154kV 활선 애자련의 불량애자를 검출하는 활선애자 점검기 개발 (Development of Inspection Tool for 154kV Live-line Insulator string)

  • 이재경;박준영;오기용;조병학
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2008년도 학술대회 논문집 정보 및 제어부문
    • /
    • pp.373-374
    • /
    • 2008
  • To prevent an insulator failure, a new inspection system is presented for 154kV insulator strings. The inspection system detects fault insulators by measuring resistance and voltage of each insulators in the 154kV insulator string. The inspection instrument obtains autonomously insulation resistance and assigned voltage along the insulator string. The insulator inspection instrument is manipulated by two operators. In addition, a set of mechanism is applied to prevent the system from being reset under live-line condition. We confirmed its effectiveness through experiments.

  • PDF

미세 방전신호 분석을 통한 케이블 수(水)트리 활선 현장진단 (On-Line Cable Water-Tree Detection by the Analysis of Pre-Discharge Signals)

  • 정상진;김영민
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2008년도 추계학술대회 논문집 전기설비전문위원
    • /
    • pp.6-8
    • /
    • 2008
  • 배전케이블 수 트리 현상은 XLPE케이블의 고장을 초래하는 주요원인이다. 수 트리에 기인한 신호는 아주 미세하여 현장진단은 배경 잡음으로 인해 검출이 어렵다. 본 논문에서는 고주파특성이 우수한 L-C결합센서를 사용하여 방전신호를 측정하고 이를 주파수영역에서의 분석을 통해 현장에서 부분방전이 발생하기 훨씬 이전에 존재하는 미세신호(Pre-Discharge)를 검출하고 분석한 결과를 제시하였다. 케이블 내 수(水) 트리가가 존재하면 이것이 이종 절연물의 경계면 역할을 하석 서-지 임피던스의 차이로 인해 케이블 단자에서 발생하는 전기적 신호가 수 트리 지점에서 다수의 반사를 일으켜 그 잡음 수준을 높이는 역한을 하게 되는 것으로 알려져 있다. 만일 여러 개소에 수 트리가 존재하는 경우에는 그 배경잡음을 현저하게 높이는 결과를 보여주었다. 실험실에서 발생하는 미세 신호와 현장의 신호를 비교한 결과 아주 유사한 패턴이 있음이 파악되어 이 방법은 수 트리의 활선 진단이 가능함을 확인시켜 주었다.

  • PDF