• Title/Summary/Keyword: 외기냉방 제어

Search Result 17, Processing Time 0.022 seconds

Effects of Control Methods of Outdoor Air Cooling System on Energy Consumption in Building (외기냉방 시스템의 제어방법이 에너지 소비량에 미치는 영향에 관한 연구)

  • Hwang, Jin-Won;Ahn, Byung-Cheon
    • Journal of the Korea Academia-Industrial cooperation Society
    • /
    • v.16 no.6
    • /
    • pp.4253-4259
    • /
    • 2015
  • In this study, the effects of various control methods of outdoor air cooling control system on control characteristics and energy consumption in building are researched by simulation. The system analysis modelling is done by using TRNSYS program package, and the control performances with existing outdoor air cooling methods are compared with the control ones without outdoor air cooling. As a result, appropriate operating temperature conditions of outdoor air cooling system according to outdoor temperature changes are required, and the outdoor air/return air dry bulb temperature comparison control method among the control methods shows best responses in energy savings.

Reduction of Cooling Load using Outdoor Air Cooling (외기냉방을 이용한 냉방부하 절감 연구)

  • Kim, Min-Yang;Kim, Young-Il;Chung, Kwang-Seop
    • Journal of the Korean Society for Geothermal and Hydrothermal Energy
    • /
    • v.7 no.1
    • /
    • pp.51-58
    • /
    • 2011
  • Due to enhanced sealing and insulation of buildings, extensive use of glasses for building envelopes and increased use of heat generating office equipments, energy consumption of modem buildings for cooling is steadily increasing. With outdoor air cooling(ODAC) system, cooling load can be reduced by exchanging indoor air with the cold outdoor air during spring and fall seasons. If ODAC is operated based only on temperature, total cooling load may virtually increase if the outdoor humidity is high. To overcome this problem, ODAC should be controlled based on enthalpy. In this work energy saving characteristics of enthalpy controlled ODAC is studied using dynamic simulation. The result shows that cooling load can be reduced by 27% by adopting ODAC.

A study on the energy efficient operation of economizer cycle control (외기냉방제어의 효율적인 운영에 관한 연구)

  • Lee, H.W.;Leigh, S.B.
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.9 no.4
    • /
    • pp.545-551
    • /
    • 1997
  • As the cooling energy requirement in an office building increases due to the increased internal heat gains, the effort to minimize the energy consumption through efficient operation of existing HVAC systems will be beneficial. In this study, one of the energy conserving efforts in an office building, operational strategies of Economizer Cycle Control have been investigated through DOE-2.1E computer simulation. The findings can be summarized : 1) Economizer Cycle Control saves energy throughout the year, 2) Econo-Limit-T must be applied seasonally based on the outside and return air conditions, 3) use of Enthalpy control is more energy efficient than that of Temperature control.

  • PDF

Night Purge Control Strategies With Outdoor Air Temperature Conditions for Central Cooling System (중앙냉방시스템의 외기온도조건을 고려한 나이트 퍼지 제어방안에 관한 연구)

  • Hwang, Jin-Won;Ahn, Byung-Cheon
    • Journal of the Korea Academia-Industrial cooperation Society
    • /
    • v.16 no.10
    • /
    • pp.6759-6765
    • /
    • 2015
  • In this study, the effects of control strategies of night-purge control system on control characteristics and energy consumption for central cooling system in building are researched by simulation. The start time and set-point temperature for night-purge control with outdoor temperature changes and building cold storage performance are obtained. The system analysis modelling is done by using TRNSYS program package, and the control performances with suggested night-purge control method are compared with the existing control ones. As a result, the suggested night-purge control method shows maximum 16.8% and 28.6% energy saving in comparison with existing control method and conventional one without night-purge control, respectively.

Comparison of Cooling-Energy Performance Depending on the Economizer-Control Methods in an Office Building (이코노마이저 제어 방법에 따른 사무소 건물의 냉방 에너지 성능 비교)

  • Son, Jeong-Eun;Hyun, In-Tak;Lee, Jea-Ho;Lee, Kwang Ho
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.27 no.8
    • /
    • pp.432-439
    • /
    • 2015
  • Current building procedures seek to minimize external air supplies to reduce the energy consumption of air conditioning, resulting in a high dependency on mechanical ventilation. We therefore studied an economizer-cycle system, whereby the introduction of external air saves energy. We analyzed different economizer-control methods, addressing mixed-air temperatures and outdoor-air fractions according to outdoor-air temperatures; also, we analyzed the energy consumption of the three economizer-cycle control types using detailed EnergyPlus simulation modeling. A differential enthalpy control method showed a lower energy consumption range from 5.8% to 6.2% than that of other methods during the simulated period. A differential dry-bulb control method showed a 12.7% lower energy consumption than the no-economizer method in the intermediate period, but also showed 7.1% more energy consumption during the summer period. When latent heat was not removed due to high summer humidity, we found a significant level of resultant energy consumption.

쾌적환경제어 및 에너지 절감제어 응용(쾌적과 에너지 절감의 협조제어, VAV제어, 외기취입제어에 관하여)

  • 조추영
    • The Magazine of the Society of Air-Conditioning and Refrigerating Engineers of Korea
    • /
    • v.33 no.2
    • /
    • pp.32-40
    • /
    • 2004
  • 지구환경보호 관점에서 건물공기조화도 에너지 절감과 쾌적한 실내환경을 실현하는 것이 요구되고 있다. 본고에서는 BAS(빌딩오토메이션)로 실현하는 쾌적환경과 에너지 절감제어 응용에 관하여 소개하기로 한다. 쾌적한 에너지 절감제어 쾌적제어 (1) 협조제어 쾌적, 에너지절감, 운영경비절감 등 다양한 목적을 조화롭게 실현하는 제어이다. 예를 들면 쾌적하고 에너지절감제어에서는 여름철 냉방이나 겨울철 난방을 하는 경우에 있어서 무효한 에너지 사용을 억제하면서 실내환경을 유지하는 방법이다.(중략)

  • PDF

Cooling Performance Analysis of Ground-Source Heat Pump System with Capacity Control with Outdoor Air Temperature (외기 온도 제어 방식을 적용한 지열 히트펌프 시스템의 냉방 성능 분석)

  • Sohn, Byonghu
    • Journal of the Korean Society for Geothermal and Hydrothermal Energy
    • /
    • v.17 no.4
    • /
    • pp.68-78
    • /
    • 2021
  • In order to solve the increasing deterioration of the energy shortage problem, ground-source heat pump (GSHP) systems have been widely installed. The control method is a significant component for maintaining the long-term performance and for reducing operation cost of GSHP systems. This paper presents the measurement and analysis results of the cooling performance of a GSHP system using capacity control with outdoor air temperature. For this, we installed monitoring equipments including sensors for measuring temperature, flow rate and power consumption, and then monitored operation parameters from July 9, 2021 to October 2, 2021. From measurement results, we analyze the effect of capacity control with outdoor air temperature on the cooling performance of the system. The average performace factor (PF) of the heat pump was 6.95, while the whole system was 5.54 over the measurement period. Because there was no performance data of the existing GSHP system, it was not possible to directly compare the existing control method and the outdoor air temperature method. However, it is expected that the performance of the entire system will be improved by adjusting the temperature of cold water produced by the heat pump, that is, the temperature of cold water on the load side according to the outside air temperature.

A Study on the Control of Water Flow and Water Temperature in the Radiant Cooling System through Simulations (시뮬레이션을 통한 바닥복사냉방 시스템의 공급유량 및 냉수온도 제어에 관한 연구)

  • 김용이;윤혜림;여명석
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.13 no.6
    • /
    • pp.532-540
    • /
    • 2001
  • The objectives of this study are to analyze the control variables according to condensation occurrence, to find the range in floor surface temperature and frequency of condensation, and to evaluate the control methods through simulations when the radiant heating system is used for cooling. Through the simulation analysis the control methods such as on/off control, variable flow control and outdoor reset with indoor temperature feedback control are evaluated and compared. The results show that the lowest floor surface temperature is around $23^{\circ}C$, the surface condensation can be prevented by controlling indoor humidity within 20g/kg(DA0, and that outdoor reset with indoor temperature feedback control is more appropriate than on/off control and variable flow control with regard to prevention of the condensation and thermal comfort.

  • PDF

An Experimental Study on Control Performance of Radiant Floor Cooling Using Ondol (온돌을 이용한 바닥복사냉방의 제어성능에 관한 실험적 연구)

  • 김용이;임재한;한여명;김광우
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.13 no.11
    • /
    • pp.1165-1173
    • /
    • 2001
  • The objectives of this study are to analyze the application of radiant floor cooling and to evaluate the control methods through experiments when the radiant heating system is used for cooling. Through the experiment analysis the control methods such as on/off control, variable flow control and outdoor reset with indoor temperature feedback control are evaluated and compared. The cooling curve (reset ratio) is found for radiant cooling, which shows tole relation between outside air temperature and supply water temperature. Comparison of cooling methods shows that outdoor reset with indoor temperature feedback control is more appropriate than on/off control and variable flow control with regard to prevention of the condensation and thermal comfort.

  • PDF