Comparison of Cooling-Energy Performance Depending on the Economizer-Control Methods in an Office Building

이코노마이저 제어 방법에 따른 사무소 건물의 냉방 에너지 성능 비교

  • 손정은 (국립한밭대학교 대학원 건축공학과) ;
  • 현인탁 (국립한밭대학교 대학원 건축공학과) ;
  • 이재호 (국립한밭대학교 대학원 건축공학과) ;
  • 이광호 (국립한밭대학교 건축공학과)
  • Received : 2015.05.20
  • Accepted : 2015.07.17
  • Published : 2015.08.10

Abstract

Current building procedures seek to minimize external air supplies to reduce the energy consumption of air conditioning, resulting in a high dependency on mechanical ventilation. We therefore studied an economizer-cycle system, whereby the introduction of external air saves energy. We analyzed different economizer-control methods, addressing mixed-air temperatures and outdoor-air fractions according to outdoor-air temperatures; also, we analyzed the energy consumption of the three economizer-cycle control types using detailed EnergyPlus simulation modeling. A differential enthalpy control method showed a lower energy consumption range from 5.8% to 6.2% than that of other methods during the simulated period. A differential dry-bulb control method showed a 12.7% lower energy consumption than the no-economizer method in the intermediate period, but also showed 7.1% more energy consumption during the summer period. When latent heat was not removed due to high summer humidity, we found a significant level of resultant energy consumption.

Keywords

References

  1. Jeong, C. S., 2010, Study on Uses of the HVAC Humidifier in the Office Building, Ph.D. Dissertation. Hanyang University, Seoul, South Korea.
  2. Kim, S. Y., Yoon, S. J., Jung, D. Y., Lee, K. H., 1992, A Study on the Indoor Air Quality of th Offices, In Proceedings of the Spring Conference of AIK, Seoul, South Korea, pp. 245-248.
  3. Kwon, K. W., and Park, J. S., 2007, Cost Benefit Analysis of Improved Indoor Air Quality in Office Building, Journal of AIK, Vol. 23, No. 10, pp. 203-212.
  4. Lim, S. H., 2002, A Study on the Energy Efficient Control Strategies of Outdoor Air Introduction in Office Buildings, Ph.D. Dissertation, Konkuk University, Seoul, South Korea.
  5. Kim, M. Y., Kim, Y. I., Chung, K. S., 2011, Reduction of Cooling Load using Outdoor Air Cooling, Journal of KSGEE, Vol. 7, No. 1, pp. 51-58.
  6. Son, J. E., Hyun, I. T., Lee, J. H., Lee, K. H., Comparison of Cooling Energy Performance depending on The Economizer Control Methods in an Office Building, In Proceedings of the Summer Conference of SAREK, Yongpyong, South Korea, pp. 202-205.
  7. Choi, B. E., Shin, K. J., Jung, Y. J., Kim, H. J., Cho, Y. H., 2013, A Study on the Effect of Energy Saving of Economizer(Air Handling Unit) Through Simulation, In Proceedings of the Winter Conference of AIKRA, Seoul, South Korea, pp. 497-500.
  8. The U. S. DOE. 2011, EnergyPlus Input Output Reference, The Encyclopedic Reference to EnergyPlus Input and Output.
  9. Winkelmann, F., 2001, Modeling Windows in Energy Plus, Building Simulation 2011 in : 7th International IBPSA Conference.
  10. ASHRAE, 2013, ANSI/ASHRAE Standard 62.1-2013-Ventilation for Acceptable Indoor Air Quality.
  11. ASHRAE, 2005, ASHRAE Handbook Fundamentals. Atlant a : American Society of Heating Refrigerating and Air-Conditioning Engineers, Inc.
  12. ASHRAE, 2007, ASHRAE Handbook Fundamentals. Atlant a : American Society of Heating Refrigerating and Air-Conditioning Engineers, Inc.
  13. KEMCO, Energy Saving Technology Instruction Manual of Public Buildings, p. 10
  14. Kang, S. H., Yu, S. W., Cho, Y. H., 2011, The Analysis of Energy Performance and Thermal Comfort for the Dual Maximum Control Logic at the VAV Terminal, In Proceedings of the Autumn Conference of KIAEBS, Seoul, South Korea, pp. 105-108.

Cited by

  1. Recent Progress in Air-Conditioning and Refrigeration Research : A Review of Papers Published in the Korean Journal of Air-Conditioning and Refrigeration Engineering in 2015 vol.28, pp.6, 2016, https://doi.org/10.6110/KJACR.2016.28.6.256