• 제목/요약/키워드: 배전 선로

검색결과 671건 처리시간 0.034초

가공 배전선로 활선 정비 로봇 시스템의 기술 타당성 검토 (Technical Feasibility Study on Live-line Maintenance Robot System for Overhead Distribution Lines)

  • 박준영;이윤건;장영식
    • KEPCO Journal on Electric Power and Energy
    • /
    • 제8권2호
    • /
    • pp.49-53
    • /
    • 2022
  • The distribution live-line work method is an operation method of working in a state in which electricity flows through overhead distribution lines to minimize inconvenience to electric customers due to power failure. In June 2016, to strengthen the safety of electrical workers, Korea Electric Power Corporation announced that it would in principle abolish the rubber glove method, in which workers wore protective equipment such as rubber gloves and performed their maintenance work. In addition, KEPCO announced that it would develop a short-range live working method using smart sticks and an advanced live-line maintenance robot system where workers work without touching wires directly. This paper is a preliminary study for the development of the live-line maintenance robot system, and deals with the results of analyzing the technical feasibility of whether the live works performed by workers can be replaced by robots or not.

스마트 홈을 위한 스마트그리드 보호 방안 연구 (A Study on Smart Grid Security in Smart Home)

  • 김미주;정현철;이재일
    • 한국정보처리학회:학술대회논문집
    • /
    • 한국정보처리학회 2010년도 추계학술발표대회
    • /
    • pp.1316-1319
    • /
    • 2010
  • 스마트 홈은 유무선 통신 인프라를 기반으로 댁내 다양한 기기 간 통신을 가능하게 함으로써 사용자에게 원격 에너지 관리, 방범, 의료 등 자동화된 지능형 서비스를 제공할 것으로 기대되고 있다. 이는 기존 전력망에 IT 기술을 융합하여 효율적인 전력 에너지의 송 배전 및 실시간 정보 서비스를 제공하는 스마트 그리드 기술을 기반으로 하고 있으며, 사용자 실생활과 밀접한 관계를 가지기 때문에 보안 문제 발생 시 치명적인 피해를 입힐 수 있다는 특징을 가진다. 이에 본 논문에서는 스마트 홈 및 스마트그리드에 대한 분석을 통해 안전한 스마트 홈을 위한 스마트그리드 보호 방안을 도출한다.

LVDC용 SiC기반 다중전압(48V/80V) 200A급 스마트 지게차 충전기 (Development of Multi-Charging Voltage (48V/80V) 200A Smart Forklift Battery Charger based on SiC-FET for LVDC)

  • 안정훈;선다운;송성근
    • 전력전자학회:학술대회논문집
    • /
    • 전력전자학회 2020년도 전력전자학술대회
    • /
    • pp.457-458
    • /
    • 2020
  • 본 논문은 저전압 직류배전 (LVDC)이 도입된 공장 및 물류센터 등 에서 다수의 전동 지게차를 운용할 때, 효과적으로 충전할 수 있는 지게차 배터리 충전기를 제안하였다. 제안하는 충전기는 SiC 반도체 및 의도적으로 비대칭으로 설계한 공진 인덕터를 사용한 두 개의 위상천이 풀브릿지 컨버터로 구성된다. 이를 통하여 최대 200A급 고속 충전 및 다종의 배터리 규격 (48V, 80V) 대응과 함께 고효율, 고전력밀도를 달성 하였다.

  • PDF

고압 가공배전선의 노화된 ACSR-OC 도체에 대한 열화진단시스템 개발 (Development of Deterioration Diagnosis System for Aged ACSR-OC Conductors in HV Overhead Distribution Lines)

  • 김성덕;이승호
    • 조명전기설비학회논문지
    • /
    • 제14권6호
    • /
    • pp.43-50
    • /
    • 2000
  • 본 논문에서는 국내의 고압 가공배전선으로 일반적으로 사용되는 ACSR-OC의 열회를 검출하기 위하여, 솔레 노아드 와류센서를 가진 비파괴 검사시스템의 설계와 실험을 다루었다. ACSR-OC 도체에 대한 부식기구와 열회 상태를 검토하므로써, 부식이 도채의 유효단면적을 감소시키는 것을 확인하였다. 노화도체의 극심한 부적정도룹 검출하고 정량화하기 위한 실용적인 전기.자기적인 방법올 제시하였다. 고주파 정전류원, 신호처리 부와 모터 구동/제어기로 구생되눈 계측시스템이 설계되고 시험되었다. 이 장치는 센서의 출력을 검출하고 검사도체의 직경변화를 연속적으로 추정하는 기능을 갖고 있다. 그 결과, 와류센서를 가진 부각검출시스템은 가공 재전선의 열화에 기인한 심각한 결함을 추정하고 극심한 노호도체가 단선되기 전에 사전 경고를 하는데 양호한 효용성을 나타내는 것을 확인하였다.

  • PDF

EMTP-RV를 이용한 변전소 모선 방식과 보호협조 기초 논리 설계 방법론에 대한 연구 (Design Methodology of the Bus Configuration and Protection Coordination Basic Logics of Power Substation Using EMTP-RV)

  • 고윤석
    • 한국전자통신학회논문지
    • /
    • 제14권6호
    • /
    • pp.1129-1138
    • /
    • 2019
  • 변전소는 변전설비들이 제한된 장소에 집중되어 구조적으로 복잡하기 때문에 송전선로나 배전선로 상에서 고장발생 시 고장파급효과를 최소화하기 위한 보호협조 시스템을 설계하기가 쉽지 않다. 본 연구에서는 변전소 전력공급 신뢰성에 핵심적인 영향을 미치는 모선 방식과 보호협조 기초논리를 분석하였으며 EMTP-RV 기반으로 변전소 내부 및 외부 고장을 정확하게 검출하기 위한 변전소 보호협조 논리를 모델링하였다. 변전소 보호협조 기본 논리로서 변전소 내부 고장 검출을 위한 비율차동 보호계전 논리와 외부고장을 추론하기 위한 과부하 보호계전 논리가 모델링되었다. 끝으로, EMTP-RV를 이용하여 개발된 보호협조 논리 모델링을 기반으로 154kV 변전소를 모델링한 후, 수개의 고장모의를 통해 EMTP-RV 모델링 결과의 유효성을 확인하였다.

안정적 전력공급을 위한 154kV 변전소 배전선로간 연계운영에 관한 연구 (A Study on Loop operation of 154kV Substation Distribution line for Stable power supply)

  • 김광호;손명권;정종찬
    • 산업기술연구
    • /
    • 제29권B호
    • /
    • pp.221-228
    • /
    • 2009
  • For a stable supply of electric power, periodical inspection of the electric facilities and repair of the distribution lines are required. In case of any unexpected accidents, looped operation among distribution lines may be necessary in order to supply electricity through the sound lines, separating the faulted lines. As a result of this study, it was found that normal looped operation became impossible when phase difference of the looped distribution lines is more than 3 degrees compared with the voltage supply of the distribution lines. Therefore, for a stable supply of electric power to Chuncheon, it is judged to be desirable that looped operation of the distribution lines coming from the same substation M. Tr Bank shall be performed in principle and in case of looped operation with the substation of different system, looped operation among the lines shall be performed after voltage regulation of the substation M. Tr Bank, maintaining similar voltages and load supply volume in order to avoid phase difference through checking the operation conditions of each substation M. Tr Banks. And when looped operation among the distribution lines is scheduled, voltage regulation schedule has been established so far by calculating maximum supply volume through the transformer of the substation and the maximum load volume through the distribution lines but in the future, looped operation of the distribution lines shall be carried out by removing voltage difference with regulating tap or load of the surrounding transformers, with giving prior notice to the substation operators.

  • PDF

휴대용 UHF대역 RFID 시스템을 위한 선형 테이퍼드 슬롯 정류 안테나 (Linear Tapered Slot Rectifying Antenna for Portable UHF-Band RFID System)

  • 표성민
    • 전기전자학회논문지
    • /
    • 제24권1호
    • /
    • pp.368-371
    • /
    • 2020
  • 본 논문에서는 휴대용 UHF대역 RFID 시스템을 위한 선형 테이퍼드 슬롯 정류 안테나를 제안하였다. 제안한 정류 안테나는 별도의 유전체 기판을 사용하지 않기 때문에, 얇은 금속 두께로 평판형 안테나를 구현하였다. 정류 안테나는 입력 RF전력을 출력 DC전압으로 전환하는 정류회로는 2개의 쇼트기 다이오드를 이용한 배전압회로를 이용하였으며, 선형 테이퍼드 슬롯 안테나에 집적하여 정류 안테나를 설계하였다. 배전압 정류회로와 선형 테이퍼드 슬롯 안테나의 임피던스 공액정합을 위하여, 테이퍼드 슬롯의 각도와 안테나 급전선의 길이의 조절을 통해 source-pull 방법을 이용하였다. 제안한 안테나 시제품은 자유공간 무선환경실험 환경에서 RF-DC전환 실험과 원거리장 안테나 방사패턴 측정실험을 통해 회로 및 방사 특성을 검증하였다. 최종 제안한 안테나는 중심주파수 915 MHz 기준으로 0.23-파장(75 mm)와 0.18-파장(60 mm) 크기로 소형화하였다.

22.9 kV-Y 계통에서 지락고장이 인체 및 저압설비의 안전에 미치는 영향 (Effects of Ground Faults on the Safety of Persons and Low-voltage Installations in 22.9 kV-Y Distribution Systems)

  • 김한수;정재희;강계명
    • 조명전기설비학회논문지
    • /
    • 제22권1호
    • /
    • pp.141-148
    • /
    • 2008
  • 본 논문에는 22.9 kV-Y 배전계통의 1선 지락고장이 인체의 안전 및 저압설비의 보호에 대한 실험적 결과를 기술하였다. 새로이 제정된 KS C IEC 60364 규격군에 따른 고압 충전도체가 대지에 접촉되는 지락고장에 의한 위험전압과 저압기기의 스트레스전압을 평가하기 위해서 22.9[kV] 중성점 다중접지계통에 대한 실증실험을 수행하였다. 실험결과로부터 KS C IEC 60364 규격군을 기존의 국내배전계통에 적용할 때 부합되지 않는 중대한 문제점을 도출하였으며, 22.9 kV-Y 다중접지와 수용가설비접지를 공용하는 공통접지계통에서 발생하는 지락고장에 의한 일시적 과전압에 대한 효과적인 보호대책을 제시하였다. 결국 22.9 kV-Y계통과 저압설비를 공통접지로 하는 경우 인체와 저압설비의 안전을 위한 효과적인 보호대책의 구현에는 등전위본딩이 중요한 필수적 요건임이 밝혀졌다.

국내 저압 전기기기의 고조파 유출 제한값 산정 (Calculation of the Harmonic Emission Limit for low-Voltage Electrical Equipment)

  • 강문호;송양회;이흥호
    • 조명전기설비학회논문지
    • /
    • 제22권10호
    • /
    • pp.56-61
    • /
    • 2008
  • 배전계통의 고조파 방해(Harmonics Disturbance)현상은 배전계통에서 전압강하와 함께 순시 전력품질을 저해하여 중성선 및 NGR(Neutral Ground Reactor) 과열, OCGR 오동작 등의 문제를 발생시킴으로써 전력회사와 고객 모두에게 막대한 경제적인 손실을 주고 있어 동 분야에 대한 적극적인 대책이 필요하다. 이에 대한 해결 방안으로 유럽에서는 IEC 61000-3-2 규격을 통해 상당 16[A] 이하 저압 전기기기의 고조파를 제한하고 있다. 본 규격은 저압 전기기기를 4개의 등급으로 구분하여 관리하고 있으며, 분석결과 클래스 A등급 해당 전기기기의 고조파 유출제한 기준은 저압계통의 기준임피던스와 허용 최대전압을 바탕으로 산정되었으며, 타 등급(B, C, D등급)의 유출제한 기준들도 클래스 A의 유출제한 기준을 바탕으로 산정되었다. 따라서 본 논문에서는 IEC 61000-3-2 규격 분석결과를 바탕으로 국내 기준임피던스에 기초하여 국내 저압 전기기기의 고조파 유출 제한 값을 산정하였다.

저압수용가에 공급하는 TT, TN계통의 뇌서지에 대한 보호성능의 평가 (Evaluation of the Protection Performance of TT and TN Systems for Low-Voltage Consumers Against Lightning Surges)

  • 이규선;최종혁;이복희
    • 조명전기설비학회논문지
    • /
    • 제24권6호
    • /
    • pp.67-74
    • /
    • 2010
  • 국내의 저압수용가 대부분은 한국전력공사의 TN-C접지방식으로부터 공급받고 있으나 부하설비는 TT 접지방식을 위주로 한 전기설비기술기준에 따라 시설되어 있다. 본 연구에서는 정보기술설비를 뇌서지로부터 보호할 수 있는 적절한 전원계통접지방식을 제안하기 위해서 TT, TN계통의 뇌서지에 대한 보호성능을 연구하였다. 그 결과, 뇌서지가 배전계통의 중성선에 입사한 때 TT계통의 기기접지단자와 전원선의 중성점 사이에 높은 전위차가 발생하였으며, 예민한 컴퓨터설비가 손상될 위험성이 있으므로 TT계통은 적합하지 않다. 뇌서지로부터 저압 설비를 보호하기 위해서는 등전위본딩이 중요한 요건이며, TN계통이 중성선을 통하여 입사하는 뇌서지의 저감에 가장 우수하였으며, 수용가 인입구에서의 추가접지도 바람직한 방법이다.