• Title/Summary/Keyword: 평판관

Search Result 116, Processing Time 0.021 seconds

Effect of Inclination Angle on the Heat Transfer and Pressure Drop Characteristics of Parallel Flow Heat Exchanger (경사각이 PF 열교환기의 열전달 및 압력 손실에 미치는 영향)

  • Kim, Do-Young;Ham, Jung-Ho;Kim, Nae-Hyun;Park, Nae-Hyun;Hwang, Jun-Hyun
    • Proceedings of the SAREK Conference
    • /
    • 2007.11a
    • /
    • pp.222-228
    • /
    • 2007
  • The effect of inclination angle on the heat transfer and pressure drop characteristics of brazed aluminum heat exchangers is experimentally investigated. Three samples having different fin pitches (1.25, 1.5 and 2.0 mm) were tested. Results show that heat transfer coefficient is not affected by the inclination angle. However, the friction factor increases as the inclination angle increases with negligible difference between the forward and backward inclination. Both the heat transfer coefficient and the friction factor are the smallest at $P_f$=1.5mm, followed by $P_f$=2.0mm and 1.25mm. Possible explanation is provided considering the louver layout. Comparison with existing correlations is also mad.

  • PDF

Air-side Performance of Louver-Finned Flat Aluminum Heat Exchangers at a Low Velocity Region (저속 영역에서 루버휜이 장착된 평판관형 알루미늄 열교환기의 공기측 전열 성능에 대한 실험적 연구)

  • Cho, Jin-Pyo;Oh, Wang-Kyu;Kim, Nae-Hyun;Youn, Baek
    • Transactions of the Korean Society of Mechanical Engineers B
    • /
    • v.26 no.12
    • /
    • pp.1681-1691
    • /
    • 2002
  • The heat transfer and pressure drop characteristics of heat exchangers with louver fins were experimentally investigated. The samples had small fin pitches (1.0 mm to 1.4 mm), and experiments were conducted up to a very low frontal air velocity (as low as 0.3 m/s). At a certain Reynolds number (critical Reynolds number), the flattening of the heat transfer coefficient curve was observed. The critical Reynolds number was insensitive to the louver angle, and decreased as the louver pitch to fin pitch ratio (L$_{p}$F$_{p}$) decreased. Existing correlations on the critical Reynolds number did not adequately predict the data. It is suggested that, for proper assessment of the heat transfer behavior, the louver pattern in addition to the flow characterization need to be considered. The heat transfer coefficient increased as the fin pitch decreased. At low Reynolds numbers, however, the trend was reversed. Possible explanation is provided considering the louver pattern between neighboring fins. Different from the heat transfer coefficient, the friction factor did not show the flattening characteristic. The reason may be attributed to the form drag by louvers, which offsets the decreased skin friction at a low Reynolds number. The friction factor increased as the fin pitch decreased and the louver angle increased. A new correlation predicted 92% of the heat transfer coefficient and 90% of the friction factor within $\pm$10%.10%.

Development of the Structure for Enhancing Capillary Force of the Thin Flat Heat Pipe Based on Extrusion Fabrication (압출형 박판 히트파이프의 모세관력 향상을 위한 구조 개발)

  • Moon, Seok Hwan;Park, Yoon Woo
    • Transactions of the Korean Society of Mechanical Engineers B
    • /
    • v.40 no.11
    • /
    • pp.755-759
    • /
    • 2016
  • The use of heat pipes in the electronic telecommunication field is increasing. Among the various types of heat pipes, the thin flat heat pipe has relatively high applicability compared with the circular heat pipe in the electronic packaging application. The thin flat heat pipe based on extrusion fabrication has a simple capillary wick structure consisting of rectangular cross sectional grooves on the inner wall of the pipe. Although the groove serves as a simple capillary wick, and many such grooves are provided on the inner wall, it is difficult for the grooves to realize a sufficiently high capillary force. In the present study, a thin flat heat pipe with a wire bundle was developed to overcome the drawback of poor capillary force in the thin flat heat pipe with grooves, and was evaluated by conducting tests. In the performance test, the thin flat heat pipe with the wire bundle showed a lower thermal resistance of approximately 3.4 times, and a higher heat transfer rate of approximately 3.8 times with respect to the thin flat heat pipe with grooves as the capillary wick respectively. The possibility of using the wire bundle as a capillary wick in the heat pipe was validated in the present study; further study for commercializing this concept will be taken up in the future.

축소 노즐에서의 슬롯 막냉각 열전달 특성에 관한 연구

  • 조용일;조형희
    • Proceedings of the Korean Society of Propulsion Engineers Conference
    • /
    • 2000.04a
    • /
    • pp.33-33
    • /
    • 2000
  • 고온의 연소가스로부터 노즐 표면을 보호하기 위하여 슬롯을 통하여 냉각 유체를 분사하는 슬롯 막냉각에 대하여 연구하였다. 냉각효율 및 열전달 특성은 주유동과 2차 유동의 분사율에 따라 크게 달라지며, 형상변화 및 유동가속에 의해서도 냉각 효과의 변화를 가져오게 된다. 따라서 본 연구에서는 실험을 통하여 면적비가 16:1인 축소노즐에서 압축성 효과를 배제할 수 있는 유동속도 범위 내에서 분사율 변화(0.5 $\leq$ M $\leq$ 3.0)에 따른 슬롯 막냉각 열전달 특성을 고찰하고, 평판 슬롯 막냉각 경험식의 결과와 비교하였으며, 수치해석을 통하여 축소노즐과 원형관에서의 냉각효율 및 열전달 특성을 비교함으로서 이를 검증하였다. 축소노즐에서의 슬롯 막냉각 열전달 특성은 단열벽면조건을 형성하여 노즐 표면을 따라 설치된 열전대를 이용하여 측정하였다. 그 결과 상대적으로 낮은 분사율(M=0.5, 1.0)에서 분사율 증가에 따른 냉각효율의 증가가 크게 나타났으며, 분사율이 높아짐(M $\geq$ 2.0)에 따라 냉각효율의 증가폭이 점점 감소하고, 일정 분사율 이상에서는 냉각 효율의 증가가 크게 둔화되었다. 분사율이 낮을 경우 평판 슬롯 막냉각 경험식으로 주어진 결과보다 상류에서는 높으나 하류로 진행하면 비슷한 냉각효율을 보였고, 분사율이 높은 경우 평판보다 전 범위에서 약간 높은 냉각효율을 나타냈다. 수치해석 결과에서는 분사율이 낮을 경우 축소노즐의 냉각효율이 원형관에서의 냉각효율 보다 낮거나 비슷하게 나타났으며, 분사율이 높아짐에 따라 축소노즐에서의 냉각효율이 오히려 높아지는 것으로 나타났다.타내었다. 액체 제트의 속도는 처음에는 일정하게 유지되다가 운동량을 보존하기 위해 가스로부터 운동량을 받아 점차 가속되어지는 것으로 나타났다.본 규격은 키, 총장, 어깨길이, 등길이, 머리길이, 머리둘레, 진동둘레, 목둘레, 가슴둘레, 허리둘레, 배둘레, 엉덩이둘레, 앞품, 뒤품, drop치를 포함하고 있고, 각 규격에서 호칭간 치수 간격도 함께 제시하고 있다. 본 연구 결과에서 보듯, 현행 8규격의 무진복의 각 호칭간 적정 허용범위를 고려해 합리적인 치수체계를 정립한다면 치수에 대한 적합도가 상당히 증가할 뿐 아니라 생산비용도 상당히 감축할 것으로 생각된다.나타났다. 4) 호감적 서비스능력 차원에서 세 독립변수간에 유의한 3원 상호작용이 존재하는 것으로 나타나( $F_{2,228}$=15.62, P<.001) 20대에 적합한 의복 착용시( $F_{2,228}$=3.98, P<.05)와 60대에 적합한 의복 착용시( $F_{2,228}$=16.55, P<.001) 점포유형과 격식차림간에는 유의한 상호작용이 존재하는 것으로 나타났다. 5) 호감을 구성하는 세 요인들이 구매의도에 미치는 영향을 조사한 결과 호감적 인상차원은 29%(P<.001), 호감적 서비스능력차원은 6%(P<.001)의 구매의도를 설명해 주는 것으로 나타났다. 본 연구결과 노년 소비자에게 호감을 주는 판매원의 외모는 구매의도에 영향을 주어 실버의류산업의 이익증대와 밀접한 연관을 갖는 서비스품질의 중요한 요인으로 밝혀졌다.중요한 요인으로 밝혀졌다.로운 단백질 EPSPS가 다른 여러 식물에 이미 존재하고 있는 단백질로서 우리가 이미 이러

  • PDF

Development of Differential Type Eddy Current Probe for NDT Evaluation of the Steam Generator Tube (증기발생기 전열관의 비파괴 탐상용 차등형 와전류 탐촉자 개발)

  • Jung, S.Y.;Son, D.;Ryu, K.S.;Park, D.K.
    • Journal of the Korean Magnetics Society
    • /
    • v.15 no.5
    • /
    • pp.292-297
    • /
    • 2005
  • Steam generator of a nuclear power plant has important rolls for the heat transfer and the isolation of radioactive materials. So bursting of the steam generator tube is directly related to the accident of nuclear power plants. Incone1600 has been used for the steam generator tube material. The material shows non-magnetic and metallic properties, eddy current NDT method has been employed for defects detection. In this work, a differential type of eddy current probe was developed to improve resolution of defect detection. To verify properties of the developed differential type eddy current probe, we have made reference material with SUS304 which has similar magnetic and electrical properties of Inconel600. Using the developed differential type eddy current probe, we can detect defect size of 0.25 mm in diameter and 0.2 mm in depth (volume of $1{\times}10^{-3}\;mm^3$) with the reference material.

Numerical Investigation of Dynamic Responses of a Thermal Elasto-plastic Tube under Kerosene-air Mixture Detonation (케로신-공기 혼합물의 데토네이션 하중에 의한 열탄소성 관의 동적 거동 해석)

  • Gwak, Min-cheol;Lee, Younghun;Yoh, Jai-ick
    • Journal of the Korean Society of Propulsion Engineers
    • /
    • v.20 no.5
    • /
    • pp.60-69
    • /
    • 2016
  • This paper presents a numerical investigation on kerosene-air mixture detonation and behaviors of thermal elasto-plstic thin metal tube under detonation loading based on multi-material analysis. The detonation loading is modeled by the kerosene-air mixture detonation which is compared with Chapman-Jouguet (C-J) condition and experimental cell size. To conform the elasto-plastic model, plastic and elastic behaviors are verified by Taylor impact and plate bending motion, respectively. The numerical results are compared with the theory on burst pressure of tube. The critical deformable thickness with the thermal softening considered is good agreement with the theoretical value.

Water Vapor Transmission for T800/AD6005 Based Composite Motor Case (T800/AD6005계 복합재 연소관의 습기 투과에 관한 연구)

  • 박명규;류백능;최영보;도영대
    • Journal of the Korean Society of Propulsion Engineers
    • /
    • v.2 no.1
    • /
    • pp.50-58
    • /
    • 1998
  • Water vapor transmission was tested in water bath controlled by $20^{\cire}C$, 90%RH for T800/AD6005 based composite motor case which made by filament winding method. We detected internal relative humidity of composite motor case by inserting the humidity detector through the head of motor case for the study of humidity transmission through the wall of composite motor case. We found out that this composite material appears the water vapor flux of 2.88${\times}$$10^{-9}$g/$\textrm{m}^2$sec and diffusivity of 7.98${\times}$$10^{-7}$$\textrm{mm}^2$/sec at $20^{\cire}C$, 90%RH water vapor condition.

  • PDF

An Experimental Study on Ground Reinforcement Effect of Concrete and Expansion Mat for Prevention of Buried Pipe Damage (지중매설관 손상 방지를 위한 콘크리트매트와 팽창매트의 지반보강효과에 관한 실험적 연구)

  • Park, Jeong-Jun;Shin, Heesoo;Yuu, Jungjo;Hong, Gigwon
    • Journal of the Korean Geosynthetics Society
    • /
    • v.18 no.1
    • /
    • pp.91-101
    • /
    • 2019
  • Recently, small-scale excavation like ground cavity restoration and buried pipe replacement works are being carried out in urban area, in order to improve living convenience. This paper describes experiment results on the ground reinforcement method that can reduce the buried pipe damage, when the differential settlement occurred due to poor compaction of ground below the buried pipe. Plate load tests were conducted to evaluate a reinforcement effect of ground using concrete mat and expansion mat in the ground below the buried pipe. The results showed that the stress reduction ratio by concrete mat and expansion mat according to the surcharge load was about 46%~48% and 39%~42%, respectively. Therefore, the differential settlement of the buried pipe and the ground deformation below the buried pipes were reduced by the reinforcement effect of the concrete mat and expansion mat. This means that it is possible to prevent a buried pipe damage due to underground cavity and ground subsidence, if concrete mat and expansion mat are reinforced in the ground below the buried pipe or on the ground between the buried pipes.

Natural Convection Heat Transfer from a Conducting Tube with Two Vertical Axial Fins (2개(個)의 수직(垂直) 평판(平板)핀을 가진 전도관(傳導管)으로 부터의 자연대류(自然對流) 열전달(熱傳達))

  • Chung, H.S.;Lee, C.J.;Kwon, S.S.
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.3 no.4
    • /
    • pp.222-230
    • /
    • 1991
  • Conjugate heat transfer by steady laminar natural convection from a conducting tube with two vertical axial fins has been studied by a finite difference numerical procedure under basic conditions; $Ra=10_6$, Pr = 5 and $L_F=0.15$. The maximum local tube Nusselt number appears at ${\theta}=140^{\circ}$ for $L_F=0.06$, at ${\theta}=130^{\circ}$ for $L_F=0.30$ and at ${\theta}=120^{\circ}$ for $L_F=0.30$, $L_F=0.06$, respectively. The maximum mean Nusselt number shows at $L_F=0.18$ for the downward fin and at $L_F=0.12$ for the upward fin. Therefore the optimized fin length is $L_F{\approx}0.15$ under these conditions. At $L_F=0.15$, the mean Nusselt number by increasing Rayleigh number is remarkably increased for downward fin and then is slowly increased except for downward fin, it by increasing Prandtl number is apparently increased at $Pr{\leq}2$, and slightly increased at Pr>2.

  • PDF

Heat Transfer Characteristics of Individual Rows for Fin-and-Tube Heat Exchangers (핀-관 열교환기의 열별 열전달 특성)

  • Kim, Nae-Hyun;Shin, Tae-Ryong;Han, Sung-Pil
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.19 no.2
    • /
    • pp.149-155
    • /
    • 2007
  • The row-by-row heat transfer characteristics of fin-and-tube heat exchangers were experimentally investigated. Three wavy fin samples having different rows (one, two and three) and one plain fin sample (three row) were tested for $600{\leq}Re_{D}{\leq}4,000$. The heat transfer data were obtained for individual rows, and the corresponding heat transfer coefficients were reduced from the data. Results showed that the heat transfer coefficients were strongly dependent on the tube row. The heat transfer coefficient decreased as the tube row increased. However, the row effect was different depending on the fin shape. For the wavy fin, the row effect significantly decreased as the Reynolds number increased, yielding approximately the same heat transfer coefficients at $Re_{D}{\approx}2,500$. For the plain fin, however, the row effect lasted for the whole Reynolds number range. The increased mixing of bulk flow by wavy channels appears to induce high heat transfer coefficient (accordingly diminishing row effect) at downstream rows. The heat transfer coefficients of individual rows were higher for heat exchangers having larger tube rows.