• Title/Summary/Keyword: 바닥복사난방 시스템

Search Result 28, Processing Time 0.025 seconds

A Experimental Study on the Application of GRNN for On-Off Control in Floor Radiant Heating System (바닥복사 난방시스템의 개폐식 제어에 대한 GRNN 적용에 관한 실험적 연구)

  • Song, Jae-Yeob;Ahn, Byung-Cheon
    • Journal of the Korean Society for Geothermal and Hydrothermal Energy
    • /
    • v.16 no.4
    • /
    • pp.16-23
    • /
    • 2020
  • In this study, the control characteristics and effects of control methods on heating performance and energy consumption for the hot water floor radiant heating control system of a residential apartment were research by experiment. As a control method, On-Off control and outdoor reset control methods with GRNN(General Regression Neural Network) and without GRNN are considered. Also, the control performances with regard to improvement of indoor thermal environment and reduction of energy consumption are compared, respectively. Experiment results show that the performance of the control method with GRNN is better than that of conventional on-off control method without GRNN in the responses of room set temperature and energy saving.

The Effective Heating Control Method of the Radiant Floor Heating System (바닥복사 난방공간의 효율적인 난방제어방법)

  • Cho, S.H.;Tae, C.S.
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.8 no.3
    • /
    • pp.317-329
    • /
    • 1996
  • By describing the floor slab of a radiant heating system as a one dimensional transient heat exchanger problem, a dynamic analysis model to incorperate with TRNSYS program was developed and their results were compared with experimental results. Results showed that the both of TPOC(Two Parameter On-off Control) and TPSC(Two Parameter Switching Control) method using room air temperature and floor surface temperature as the control parameters does not maintain room air and floor surface temperature exactly at the setting temperatures. But TPSC method is a better candidate for the temperature regulations of room air and floor surface temperature than TPOC method which can keep on the upper and lower limit temperature according to outside temeperature and wall structure etc. And better thermal circumstance can be given by TPSC method than On-off and TPOC method and the overheating which can be occured at the radiant floor heating system with on-off heating control will be reduced.

  • PDF

A Study on the Improvement of Indoor Thermal Performance of Floor Radiant Heating System Considering Valve Operation Characteristics (바닥복사 난방시스템의 밸브구동 특성을 고려한 실내 열환경 성능 개선 연구)

  • Song, Jae-Yeob;Ahn, Byung-Cheon
    • Journal of the Korean Society for Geothermal and Hydrothermal Energy
    • /
    • v.17 no.4
    • /
    • pp.36-45
    • /
    • 2021
  • In this study, to improve the indoor thermal environment of the radiant floor heating system, a study was conducted on the temperature change characteristics and energy consumption according to the change of the indoor air set temperature, the supply hot water temperature and the outdoor temperature. As for the control method, the on/off control and the thermal difference proportional control method proposed through previous studies were applied. In addition, in consideration of field applicability, numerical analysis was performed for the case where the indoor air temperature sensor was affected by the wall temperature. As a result, it was found that the temperature difference proportional control method is more effective for thermal comfort and energy saving than on/off control.

A Study on the Individual Room Control of Radiant Floor Heating System in Apartment Buildings (공동주택에서 바닥복사 난방시스템의 실별 제어에 관한 연구)

  • 김오봉;이미경;김광우;여명석
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.16 no.5
    • /
    • pp.421-429
    • /
    • 2004
  • In Korea, the radiant heating system has been widely used as a residential heating method, which has been modernized to use hot water running into the tubes embedded in the floor structure. According to the recent improvement of living standard of residential buildings, the requirement of the thermal comfort and energy saving in heating system has been raised. Until now, the radiant floor heating system has been controlled by room thermostat installed in the living room, but for better thermal comfort, an individual room control method is adopted as an alternative. Therefore, it is necessary to evaluate the control performance between the current control method and the individual room control method. In this study, the control performance between the two systems is evaluated through the field experiment. And the control performances of room air temperature and energy performances are analyzed through the simulation using TRNSYS. Firstly, the simulations are performed in the various outdoor conditions and the flow rates and the simulation results are analyzed for the control performances. Also, to evaluate the energy performance, the simulations are performed under the operating conditions in which the set-point of the room air temperature is fixed or changed according to the schedule of occupancy, and the simulation results are analyzed between the two methods.

Energy Saving Potentials of Radiant Floor Heating Systems Based on Control Strategies (바닥 복사 난방 시스템의 제어전략에 따른 에너지 사용량 분석)

  • Lee, Joon-Woo;Park, Cheol-Soo
    • 한국태양에너지학회:학술대회논문집
    • /
    • 2009.04a
    • /
    • pp.109-114
    • /
    • 2009
  • The dominant heating system used in Korean residential apartment buildings is a hydronic radiant floor heating system, known as the Ondol system. The most common control strategy applied to this traditional hydronic radiant system is a simple on-off control that intermittently supplies "hot water of a fixed temperature" at a "constant flow rate" to each room. However, the current problems with the aforementioned control are as follows: (1) since the simple on-off control is usually based on a one point measured temperature (a signal from a thermostat installed in a living room) in each dwelling unit, heating energy use for unoccupied rooms as well as a difference in temperatures between spaces (master bedroom, living room, bedroom1, bedroom2) can occur occasionally. (2) the most widely used residential water splitter has static valves, and is thus not able to change the flow rate to each room depending on the space heating load. In other words, the ratio of flow rates to rooms is fixed after construction, resulting in over- or under-heating and an improper use of energy. The aim of this paper is therefore to investigate the differences in the system's performance between control strategies in terms of the flow rate control and sensor location. It is shown that energy savings of control strategies are strongly influenced by occupant schedule.

  • PDF

A Study on the Operational Strategies for Outdoor Air Temperature Change Characteristics in a Radiant Floor Heating System (바닥난방시스템의 외기온도 변화특성을 고려한 운전방안에 관한 연구)

  • Ahn, Byung-Cheon;Song, Jae-Yeob
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.25 no.12
    • /
    • pp.685-692
    • /
    • 2013
  • In this study, the control characteristics and effects of heating control methods on the heating performance and energy consumption of a hot-water heating control system of a residential apartment were researched by simulation and experiment. The purpose of this study is to evaluate operational strategies for improving an indoor thermal environment and reducing f energy consumption in the radiant floor heating system of a residential apartment.

A Study on the Performance Analysis of Proportional Automatic Thermostatic Valves in Floor Radiant Heating System (바닥난방 시스템용 비례식 자동온도조절밸브의 성능해석에 관한 연구)

  • Song, Jae-Yeob;Ahn, Byung-Cheon;Kim, Yong-Ki;Lee, Tae-Won
    • Proceedings of the SAREK Conference
    • /
    • 2007.11a
    • /
    • pp.52-57
    • /
    • 2007
  • The control characteristics for radiant panel heating system with automatic thermostatic valves were researched by computer simulation and experiment. The unsteady energy analysis using equivalent R-C circuit method and radiation heat transfer analysis of enclosure analysis method with simple structured rooms was performed. The results of flow rate changes of the simulation study are good fit with the ones of experimental one.

  • PDF

Application Study of the Predictive Pulse Control for Floor Heating System (바닥난방을 위한 부하 예측식 펄스제어 방식의 적용성 연구)

  • Cho, Sung-Hwan;Kim, Seong-Su;Kim, Yong-Bong;Na, Hee-Hyeong
    • Proceedings of the SAREK Conference
    • /
    • 2007.11a
    • /
    • pp.167-175
    • /
    • 2007
  • A predictive pulse control strategy as a means of improving the energy efficiency of radiant floor heating systems is explored. Experiments at the apartment with floor heating system are conducted to assess and compare the energy performance of the predictive pulse control strategy with an existing conventional control strategy. The Results showed that new suggested PPCM( Predictive Pulse Control Method) was available to decrease the gap of $1{\sim}1.5^{\circ}C$ between maximum and minimum indoor temperature of each rooms. Therefore PPCM method was favor to radiant floor heating system which have a delay time of 10-20 minutes for heat transfer by floor layers.

  • PDF