• 제목/요약/키워드: 변류기

검색결과 90건 처리시간 0.029초

차분을 이용한 변류기 포화 검출 알고리즘의 저역통과 필터의 영향 분석 (Performance Analysis on a Low Pass Filter of a CT Saturation Detecting Algorithm Using Difference of the Secondary Current)

  • 강용철;옥승훈;윤재성;김대성
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2001년도 하계학술대회 논문집 A
    • /
    • pp.249-251
    • /
    • 2001
  • This paper presents performance analysis on a low pass filter of a CT saturation detecting algorithm using difference. At the instants of beginning/end of saturation, the shapes of the secondary current are changed significantly though secondary currents are continuous. At the instants, the second-order or third-order difference of the secondary current has big values because of discontinuity of the first order difference. Thus, the third difference of the current is used to detect the beginning/end of CT saturation. An antialiasing low pass filter removes high frequency components and causes phase lag. A CT saturation detecting algorithm using difference of CT secondary currents is affected by the low pass filter. The algorithm is tested with cutoff frequencies of the filter for the two sampling rates of 64[S/C] and 32 [S/C]. The results of various test cases indicate satisfactory performance of the algorithm.

  • PDF

WS시리즈 누설전류표시부 차단기

  • 대한전기협회
    • 전기저널
    • /
    • 통권307호
    • /
    • pp.68-73
    • /
    • 2002
  • 감전보호$\cdot$누전화재보호로서 누전차단기가 일반적으로 사용되고 있는데 이 누전차단기가 누전으로 트립되었을 경우 (1) 누전트립이 재현되지 않는다. (2) 누설전류치가 고조파의 영향 때문에 측정이 곤란하다는 등의 이유로 원인조사가 어려운 경우가 많다. 그래서 누전차단기의 동작원인조사를 지원하는 기기로서 WS시리즈의 노퓨즈차단기 및 누전차단기에 각종 누설전류치의 액정표시유닛을 탑재한 $''$누설전류표시부 노퓨즈차단기$\cdot$누전차단기$''$를 제품화하였다. 이에 의하여 전로에 영상변류기(ZCT)와 계측기 등을 설치하지 않고 전로의 절연열화상태나 누전사고 상황을 간단하게 파악할 수가 있다. 또 액정표시유닛의 제어전원은 차단기 내부에 포함하고 있기 때문에 특별배선작업은 불필요하다. 이 제어전원은 차단기가 오프상태 또는 트립상태에서는 끊어지나 내부에 전기이중충 콘덴서를 내장하고 있기 때문에 각종 누설전류 정보를 표시할 수가 있다(정전보상시간 100시간). 주요특징은 다음과 같다. (1)각종 누설전류의 계측과 표시(현재치, 최대치, 이동평균치, 이동평균의 최대치, 각 최대치의 발생경과시간) (2) 누전경보의 설정 감도를 세분화하여 설정가능 또한 접점경보출력 표준탑재 (3) 누전트립 발생시의 누전사고전류치 및 누전사고 발생으로부터의 경과시간 표시(누전차단기만) (4) 미쓰비시전기 누전차단기의 액티브필터와 같은 특성의 필터를 내장하고 있으며 누전차단기의 동작특성에 맞는 누설전류치 표시가능 (5) 누전경보만으로 누전트립 동작을 하지 않는 누설전류표시부 노퓨즈차단기 라인업

  • PDF

철심 변류기의 2차 전류 보상 알고리즘의 실시간 구현 및 오차 분석 (Hardware implementation and error analysis of an algorithm for compensating the secondary current of iron-cored current transformers)

  • 강용철;김성수;박종근;강상희;김광호
    • 대한전기학회논문지
    • /
    • 제45권4호
    • /
    • pp.490-500
    • /
    • 1996
  • The conventional method to deal with current transformer (CT) Saturation is over dimensioning of the core so that CTs can carry up to 20 times the rated current without exceeding 10% ratio correction. However, this not only reduces the sensitivity of relays as some errors may still be present in the secondary current when a severe fault occurs, but also increases the CT size. This paper presents an algorithm for compensating the distorted secondary current of iron-cored CTs under CT saturation using the magnetization (flux-current : .lambda.-i) curve and its performance is examined for fault currents encountered on a typical 345[kV] Korean transmission system, under a variety of different system and fault conditions. In addition, the results of hardware implementation of the algorithm using a TMS320C10 digital signal processor are also presented. The proposed algorithm can improve the sensitivity of relays to low level internal faults, maximize the stability of relays for external faults, and reduce the required CT core cross-section significantly. (author). refs., figs.

  • PDF

가공배전선로의 전력설비 감시를 위한 유비쿼터스 센서 (Ubiquitous Sensors for Supervision of Power Facilities in Overhead Power Distribution Lines)

  • 길경석;박대원;김일권;최수연;박찬용
    • 조명전기설비학회논문지
    • /
    • 제21권10호
    • /
    • pp.59-65
    • /
    • 2007
  • 최근 유비쿼터스 센서네트워크 기술이 전력설비관리에 적용되어 오고 있다. 본 연구에서는 가공배전선로에서 전력용변압기와 피뢰기를 관리할 수 있는 유비쿼터스 센서의 설계 및 제작에 대해 기술하였다. 이 센서들은 8-[bit] 마이크로프로세서, IEEE 802.15.4기반 무선통신모듈과 주변 전자회로로 구성되어 있다. 변압기의 부하 및 서지전류 측정에는 1000[A]까지 포화되지 않고 선형성을 유지할 수 있도록 공심형 로고우스키 코일을 제작하여 적용하였다. 피뢰기를 흐르는 $50[{\mu}A]{\sim}1[mA]$의 미소누설전류를 측정하기 위하여 180[Hz]에서 $10^5$의 고투자율을 갖는 영상변류기를 사용하였으며, 피뢰기 감시모듈의 -3[dB] 주파수 대역은 12[Hz]에서 1.24[kHz]이다.

운전 중인 고전압 케이블의 절연저항 측정 및 수명평가장치의 개발 (Development of Equipment to Measure Insulation Resistance and Evaluate the Lifetime of High-voltage Cable in Operation)

  • 엄기홍;이관우
    • 한국인터넷방송통신학회논문지
    • /
    • 제14권5호
    • /
    • pp.237-242
    • /
    • 2014
  • 이 논문은 발전소에서 설치 운전 중인 6.6kV 고전압 케이블이 시간에 따라 성능이 악화되는 현상의 추세를 결정하는 수명지수를 파악하기 위한 논문이다. 우리가 연구한 케이블 시스템은 설치 후 13 년 동안 운전하고 있다. 삼상전력에 연결되는 변류기, 온도센서 LPF 등을 이용한 측정장치를 개발하여 케이블의 절연저항 변화 특성을 해석하였다. 고전압 22kV 케이블과 비교하면 절연체의 두께가 더 두껍기 때문에 특성을 다르게 나타낸다. 동작시간이 경과함에 따라, 절연저항이 계속 감소하지 않음을 확인 하였다. 일정한 값으로 감소하다가 더 이상 감소하지 않고 상하진동하는 특성을 나타내었다. 지난 13 년 동안의 열화과정을 파악할 수 없었지만, 시스템이 안정 상태에서 동작을 하였다는 사실은 열화가 아직 발생하지 않았다는 의미이다. 이런 경우에는, 수명지수를 예측할 수 없기 때문에 케이블의 수명을 정량적으로 예측할 수 없음을 확인하였다.

포화를 방지하기 위한 보호용 철심 변류기 설계 방법 (A Design Method of Iron-cored CTs To Prevent Satruation)

  • 이주훈;강상희;강용철;이승재;배주천;안준기;이청학;이정택
    • 대한전기학회논문지:전력기술부문A
    • /
    • 제48권2호
    • /
    • pp.119-126
    • /
    • 1999
  • Current transformer (CT) saturation may cause a variety of protective relays to malfunction. The conventional CT is designed that it can carry up to 20 times the rated current without exceeding 10% ratio error. However, the possibility of CT saturation still remains if the fault current contains substantial amounts of ac and/or dc components. This paper presents a design method of iron-cored CTs for use with protective relays to prevent CT saturation. The proposed design method determines the core cross section of the CT; it employs the transient dimensioning factor to consider relay's operating time (duty cycle) and dc component as well as ac components contained in the fault current, and symmetrical short-circuit current factor to consider as well as ac components contained in the fault current, and symmetrical short-circuit current factor to consider the biggest fault current. The method designs the cross section of CTs in cases of reclosure and no reclosure.

  • PDF

자속-자화 전류 곡선과 전압-철손 전류 곡선을 이용한 측정용 철심 변류기의 보상 알고리즘 개발 (Development of a Compensating Algorithm for an Iron-cored Measurement CT using Flux-magnetizing Current Curves and Voltage-core Loss Current Curves)

  • 강용철;정태영;강해권;이병은;김용균
    • 전기학회논문지
    • /
    • 제58권10호
    • /
    • pp.1849-1854
    • /
    • 2009
  • This paper describes the design, evaluation and implementation of a compensating algorithm for an iron-cored measurement current transformer (CT) that removes the effects of the hysteresis characteristics of the iron-core. The exciting current resulting from the hysteresis characteristics of the core causes an error of the CT. The proposed algorithm decomposes the exciting current into the core loss current and the magnetizing current and each of them is estimated. The core loss current is calculated from the secondary voltage and the voltage-core loss current curve. The core flux linkage is calculated and then inserted into the flux-magnetizing current curve to estimate the magnetizing current. The exciting current at every sampling interval is obtained by summing the core loss and magnetizing currents and then added to the measured current to obtain the correct secondary current. The voltage-core loss current curve and flux-magnetizing current curves, which are different from the conventional curves, are derived in this paper. The performance of the proposed algorithm is validated under various conditions using EMTP generated data. The experimental test results of an iron-core type electronic CT, which consists of the iron-core and the compensation board, are also included. The results indicate that the proposed algorithm can improve the accuracy of the measurement CT significantly, and thus reduce the size and the cost of the CT.

히스테리시스 특성을 고려한 측정용 변류기 보상 알고리즘 (Compensating algorithm for a measurement type CT considering hysteresis characteristic of the core)

  • 강용철;정태영;이병은;소순홍;이현웅;이미선;박정호;최현태;장성일;김용균
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2007년도 제38회 하계학술대회
    • /
    • pp.44-45
    • /
    • 2007
  • This paper deals with error compensation in current transformers. Since the exciting current can be considered as the main error source, its evaluation can allow the compensation of its detrimental effects to be obtained. The exciting current required by the transformer in every king of steady state operation can be determined by simply acquiring the secondary current, provided that the examined CT has been preliminarily identified. This paper also proposed a new approach to the model of the exciting branch. The exciting branch can be divided into a non-linear core loss resistor, and a non-linear magnetizing inductor whose flux and current characteristic is not the same as the characteristic shown by the joined tips of the first quadrant of a family of hysteresis loops. The performance of the proposed algorithm was validated under various conditions using EMTP generated data. Test result show, in all cases an improvement in primary current reproduction accuracy, compared with that achieved using CT's ratio.

  • PDF

증강현실(Augmented Reality)기반 유도시스템 아이디어와 구현에 관한 연구 (A Study on Idea and Implementation of Augmented Reality-based Guidance System)

  • 박명석;권순영;김경욱;강동혁;권승언;남궁웅;곽성주
    • 한국정보처리학회:학술대회논문집
    • /
    • 한국정보처리학회 2022년도 추계학술발표대회
    • /
    • pp.989-991
    • /
    • 2022
  • 최근 들어 기후변화와 함께, 화재 발생이 증가함에 따라 인명피해와 경제적 피해가 늘고 있다. 화재 발생시 인명 피해를 줄여주는 소방시설 중 경보설비와 유도등설비는 위험 상황시 경보와 함께 동선을 유도하는 유도등을 보고 재실자들이 안전한 공간으로 신속하게 대피할 수 있도록 하는 소방설비 이다. 이중에서 유도등설비는 화재발생 상황에서 매우 중요한 역할을 맡고 있다. 특히 복잡한 동선을 가지고 있는 복합건물 및 지하철, 고층건축물에 신속한 대피 유도에 필요한 설비이다. 그러나, 화재 초기에 신속한 대피를 해야 하는데 5분도 되지 않아 화재로 인해 발생한 가스는 검은 연기로 유도등의 역할과 효과를 저해하는 현상을 가져온다. 즉 유도등의 녹색빛이 보이지 않는다. 이는 저시력자 또는 시력에 장애를 가지고 있는 자들은 더욱더 유도등을 확인하고 대피 하기란 쉽지 않게 된다. 이런 단점이 있는 기존의 유도등에 IoT(Internet of Things)와 함께 증강현실 이미지를 스마트기기에 활성화 한다면, 진한 검은연기로 인한 빛의 가림으로 인한 유도장애에 대해서 개선 할 수 있을 거라 생각되어, 변류기의 전류 감지를 시작으로 그 신호를 스마트기기에 녹색의 유도 이미지를 활성화하여 골든타임에 대피가 신속하도록 설비를 구현하여 그 가능성을 확인하였다.

XLPE 케이블에서 보이드 결함의 부분방전 특성과 위치추정 (Partial Discharge Characteristics and Localization of Void Defects in XLPE Cable)

  • 박서준;황성철;왕국명;길경석
    • 한국철도학회논문집
    • /
    • 제20권2호
    • /
    • pp.203-209
    • /
    • 2017
  • 전력공급의 안정성 및 신뢰도 향상을 위해 각종 전력설비의 예방진단에 관한 연구개발이 활발하다. 가스절연개폐장치와 변압기와 같은 단위 기기의 절연진단기술은 빠르게 발전하고 있으나, 전력케이블에 있어서는 단순히 결함의 유무와 부분방전을 측정할 뿐, 세부적 특성에 대해서는 거의 연구되고 있지 않다. 따라서 본 논문에서는 XLPE 케이블에서 보이드의 크기와 위치에 따른 부분방전 특성과 결함의 위치추정에 관한 연구를 수행하였다. 보이드의 크기 및 위치에 따른 4종의 결함계를 모의하였으며, 부분방전펄스는 주파수 대역 150kHz~30MHz의 고주파변류기로 검출하였다. 실험결과, 도체에 인접한 결함일수록 방전전하량이 크고, 정극성에 비해 부극성의 방전펄스 수가 약 20% 많게 나타났다. 또한 TDR 방법으로 결함위치를 산출하였으며, 50m 케이블에서 1m 이내로 결함의 위치를 추정할 수 있었다.