• Title/Summary/Keyword: 물분무소화설비

Search Result 17, Processing Time 0.026 seconds

미세물분무 소화설비의 현장적용을 위한 실험적 평가

  • 김성원;이경덕;원정일;신창섭
    • Proceedings of the Korean Institute of Industrial Safety Conference
    • /
    • 2002.05a
    • /
    • pp.227-230
    • /
    • 2002
  • 환경문제를 야기하는 할론 소화설비의 사용이 금지되면서 대체소화설비로 관심을 끌며 연구되기 시작한 미세물분무 소화설비이다. 미세물분무는 고압에서 물을 방사하여 $Dv_{0.99}$가 1,000$\mu$m 미만의 물입자를 만들며 작은 물입자로 인해 표면적의 증가와 증발특성이 우수하고, 산소농도를 감소시키는 질식작용과 화염의 냉각작용에 의해 소화작용을 상승시킨다. 이러한 미세물분무의 소화작용에 대한 소규모 화재실험을 기반으로 유류화재의 진압$\cdot$소화특성에 대한 실용화를 위해 실제크기 화재실험을 하였다.(중략)

  • PDF

A study on use of quantitative risk analysis on life safety performance for the effect of fixed fire fighting system at road tunnel fires (정량적 위험성 평가를 활용한 도로터널 화재시 물분무 소화설비의 피난 안전 효과 연구)

  • Park, Kyung-Hwan;Yoo, Ji-Oh
    • Journal of Korean Tunnelling and Underground Space Association
    • /
    • v.14 no.1
    • /
    • pp.1-22
    • /
    • 2012
  • This paper tried to verify whether the fixed fire fighting system (FFFS) that is installed in road tunnel improves evacuation performance or not. Verification was performed according to the Disaster Prevention Facilities Installation and Management Guide at Road Tunnel. Twenty seven different fire scenarios were set up for the verification and the cases that FFFS was installed were compared with the cases that FFFS was not installed. The result of the comparison showed that the average equivalent death was reduced in 26 cases out of 27 cases when water spray extinguishing system was installed. It was confirmed that the risk when was not installed was unacceptable in Hong Kong and the Netherlands. On the other hand, it was confirmed that the risk was reduced to as low as reasonably practicable (ALARP) when was installed. The cumulative frequency of average death in case with FFFS was compared against the frequency of death without FFFS: death of one or more is about 50 times less; 10 or more is about 100 times less; and the death of more than 100 is four times less. It was verified that FFFS makes improved conditions to escape from the fires in road tunnel.

첨가제로 NaCl과 포소화약제가 포함된 미세물분무의 소화성능

  • 이경덕;김성원;신창섭
    • Proceedings of the Korean Institute of Industrial Safety Conference
    • /
    • 2002.05a
    • /
    • pp.217-220
    • /
    • 2002
  • 할론 등 CFC 계통의 소화약제는 환경오염물질을 내포하며, 지구온난화지수와 오존파괴지수 등이 높아 전세계적으로 그 사용이 중단되고 있다 또한, IMO의 SOLAS Chapter II-2에서는 소화설비에 대한 규정으로 할론소화장치의 새로운 설치를 금지하고 있으며, 2002년 7월 1일 이전에 건조된 2,000톤 이상의 현존 여객선은 기관실 전체를 방호하는 고정식 수계국소방출소화설비를 설치하여야 한다고 규정하고 있다. 이에 대체소화기술의 하나로 관심을 끌며 연구되기 시작한 소화방법이 미세물분무노즐을 이용한 소화설비이다.(중략)

  • PDF

미세물분무의 분사특성에 따른 n-Heptane 화염의 소화

  • 이경덕;김영수;신창섭
    • Proceedings of the Korean Institute of Industrial Safety Conference
    • /
    • 2000.11a
    • /
    • pp.118-123
    • /
    • 2000
  • 화재에 대한 소화방법으로서는 점화원의 냉각, 산화제 농도의 감소에 의한 화염의 질식 및 제거소화와 부촉매를 이용한 소화법이 있다. 이중 냉각소화방법은 주로 물을 사용하여 화재를 진압하고 있으나, 유류화재와 전기화재 등에서는 물보다 할론소화약제가 효과적으로 사용되어 왔다. 그러나 할론 등 CFC 계통의 소화약제는 환경오염물질을 내포하며, 지구온난화지수와 오존파괴지수 등이 높아 전세계적으로 그 사용이 중단되고 있다. 이에 대한 대체 기술의 하나로 최근에 관심이 고조되기 시작한 소화기술은 분무 노즐을 이용한 미세물분무(water mist) 소화설비이다.(중략)

  • PDF

화재진압용 미세 물분무 상용 노즐의 분무 특성에 관한 실험적 연구

  • 박현태;김성찬;이성룡;유홍선;방기영
    • Proceedings of the Korean Institute of Industrial Safety Conference
    • /
    • 2002.05a
    • /
    • pp.397-402
    • /
    • 2002
  • 노즐을 통하여 미세한 물 입자를 뿜어내어 화재를 진압하는 방식은 1930년대부터 응용되어왔지만 하론이 소화 물질로서 개발되어 널리 사용됨에 따라 물분무에 대한 개발이 중단되었다. 그러나 몬트리올 환경회의에 의해 하론이 오존층 파괴 물질로 사용이 제한됨에 따라 대체 소화물질로서 1990년대에 미세 물분무에 대한 연구가 활발히 진행되기 시작하였으며 최근 IMO(세계 해사기구)에서는 2003년부터 건조되는 선박의 소화설비로서 물분무 노즐 사용을 의무화하기 시작했다.(중략)

  • PDF

Extinguishing Charactristics of Water Mist by Discharge Properties (방사특성 변화에 따른 미세물분무의 소화특성)

  • 이경덕;신창섭
    • Fire Science and Engineering
    • /
    • v.15 no.4
    • /
    • pp.41-48
    • /
    • 2001
  • Halogen-based fire suppressing agents have been the most effective fire suppressants and widely used for flammable liquid and electric fire. However they have environmental problems causing stratospheric ozone depletion and globe warming. As a substitution of halon, fire suppression system using fine water mist is one of an effective fire suppressant. Suffocating and cooling effects of water mist are increased by the evaporation characteristics because it has droplet size less than 1,000 $\mu{m}$ and very large surface area. In this study, the extinguishing characteristics of fire was measured with changing of water mist droplet size, flow density; discharge pressure, and fire size. As a result, the extinguishing time of pool fire was shortened with the increase of flow density and in case of low flow density less than 0.5$\pm$0.05 ml/$\textrm{cm}^2$ . min, the extinguishing time was shortened with the increase of droplet size. The cycling discharge was effective for $\eta$-heptane pool fire, and total amount of water mist required to extinguish fire was reduced to a quarter compare with continuous discharge.

  • PDF

Experimental study on the spray density distribution of water spray system in road tunnel (터널 물분무소화설비의 살수밀도분포에 대한 실험연구)

  • So, Soo-Hyun;Park, Kyung-Hwan
    • Journal of Korean Tunnelling and Underground Space Association
    • /
    • v.13 no.1
    • /
    • pp.1-8
    • /
    • 2011
  • Spray density of the water spray system which is installed in long road tunnels and hazardous vehicle tunnels is applied without proper performance assessment process. In this study, the requirements of Spray Density Guidelines at the standard pressure is investigated through spray test set up the nozzle of a water spray system in a simulated road tunnel. The results showed that all the nozzles used in the test area did not meet the requirements of the Guidelines. The absence of performance test codes and inspection process on the nozzle at real scale in tunnels may have caused this practice. Therefore, it is suggested that the performance test regulations of the nozzle on the water spray system is established in order to properly assess the system performance.

미세 물분무 노즐의 분사특성 실험 결과 분석

  • Kim, Chang-Seop;Yu, U-Jun;Gwon, Seong-Pil;Yeom, Mun-Cheon;Kim, Chang;Han, Yong-Taek
    • Proceedings of the Korea Institute of Fire Science and Engineering Conference
    • /
    • 2013.11a
    • /
    • pp.229-229
    • /
    • 2013
  • 본 연구에서는 미세 물분무 노즐의 소화성능을 분석하기 위해 유량계수, 방사거리, 방사각도, 그리고 작동압력에 따라 분사되는 물입자 크기를 측정하였다. 이를 위해서 이중 구조의 미세 물분무 노즐 LPN-61과 LPN-63을 제작하였으며, 미분무 소화설비를 구성하여 이중구조 노즐의 형상에 따라서 유동특성을 정량화하였다. 그 결과 LPN-61은 유량계수 5.116, 방사각 $120^{\circ}{\sim}125^{\circ}$로 작동압력이 $4kgf/cm^2$에서 $10kgf/cm^2$까지 증가함에 따라서 SMD는 $127{\mu}m$정도에서 $88{\mu}m$까지 입자 크기가 감소하였으며, LPN-63은 유량계수 5.121, 방사각도 $120^{\circ}{\sim}125^{\circ}$로 동일한 작동압력 범위에서 SMD는 $108{\mu}m$에서 $80{\mu}m$까지 감소하는 것을 확인하였다.

  • PDF

A Study on the Performance of Water Mist Spray Fire Protection System (미세물분무 소화성능에 관한 연구)

  • 김봉환;김용판;문철진;홍철현;이형욱;최현호
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.15 no.7
    • /
    • pp.572-578
    • /
    • 2003
  • The present study was numerically and experimentally performed to investigate the fire suppression performance of water mist spray subjected to thermal radiation in closed space. Downward-directed water mist sprays to interact with an under kerosine pool fire were investigated in test facility The mass mean diameters of water mist droplet were measured by PMAS under various flow conditions. The developed water mist spray nozzle was satisfied to the criteria of NFPA 750, Class 1. The mechanism of the fire suppression by water mist was attributed to the cooling of the fire surface which lead to suppressed of fuel evaporation. It was proved that the water mist spray system under lower pressures could be applied to underground fire protection system.