control method for a combined system of shunt passive filter and series active filter in 3-phase 4-wire system are discussed. Moreover, the three-phase four-wire system is widely employed in distributing electric energy to several office building and manufacturing plants. In such systems, the third harmonic and its 3th harmonics are termed as triple and zero sequence components that do not cancel each other in the system neutral. Consequently, the triple harmonics add together creating a primary source of excessive neutral current. Regarding this concern, this paper presents a new control algorithm for a series hybrid active system, whereas the control approach it adopts may directly influence its compensation characteristics. Hence, the advantage of this control algorithm is direct extraction of compensation voltage reference and the required rating of the series active filter is much smaller than that of a conventional shunt active filter. Some experiments were executed and experimental results from a prototype active power filter confirm the suitability of the proposed approach.

순시전압 sag 및 고조파 전류 보상을 위한 공간벡터 검출법 기반의 3상 하이브리드 직렬형 능동전력필터 (The Space Vector Detection based Three-Phase Hybrid Series Active Power Filter for Compensating Dynamic Voltage Sag and Harmonic Current)

  • 양승환;정영국;임영철
    • 전력전자학회논문지
    • /
    • 제9권4호
    • /
    • pp.303-310
    • /
    • 2004
  • 본 연구에서는 순시전압 sag 및 고조파 전류 보상을 위한 공간벡터 검출법을 기반으로 한 3상 하이브리드 직렬형 능동전력필터 시스템을 제안하고 있다. 순시전안 sag 및 고조파 전류를 검출하기 위한 공간벡터 검출법은 종전의 이론에 비해 곱셈 연산 과정을 감소할 수 있고 좌표 변환이 필요치 않기 때문에 간략화한 보상 알고리즘 구현이 가능하다. 본 연구의 타당성은 전력전자전용 시뮬레이터 PSIM에 의해 정상상태와 과도상태에서 입증하였다. 그 결과 3상 교류 전원 모두에 순간적인 전압 sag가 발생되거나, 임의의 상에 왜형 및 sag가 있는 경우, 전압 보상 및 고조파 전류 보상이 모두 가능함을 입증하였다.

Series Active Power Filters to Compensate Harmonics and Reactive Power with the Direct Compensating Voltage Extraction Method in Three-Phase Four-Wire Systems

  • Kim, Jin-Sun;Kim, Young-Seok
    • Journal of Power Electronics
    • /
    • 제9권5호
    • /
    • pp.691-699
    • /
    • 2009
  • This paper presents the analysis of series active power filter for reactive power compensation, load balancing, harmonic elimination, and neutral current eradication in three-phase four-wire power systems. Generally, the three-phase four-wire system is widely employed in distributing electric energy to several office building and manufacturing plants. In such systems, the third harmonic and its 3rd harmonics are termed as triple and zero sequence components that do not cancel each other in the system neutral. Consequently, the triple harmonics add together creating a primary source of excessive neutral current. Regarding this concern, this paper presents a new control algorithm for a series hybrid active system, whereas the control approach it adopts directly influence its compensation characteristics. Hence, the advantage of this control algorithm is the direct extraction of compensation voltage reference without phase transformations and multiplying harmonic current value by gain and the required rating of the series active filter is much smaller than that of a conventional shunt active power filter. In order to show the effectiveness of the proposed control algorithm, experiments have been carried out.

Three-Phase Hybrid Shunt Filters for Power Quality Improvement

  • Bhuvaneswari, G.;G.Nair, Manjula
    • Journal of Power Electronics
    • /
    • 제7권3호
    • /
    • pp.257-264
    • /
    • 2007
  • Active power filters can be cost-effective for use in practical systems with the insertion of a few passive elements in shunt or series configuration. The resulting hybrid filters can be designed to provide dominant lower order harmonic elimination and reactive power support by the passive elements so that the burden on the active filter counterpart is reduced. In this paper, the rate reduction in the shunt active filter is estimated when it is connected in parallel with suitable passive tuned harmonic filters. The active filtering system is based on an appropriate control scheme. The simulation and the experimental results of the shunt active filter, along with the estimated value of reduction in rating, show that the hybrid shunt filtering system is quite effective in compensating for the harmonics and reactive power, in addition to being cost-effective.

DVR 기능을 갖는 3상 하이브리드형 직렬 능동전력필터 (3-Phase Hybrid Series Active Power Filter with Dynamic Voltage Restorer)

  • 한석우;최규하
    • 전력전자학회:학술대회논문집
    • /
    • 전력전자학회 2002년도 전력전자학술대회 논문집
    • /
    • pp.598-602
    • /
    • 2002
  • This paper presents the 3-phase hybrid series active power filter with dynamic voltage restorer(DVR) which serve as an energy buffer and current harmonics blocking resistor connected to sensitive loads, such as, to compensate voltage dips and current harmonics in power distribution system. The DVR is to inject a dynamically controlled voltage generated by a forced commutated converter in series to the bus voltage by means of a booster transformer. The momentary amplitudes of the three injected phase voltages are controlled such as to eliminate any detrimental effects of a bus fault to the load voltage. The proposed system is able to simultaneously compensate current harmonics, voltage fluctuating and voltage unbalance in power distribution systems. The reference phase angle detected by synchronized with the positive sequence component of the unbalanced source by using symmetrical component transformation. The effectiveness of proposed system is verified by the computer simulation.

  • PDF

순간전압변동 보상 기능을 갖는 3상 하이브리드형 직렬 능동전력필터 (3-Phase Hybrid Series Active Power Filter with Instantaneous Voltage Fluctuations Compensation)

  • 이승요
    • 전력전자학회:학술대회논문집
    • /
    • 전력전자학회 2000년도 전력전자학술대회 논문집
    • /
    • pp.739-743
    • /
    • 2000
  • With significant development of power electronics technology the proliferation of nonlinear loads such as such as static power converters has deteriorated power quality in power transmission distribution systems. Notably voltage harmonics resulting from current harmonies produced by the nonlinear loads have become a serious problem in many systems Moreover momentary interruptions and voltage sags are responsible for many of the power quality problems found in typical industrial plants. Int his paper proposed 3 phase hybrid series active power filter is not only for harmonic compensation but also for harmonic isolation between supply and load and for voltage regulation and imbalance compensation Through computer simulations we have verified the effectiveness of the proposed system.

  • PDF

고조파 전류와 불평형 전원전압 보상을 위한 복합형 능동전력 필터 (Hybrid-Type Active Power Filters for Compensating Harmonic Current and Unbalanced Source Voltages)

  • 이지명;이동춘
    • 대한전기학회논문지:전기기기및에너지변환시스템부문B
    • /
    • 제51권5호
    • /
    • pp.249-257
    • /
    • 2002
  • In this paper, a novel control scheme compensating source voltage unbalance and harmonic currents for the combined system of series active and shunt passive power filter is proposed, where no low/high-pass filters are used in deriving the reference voltage for compensation. The phase angle and the reference voltages compensating for harmonic current and unbalanced voltage are derived from the positive sequence component of the unbalanced voltage set, which is simply obtained by using digital all-pass filters. In order to remove the phase delay in generating the reference voltage for compensation, the reference of 5th and 7th harmonic components is predicted one-sampling ahead. The validity of the proposed scheme has been verified for 3[kVA] proto-type active power filter system.