• Title/Summary/Keyword: 단독 운전 검출

Search Result 81, Processing Time 0.023 seconds

Reactive Power Variation Method for Anti-islanding Using Digital Phase-Locked-Loop (DPLL을 이용한 능동적 단독운전방지를 위한 무효전력변동법)

  • Lee, Ki-Ok;Yu, Byung-Gu;Yu, Gwon-Jong;Choi, Ju-Yeop;Choy, Ick
    • Journal of the Korean Solar Energy Society
    • /
    • v.28 no.2
    • /
    • pp.64-69
    • /
    • 2008
  • As the grid-connected photovoltaic power conditioning systems (PVPCS) are installed in many residential areas, these have raised potential problems of network protection on electrical power system. One of the numerous problems is an Islanding phenomenon. There has been an argument that it may be a non-issue in practice because the probability of islanding is extremely low. However, there are three counter-arguments: First, the low probability of islanding is based on the assumption of 100% power matching between the PVPCS and the islanded local loads. In fact, an islanding can be easily formed even without 100% power matching (the power mismatch could be up to 30% if only traditional protections are used, e.g. under/over voltage/frequency). The 30% power-mismatch condition will drastically increase the islanding probability. Second, even with a larger power mismatch, the time for voltage or frequency to deviate sufficiently to cause a trip, plus the time required to execute a trip (particularly if conventional switchgear is required to operate), can easily be greater than the typical re-close time on the distribution circuit. Third, the low-probability argument is based on the study of PVPCS. Especially, if the output power of PVPCS equals to power consumption of local loads, it is very difficult for the PVPCS to sustain the voltage and frequency in an islanding. Unintentional islanding of PVPCS may result in power-quality issues, interference to grid-protection devices, equipment damage, and even personnel safety hazards. Therefore the verification of anti-islanding performance is strongly needed. In this paper, improved RPV method is proposed through considering power quality and anti-islanding capacity of grid-connected single-phase PVPCS in IEEE Std 1547 ("Standard for Interconnecting Distributed Resources to Electric Power Systems"). And the simulation results are verified.

Islanding Detection for Grid-connected PV Inverter under Parallel Operation (계통연계형 태양광 인버터 병렬운전 상황에서의 단독운전 검출)

  • Jo, Yeong-Min;Kim, Dong-Gyun;Song, Seung-Ho;Choy, Ick;Lee, Young-Kwoun;Cho, Sang-Yoon;Choi, Ju-Yeop
    • The Transactions of the Korean Institute of Power Electronics
    • /
    • v.21 no.4
    • /
    • pp.283-289
    • /
    • 2016
  • Islanding protection of a grid-connected photovoltaic (PV) inverter is a key function for standards compliance. Unintentional islanding results in safety hazards, reliability, and many other issues. Therefore, many anti-islanding schemes have been examined. However, existing anti-islanding schemes have poor power quality and non-detection zone issues. Moreover, most schemes have problems that deteriorate the performance of islanding detection under parallel operation. Therefore, this paper proposes a novel anti-islanding scheme that has negligible power quality degradation and has no non-detection zone and islanding detection under a parallel operation. Both simulation and experimental results validate the proposed scheme.

Technical Analysis for Small Hydro-power Generator Integrated with Electric Distribution Systems (소수력발전의 배전계통 연계를 위한 기술적 분석)

  • Jung, Won-Wook;Kim, Sang-Jun;Yoon, Ki-Gab;Seo, Jung-Chul
    • Proceedings of the KIEE Conference
    • /
    • 2006.07a
    • /
    • pp.529-530
    • /
    • 2006
  • 분산형 전원이 전력계통에 연계됨에 따라 역조류, 보호협조, 계통 동기화, 전기품질 문제 등 여러 가지 문제를 야기한다. 이에 따라 전력회사에서는 분산형 전원의 계통연계 기술 기준을 제시하고 해당 분산형 전원의 계통 연계에 대한 기술 검토를 수행한다. 본 논문에서는 동기발전기형 2500KVA 소수력발전기 2대의 배전계통 연계에 대한 기술적 검토를 수행하였으며 해당 분산형 전인이 동기발전기임을 고려하여 계통연계시 상시전압변동 및 보호방식에 대해 집중 분석하였다. 먼저 소수력발전기가 연계되는 지점에서의 기존 선로 및 전력설비의 여건과 소수력발전기의 출력용량 및 역률을 고려하여 연계 지점에서의 전압변동을 검토하여 적절한 연계방식을 제시한다. 그리고 시간대별 소수력발전기의 발전량과 해당 배전선로의 부하량을 고려하여 기 설치된 보호계전기에 의한 단독운전 검출 능력을 검토하고자 한다.

  • PDF

A Novel Active Anti-islanding Method using Effective Power Variation (유효전력변동방식을 이용한 새로운 단독운전 검출기법 연구)

  • Yu Byung-Gyu;Jung Young-Seok;Matsui Mikihiko;Yu Gwon-Jong
    • Proceedings of the KIPE Conference
    • /
    • 2006.06a
    • /
    • pp.213-215
    • /
    • 2006
  • Islanding phenomenon is undesirable because it lead to a safety hazard to utility service personnel and may cause damage to power generation and power supply facilities as a result of unsynchronized reclosure. In order to prevent the phenomenon, various anti-islanding methods have been studied. This paper proposes the variation method of inverter output current magnitude to prevent the islanding phenomenon as a novel method, which causes the large frequency variation of inverter output voltage after islanding. Unlike most active anti-islanding method deteriorating power quality, this novel method will have high performance of islanding detection and good power quality. For the verification of the proposed method, the simulated result and analyses are presented.

  • PDF

A Study on the Islanding Detection for Grid Connected Photovoltaic System (계통연계형 태양광발전시스템을 위한 단독운전 검출에 관한 연구)

  • Lee Gi-Je;Kim Min;Lee Jin-Seop;Yu Gwon-Jong
    • Proceedings of the KIPE Conference
    • /
    • 2002.07a
    • /
    • pp.555-558
    • /
    • 2002
  • The general ways of the anti-islanding can be classified into the active method and passive method. The passive method which use only the voltage information when power failure occurs has much possibility of the wrong detection. And the active method detects the change of the voltage frequency as instantaneously changing the frequency of the inverter output current. Therefore, in this paper, the method to inject arbitrary order harmonics into controlled current is proposed. In this method islanding can be detected by measuring the amount of load voltage of injected harmonics order. And as a current control method predictive control method is used, which make actual current accurately to track reference current by Instantaneously computing converter output voltage and has fast response in transient state. This parer proposed method was verified by simulation.

  • PDF

Novel Anti-islanding method using phase shift with a periodic function (주기적 위상 변동 기법을 이용한 새로운 단독운전 검출 기법)

  • Jung, Young-Seok;Choi, Jae-Ho;So, Jung-Hoon;Yu, Byung-Guy;Yu, Gwon-Jong
    • Proceedings of the KIEE Conference
    • /
    • 2006.07b
    • /
    • pp.1153-1154
    • /
    • 2006
  • This paper proposes the optimal design method based on NDZ analysis to secure the islanding defection ability and to maintain the stability and power quality when the grid is connected. A PSiM-based model and analysis of the system is presented, specialty aimed at improving the effectiveness of phase shift anti-islanding method with frequency feedback, which causes the inverter current to be generated slightly lower or higher in frequency than the frequency of the terminal voltage. The proposed method can cause frequency jump with leading and lagging phase of output current in two line cycles. As a result, the proposed algorithm is more sensitive and reliable than the conventional phase shift method. Experimental results, on a 3 kW inverter connected to 220 V, 60 Hz utility, are discussed.

  • PDF

Novel Islanding Detection Method using Frequency Drift for Grid-connected PV System (계통연계형 PV 시스템의 주파수 변동에 의한 새로운 단독운전 검출기법)

  • Eun Seog-Jun;Choi Jong-Woo;Kim Heung-Geun
    • Proceedings of the KIPE Conference
    • /
    • 2004.11a
    • /
    • pp.133-137
    • /
    • 2004
  • PV system's islanding occurs when the uitilty grid is removed but local sources continue to operate and provide power to local loads. Islanding is one of the serious problems m an electric power system connected with dispersed power sources. Also, this can present safety hazards and the possibility of damage to other electric equipments. If the real and reactive power of RLC load and PV system are closely matched, islanding detection by passive methods becomes difficult. Novel islanding detection method using frequency drift is proposed for grid-connected PV system.

  • PDF

Modeling and Evaluation of Slip-Mode Frequency Shift Method for Anti-islanding Method (슬립모드 방식을 이용한 단독운전 검출기법의 모델링과 평가)

  • Yu, Byung-Gyu;Jung, Young-Seok;So, Jung-Hun;Yu, Gwon-Jong
    • Proceedings of the KIPE Conference
    • /
    • 2005.07a
    • /
    • pp.520-522
    • /
    • 2005
  • Islanding phenomenon is undesirable because it lead to a safety hazard to utility service personnel and may cause damage to power generation and power supply facilities as a result of unsynchronized reclosure. In order to prevent this phenomenon, various anti-islanding methods have been studied. Even though the slip mode frequency shift (SMS) method has been regarded as a highly effective anti-islanding method, the analytical design method of that was not cleared. This paper proposes a modeling of the SMS method using non-detection zone (NDZ) and evaluation of the method according to the test conditions of IEEE Std. 929-2000. The SMS method is derived analytically through the modeling and verified visually by simulation and experiment.

  • PDF

Islanding Detection Technique using Wavelet Energy in Grid-Connected PV System (웨이블렛 에너지를 이용한 태양광 발전시스템의 단독운전 검출 기법)

  • Park, Hae-Chan;Kim, Il-Song
    • The Transactions of the Korean Institute of Power Electronics
    • /
    • v.20 no.5
    • /
    • pp.471-478
    • /
    • 2015
  • The new islanding detection method using wavelet energy is proposed in this paper. The proposed method is based on the autocorrelation of the wavelet energies, which is obtained from the high-frequency components of the grid voltage. It has the enhanced detection capabilities in the UV/OV/UF/OF region, which the conventional passive methods cannot obtain. The mathematical theories on the wavelet are presented, and the performance effectiveness is proved by the experimental results.

Analysis and Modeling of Slip Mode Frequency Shift Method for Anti-islanding (슬립모드 주파수변이 방식의 단독운전 검출법의 분석과 모델링)

  • Yu, Byung-Gyu;Jung, Young-Seok;So, Jung-Hun;Yu, Gwon-Jong
    • Proceedings of the KIEE Conference
    • /
    • 2005.07b
    • /
    • pp.1699-1701
    • /
    • 2005
  • Islanding phenomenon is undesirable because it lead to a safety hazard to utility service personnel and may cause damage to power generation and rower supply facilities as a result of unsynchronized reclosure. In order to prevent this phenomenon, various anti-islanding methods have been studied. Even though the slip mode frequency shift(SMS) method has been regarded as a highly effective anti-islanding method, the analytical design method of that was not cleared. This paper proposes a modeling of the SMS method using non-detection tone(NDZ) and evaluation of the method according to the test conditions of IEEE Std. 929-2000. The SMS method is derived analytically through modeling and verified visually by simulation and experiment.

  • PDF