• Title/Summary/Keyword: 지중열원

Search Result 41, Processing Time 0.02 seconds

Numerical analysis of the vertical tube-in-tube ground coil heat exchanger (수직으로 매설된 이중관형 지중 열교환기에 대한 해석적인 연구)

  • 유지오;금성민;신현준
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.11 no.3
    • /
    • pp.339-348
    • /
    • 1999
  • A computer model was developed in order to predict the temperature distribution and the performance of the vertical tube-in-tube ground coil heat exchanger. This model has been validated by experimental results conducted by ORNL. The heat exchanger performance with the variation of the length is calculated and compared. As results, the heat exchanger performance is proportional to the length but the performance per unit length decreases. The minimum performance of 70m - PVC heat exchanger during cyclic operation for a week is obtained 20,054kJ/h for cooling operation and 13,915kJ/h for heating operation. And minimum temperature difference is $4.64^{\circ}C$ for cooling operation and $2.64^{\circ}C$ for heating operation. In each case, it is noted that the temperature difference between the pipe and the far-field occurs within 0.8m from the heat exchanger.

  • PDF

A Study of the Effect of Borehole Thermal Resistance on the Borehole Length (보어홀 전열저항이 보어홀 길이에 미치는 영향에 관한 연구)

  • Lee, Se-Kyoun;Woo, Joung-Son
    • Journal of the Korean Solar Energy Society
    • /
    • v.29 no.5
    • /
    • pp.20-27
    • /
    • 2009
  • The effect of borehole thermal resistance on the borehole length is studied. In performing this work a new concept BLRR(borehole length reduction rate) is developed based on the line source model. The solution of line source model is shown to be valid through the comparison with the data of thermal response test. It is shown that BLRR is a function of soil thermal conductivity(k) and borehole thermal resistance($R_b$). The value of BLRR increases with increasing k, which means reducing $R_b$ is more effective when k is high. The reduction of borehole length with change of $R_b$ is easily estimated with BLRR. The validity of BLRR is also examined with EED analysis.

Climatological Characteristics in the Variation of Soil temperature in Korea (우리나라 지중온도 변동의 기후학적 특성)

  • Kim Seoung-Ok;Suh Myoung-Seok;Kwak Chong-Heum
    • Journal of the Korean earth science society
    • /
    • v.26 no.1
    • /
    • pp.93-105
    • /
    • 2005
  • Climatological characteristics in the variation of soil temperatures in Korea were investigated using Korea Meterological Administration's observation data. And the impacts of soil moisture on the variation of soil temperature were examined using observed precipitation data. The climatological averages of soil temperatures are ranged from 14.4 to $15.0^{\circ}C$ regardless of depths. And they showed an latitudinal gradient with a warm temperature at the southern region and 'U' shape as in the air temperature with a high value along the coastal region. The relatively higher heat capacity and low conductivity of soil compared to those of the air resulted in the significant delay of the maximum and minimum date with depth. As a results, soil acts as a heat source during winter while a heat sink during summer. Global warming and urban heat island have increased the soil temperatures with an average rate $0.3\~0.5^{\circ}C/10-year$ as in the air temperature during last 30 years $(1973\~2002)$. However, the warming rate is maximized during spring contrary to the winter in the air temperature. The temporal variation of soil temperatures is strongly affected by that of soil moisture through an modification of the heat capacity and heat convection. In general, the increased soil moisture clearly decreased the temporal variations and increased the deep layer soil temperatures during cold season.

Integrity of Optical Fiber Sensor for Measurement of Ground Thermal Conductivity (지중 열전도도 측정을 위한 광섬유 센서의 건전성)

  • Yoon, Seok;Choi, Jung-Chan;Lee, Seung-Rae;Lee, Michael-MyungSub
    • Proceedings of the Computational Structural Engineering Institute Conference
    • /
    • 2011.04a
    • /
    • pp.157-160
    • /
    • 2011
  • 본 연구에서는 광섬유 센서 기반 스마트 모니터링 시스템이 지중 열전도도 측정에도 효율적으로 적용될 수 있는지를 분석하였다. 이를 위해 광섬유 온도센서를 이용하여 지반의 열전도도를 측정할 수 있는 열응답 시험기가 개발되었다. 개발된 열응답 시험기는 기존의 RTD(Resistance Temperature Detector) 온도 센서 외에 광섬유 센서의 한 종류인 FBG(Fiber Bragg Grating) 센서도 실시간적으로 측정할 수 있는 시스템으로 구성되어 있다. 개발된 장비의 적용성 검증을 위하여 주문진 표준사를 이용하여 모형토조 내에 일정한 간극비에 맞추어 시료가 조성되었으며 지중열교환기는 U자형 파이프가 사용되었다. 20시간동안 열응답 시험을 통하여 광섬유 센서와 RTD 센서를 동시에 이용하여 온도값을 측정하여 표준사의 열전도도 값을 산출하였다. 그 결과 모형실험을 통한 열전도도 값은 탐침법을 통해 얻어진 열전도도 값과 선형 열원 모델(line source model) 해석해와 거의 유사하게 나타났으며 광섬유 센서와 RTD 센서와의 온도차는 0.1~0.3$^{\circ}$로써 유사한 값을 나타내었다. 따라서 본 연구에서 개발된 광섬유 기반 열응답 시험기는 지반의 열전도도를 측정하는데 효과적으로 사용될 수 있음을 알 수 있었으며 향후 지열시스템 가동에 따른 지중열 교환기의 손상도 평가 및 경보시스템 개발을 위해 지중열교환기의 거동을 실시간으로 모니터링 하는데 있어서도 효과적으로 사용될 수 있을 것으로 생각된다.

  • PDF

Ground Air Heat Exchanger Design and Analysis for Air Source Heat Pump (공기열원 히트펌프를 위한 공기식 지중 열교환기(GAHX) 설계 및 분석 연구)

  • Lee, Kwang-Seob;Lyu, Nam-Jin;Kang, Eun-Chul;Lee, Euy-Joon
    • Journal of the Korean Society for Geothermal and Hydrothermal Energy
    • /
    • v.12 no.2
    • /
    • pp.1-6
    • /
    • 2016
  • A ground air heat exchanger (GAHX), also called earth air heat exchanger is a useful technology to be integrated with other renewable energy technologies. In this study, ground-air heat exchanger system for the air source heat pump is introduced. The purpose of this study is to design the volumetric flow rate and the length of GAHX system. A GAHX length model equation has been developed and used for calculation. GAHX thermal efficiency are recommended as 75% and 85% in order to optimize pipe length. $2,750m^3/h$, $2,420m^3/h$ of volumetric flow rate on 88.3m, 111.7m length are suggested for providing 7.5kW thermal capacity. And the number of path is recommended more than two to minimize pressure drop. For future study, advanced model equation study with ground thermal behavior and a more efficient GAHX design will be considered.

Evaluation of Ground Effective Thermal Conductivity and Borehole Effective Thermal Resistance from Simple Line-Source Model (단순 선형열원 모델을 이용한 지중 유효 열전도도와 보어홀 유효 열저항 산정)

  • Sohn, Byong-Hu
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.19 no.7
    • /
    • pp.512-520
    • /
    • 2007
  • The design of a ground-source heat pump system includes specifications for a ground loop heat exchanger where the heat transfer rate depends on the effective thermal conductivity of the ground and the effective thermal resistance of the borehole. To evaluate these heat transfer properties, in-situ thermal response tests on four vertical test boreholes with different grouting materials were conducted by adding a monitored amount of heat to circulating water. The line-source method is applied to the temperature rise in an in-situ test and extended to also give an estimate of borehole effective thermal resistance. The effect of increasing thermal conductivity of the grouting materials from 0.818 to $1.104W/m^{\circ}C$ resulted in overall increases in effective thermal conductivity by 15.8 to 56.3% and reductions in effective thermal resistance by 13.0 to 31.1%.

Evaluation of a Ground Heat Exchanger Appropriate for the Site of the Third Stage Construction of Incheon International Airport (인천국제공항 3단계 건설부지에 적합한 지중열교환기 시스템 평가 연구)

  • Cho, Nam-Hyun;Song, Jung-Tae;Yoon, Seok;Lee, Seung-Rae
    • Journal of the Korean Geotechnical Society
    • /
    • v.31 no.5
    • /
    • pp.23-33
    • /
    • 2015
  • In the present study, a ground heat exchanger was installed for each heat source in the system at the site to evaluate ground heat conductivity, constructability, and economic feasibility; the factors considered in the study included ground heat, groundwater, fillers (such as bentonite and pea pebbles) and the shape of the heat exchange pipe (e.g., U and D-U). The aim was to determine the ground heat exchanger appropriate for the geothermal system in the 3rd-phase construction of Incheon International Airport. A comparative cost analysis of the initial costs based on the above information showed that although the initial costs of the regular vertical closed loop-II and modified vertical closed loop were lower than those of the regular vertical closed loop-I, they could not be expected to deliver high economic efficiency from the viewpoint of constructability (filler injection, heat exchange pipe insertion). The initial costs proved to be higher in the case of Geohil.

Analysis of Effective Soil Thermal Conductivities and Borehole Thermal Resistances with a Line Source Method (선형열원법에 의한 지중유효열전도도와 보어홀 전열저항 해석)

  • Lee, Se-Kyoun;Woo, Joung-Son;Ro, Jeong-Geun
    • Journal of the Korean Solar Energy Society
    • /
    • v.30 no.4
    • /
    • pp.71-78
    • /
    • 2010
  • Investigation of the effective soil thermal conductivity(k) is the first step in designing the ground loop heat exchanger(borehole) of a geothermal heat pump system. The line source method is required by New and Renewable Energy Center of Korea Energy Management Corporation in analyzing data obtained from thermal response tests. Another important factor in designing the ground loop heat exchanger is the borehole thermal resistance($R_b$). There are two methods to evaluate $R_b$ : one is to use a line source method, and the other is to use a shape factor of the borehole. In this study, we demonstrated that the line source method produces better results than the shape factor method in evaluating $R_b$. This is because the borehole thermal resistance evaluated with the line source method characteristically reduces the temperature differences between an actual and a theoretical thermal behaviors of the borehole. Evaluation of $R_b$ requires soil volumetric heat capacity. However, the effect of the soil volumetric heat capacity on the borehole thermal resistance is very small. Therefore, it is possible to use a generally accepted average value of soil volumetric heat capacity($=2MJ/m^3{\cdot}K$) in the analysis. In this work, it is also shown that an acceptable range of the initial ignoring time should be in the range of 8~16hrs. Thus, a mean value of 12 hrs is recommended.

Effectiveness Assessment on the Soil Temperature of KMA as Ground Heat Source Using CFD in Pit Area (CFD를 이용한 기상청 지중온도의 피트부분 지중열원 유용성 평가에 관한 연구)

  • Min, Joon Ki;Kim, Jeong Tai
    • KIEAE Journal
    • /
    • v.8 no.5
    • /
    • pp.49-54
    • /
    • 2008
  • The experimental of temperature, humidity and velocity was taken from the underground pit which utilized the system of ground heat source quite similar to the cool-pit system. Also, through CFD analysis, one could review the effectiveness of analysis of future alternatives. Furthermore, the temperature range of mock up cool-pit system was analyzed by inputting the weather data of annual average soil temperature provided by KMA(Korea Meteorological Administration) into the fluid simulation of anticipated heat distribution. Firstly, the difference between the temperature of air exhaust of the pit or the temperature of air supply of the compressor room and the experimental data for the month of May from the CFD analysis came out to be $0.6^{\circ}C$ and $0.9^{\circ}C$ respectively with tolerance of 3.1% and 4.7%. Secondly, the difference between the temperature of air exhaust of the Pit or the temperature of air supply of the compressor room and the experimental data for the month of July from the CFD analysis came out to be $0.8^{\circ}C$ and $1.1^{\circ}C$ respectively with tolerance of 3.3% and 4.5%. Thirdly, for the month of May, the difference between the experimental data taken for the air exhaust of the Pit or the air supply of the compressor room and soil temperature provided by KMA for monthly and yearly average temperature of Jeonju region came out be $1.9^{\circ}C$ and $1.8^{\circ}C$ respectively with tolerance of 10.7% and 9.8%. Fourthly, for the month of July, the difference between the experimental data taken for the air exhaust of the Pit or the air supply of the compressor room and soil temperature provided by KMA for monthly and yearly average temperature of Jeonju region came out be $1.1^{\circ}C$ and $1.4^{\circ}C$ respectively with tolerance of 4.5% and 5.8%. The result of above experiments allowed us to establish CFD model set up as a verification tool that is based on experimental data collected within the Pit area. Also, one could confirm the possibility to apply weather data of soil temperature provided by KMA in order to anticipate proper value for CFD analysis.

Study on the characteristic of heat exchange for vertical geothermal system using the numerical simulation (수치 시뮬레이션을 이용한 수직밀폐형 지열시스템의 채열특성에 관한 연구)

  • Nam, Yu-Jin;Oh, Jin-Hwan
    • Journal of the Korean Solar Energy Society
    • /
    • v.34 no.2
    • /
    • pp.66-72
    • /
    • 2014
  • Ground source heat pump system can achieve high efficiency of performance by utilizing annually constant underground temperature to provide heat source for space heating and cooling. Generally, the depth of constant-temperature zone under the ground depends on surface heat flux and soil properties. The deeper the ground heat exchanger is installed, the higher the heat exchange rate can be acquired. However, in order to optimally design the system, it is necessary to consider both the installation cost and the system performance. In this study, performance analysis of ground source heat pump system according to the depth has been conducted through the case study.