Abstract
Most of domestic low-voltage consumers are supplied from the TN-C system of KEPCO, but their load installations have established according to the national statutory standard for electrical installations based on the TT system. In this work, to propose the proper system earthing arrangements of ensuring the protection of information-technology equipment against lightning surges, the protection performance of TT and TN systems against lightning surges was investigated. As a result, when lightning surge was injected to the neutral line of distribution system, the potential difference between the equipment earth terminal and neutral point of low-voltage mains in a TT system was significantly raised. The TT system is not advised due to the risk of damage to the sensitive computer equipment. Main equipotential bonding is an important requirement for protection of low-voltage installations against lightning surges. The TN system provides the best means to reduce the incoming lightning surges through the neutral line of low-voltage service systems. In addition, It is highly recommended to install the additional earthing at the service position of low-voltage consumers.
국내의 저압수용가 대부분은 한국전력공사의 TN-C접지방식으로부터 공급받고 있으나 부하설비는 TT 접지방식을 위주로 한 전기설비기술기준에 따라 시설되어 있다. 본 연구에서는 정보기술설비를 뇌서지로부터 보호할 수 있는 적절한 전원계통접지방식을 제안하기 위해서 TT, TN계통의 뇌서지에 대한 보호성능을 연구하였다. 그 결과, 뇌서지가 배전계통의 중성선에 입사한 때 TT계통의 기기접지단자와 전원선의 중성점 사이에 높은 전위차가 발생하였으며, 예민한 컴퓨터설비가 손상될 위험성이 있으므로 TT계통은 적합하지 않다. 뇌서지로부터 저압 설비를 보호하기 위해서는 등전위본딩이 중요한 요건이며, TN계통이 중성선을 통하여 입사하는 뇌서지의 저감에 가장 우수하였으며, 수용가 인입구에서의 추가접지도 바람직한 방법이다.