• Title/Summary/Keyword: 피난안전구역

Search Result 36, Processing Time 0.023 seconds

Comparison of Airport Emergency Plans in Korea and Japan and Survey of Emergency Response of Airline Employees at Check-in Counter (한·일 공항비상계획 비교 및 체크인카운터의 항공사 직원 비상대응 실태조사)

  • Kwon, Kyum;Kwon, Byung Hwa;Cheung, ChongSoo
    • Journal of Korean Society of Disaster and Security
    • /
    • v.13 no.2
    • /
    • pp.11-25
    • /
    • 2020
  • This study is a basic study to improve responsiveness in the event of a disaster in the landside area of the Airport Passenger Terminal, and it investigated the airport emergency plan and the status of emergency response in the event of a disaster by the airline's ground staff. The Airport Emergency Plan examined the airport evacuation plan of Korea's Gimpo Airport and Japan's Ministry of Land, Infrastructure, and Transport, confirming that the domestic airport emergency plan was not specific. In addition, a survey of 100 airline ground employees working at check-in counters found that 69% of the respondents were unaware of their role in disaster situations, 90% were not educated in emergency response and 98% were not trained in disaster training in landside areas. Cross-analysis confirmed significant results in the safety of the airport where the service life worked and whether it was a role in the event of a disaster. Therefore, it is suggested that the airport emergency response plan should be improved to improve the ability to respond to disaster sites in the landside area of the airport passenger terminal and that the airline's ground staff should be educated and trained to enhance disaster response.

Optimum Evacuation Route Calculation Using AI Q-Learning (AI기법의 Q-Learning을 이용한 최적 퇴선 경로 산출 연구)

  • Kim, Won-Ouk;Kim, Dae-Hee;Youn, Dae-Gwun
    • Journal of the Korean Society of Marine Environment & Safety
    • /
    • v.24 no.7
    • /
    • pp.870-874
    • /
    • 2018
  • In the worst maritime accidents, people should abandon ship, but ship structures are narrow and complex and operation takes place on rough seas, so escape is not easy. In particular, passengers on cruise ships are untrained and varied, making evacuation prospects worse. In such a case, the evacuation management of the crew plays a very important role. If a rescuer enters a ship at distress and conducts rescue activities, which zones represent the most effective entry should be examined. Generally, crew and rescuers take the shortest route, but if an accident occurs along the shortest route, it is necessary to select the second-best alternative. To solve this situation, this study aims to calculate evacuation routes using Q-Learning of Reinforcement Learning, which is a machine learning technique. Reinforcement learning is one of the most important functions of artificial intelligence and is currently used in many fields. Most evacuation analysis programs developed so far use the shortest path search method. For this reason, this study explored optimal paths using reinforcement learning. In the future, machine learning techniques will be applicable to various marine-related industries for such purposes as the selection of optimal routes for autonomous vessels and risk avoidance.

A Study on the Performance Improvement Plan of Inflowing Air Emission (유입 공기의 배출 성능 개선방안에 관한 연구)

  • Lee, Hye-Young
    • Journal of the Society of Disaster Information
    • /
    • v.18 no.2
    • /
    • pp.241-251
    • /
    • 2022
  • Purpose: In the event of a fire in a high-rise building, if the smoke control area is not effectively protected, smoke or flames enter the stairwell, making it difficult to evacuate. When inflowing air is discharged from a closed corridor, a negative pressure is formed in the corridor, the pressure in the smoke control area becomes excessively high, and the force required to open the door during evacuation is exceeded. Also, if the air introduced into the hallway is not exhausted, the smoke may flow back into the smoke control area. This paper tried to identify the problems caused by the inflowing air and to find out how to improve the performance. Method: Using the CONTAM program, simulations were performed with the basic conditions and the modified conditions. Result: If the inflowing air was discharged from the sealed corridor, overpressure occurred in the Smoke Control Area and exceeded the opening force, and the prevent smoke backflow was insufficient in the layer where the inflowing air was not discharged. Conclusion: "Differential pressure exhaust damper" application, simultaneous opening of two exhaust dampers, and automatic window installation between corridors and outdoors improved the exhaust performance of inflowing air.

The Influence of Zoning at Shafts of Super-tall Buildings on the Stack Effect and Stairwell Pressurization (초고층건물 샤프트의 수직구획이 연돌효과 및 급기가압 성능에 미치는 영향)

  • Kim, Beom-Kyue;Kim, Hak-Jung;Yeo, Yong-Ju;Leem, Chae-Hyun;Park, Yong-Hwan
    • Fire Science and Engineering
    • /
    • v.26 no.5
    • /
    • pp.92-98
    • /
    • 2012
  • This study analyzed the effect of zoning on the distribution of pressure differentials caused by stack effect and air pressurization in a center core type of 80 story super-tall building. The results showed that maximum pressure difference more than 250 Pa can be generated by stack effect without zoning. Zoning of stairwell only resulted in 10 Pa reduction of maximum pressure difference, however, zoning of both stairwell and EV shaft especially at the same floor revealed 50 % reduction in stack effect. It was also analysed that the minimum required air flow rate occurred when the stairwell temperature reached 50 % of temperature difference between indoor and outdoor.

Study on Heat and Smoke Behavior Due to the Natural Wind and the Forced Smoke Ventilation for the Fire in an Underground Subway Station (지하역사에서 화재발생시 자연풍 및 강제배연의 유무에 따른 열 및 연기거동 특성 연구)

  • Chang Hee-Chul;Kim Tae-Kuk;Park Won-Hee;Kim Dong-Hyeon
    • Fire Science and Engineering
    • /
    • v.19 no.1 s.57
    • /
    • pp.80-86
    • /
    • 2005
  • In this study effects of the natural wind and the forced smoke ejection by operating the exhaust fan are studied numerically to examine the flow characteristics of the smoke and heat generated from a fire on the platform of an underground subway station. Three different situations, including 1) the case with no natural wind and no exhaust fan operation, 2) the case with natural wind but no exhaust fan operation and 3) the case with no natural wind but exhaust fan operation, are considered for the numerical analyses. The numerical results show that the natural wind causes a rapid spread of the fire along the tunnel resulting in rapid spread of the smoke and heat over the platform which affects the escape. The operation of the exhaust fan also results in the rapid spread of smoke and heat over the platform, but the time required for reaching the safe escaping height of the smoke layer with the exhaust fan operation is much longer than that without the exhaust fan operation. The numerical results also show that the required capacity of the exhaust fan becomes larger when the effect of the natural wind is included.

A study on the standard of effective fire facilities for the Atrium (아트리움 공간의 효과적인 방화설비 기준연구)

  • Choi, Don-Mook;Kim, Jae-Woon;Min, Se-Hong
    • Journal of Korean Institute of Fire Investigation
    • /
    • v.6 no.1
    • /
    • pp.49-66
    • /
    • 2005
  • The purpose of this study is to present reference data to be considered in designing fur the fire safety of atrium buildings. This study deals with the characteristics of atrium buildings in the fire safety aspect, analysis of fire examples and foreign fire codes of atrium space. And con-crete factors to be consigning fur the fire facilities of atrium buildings are presented. Recently many atrium spaces have been built in Korea. They provide new experience of space with resident and pedestrians. However, because of the lack of knowledge in design principle and disaster prevention, large loss of lives is expected in an emergency situation. cion. Therefore safety ensuring from the case is urgently needed. The following is the summary on the standard of effective fire facilities for the atrium. 1. The smoke control. inside atrium must use the machine ventilation in the atrium. 2. It is desirable to divide the section between atrium and nearby living room by anti-smoke screen in order to prevent damage by smoke when fire break out. 3. It is desirable to instill an excellent fire detector like infrared light detector as a replacement of old one. 4. It is desirable to transfer from closed operating sprinkler to fire-cycle sprinkler equipment or ablative sprinkler when the height is lower than 20m.

  • PDF