서지보호소자와 누전차단기 설치에 따른 기기의 뇌보호 효과 (The Protection Effect of Lightning Surge for electronic Equipments According to Installation of Surge Protective Device and Earth Leakage Breaker)

  • 이석우;고연성;여동구;서호준;이동희
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2005년도 추계학술대회 논문집 전기물성,응용부문
    • /
    • pp.90-92
    • /
    • 2005
  • Lightning surge damages of low voltage equipments in building are increasing due to increase in electrical and communication networks in the information-oriented society. And electronic equipments contained electrical circuits with semiconductor are very weak against lightning surge. The surge protective devices for electronic circuit in electronic equipments and AC power lines are becoming more widely. To achieve effective method of surge protection, there are needs for correlation between lightning surge protective effect of electronic equipment and installation method of surge protective device. This paper describes as a result of experiments for correlation between lightning surge protective effect and installation of surge protective device and Earth Leakage Breaker.

  • PDF

충격파 부동작형 누전차단기의 뇌써지 응답 특성 (Lightning Surge Response Characteristics of Non-tripping Type Earth Leakage Breakers for Impulse)

  • 이재복;명성호;조연규;장석훈;김정식;길경석
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2002년도 하계학술대회 논문집 C
    • /
    • pp.1688-1690
    • /
    • 2002
  • The unpredictable threat of lightning surge is ever increasing in today's low-voltage power supplies. Thus Surge protection devices for AC mains are more widely used. The false-tripping of the earth leakage breaker (ELB) can be caused by the installation of surge protection devices with MOV. In order to examine the cause of malfunction, the malfunction characteristics of ELBs applied by lightning surge were investigated experimentally. As a result, all of them brought about malfunctions under 7 kV of the impulse voltage. The suitable position of MOV and use of zener diode were suggested to eliminate the problems.

  • PDF

저압용 누전차단기의 차단특성 및 그라파이트 분석에 관한 연구 (A Study on the Cut Off Characteristics and Graphite Analysis of Residual Current Protective Devices for Low Voltage)

  • 최충석;이경섭;정재희;박수홍;김병수;이덕출
    • 한국안전학회지
    • /
    • 제14권1호
    • /
    • pp.49-54
    • /
    • 1999
  • In this paper. we studied cut off characteristics and fire hazard of residual current protective devices(RCD or ELB) for low voltage. The operative time of RCD with grounding resistance was analyzed by using RCD operating tester. The surface structure and composition of insulator were analyzed by using scanning electron microscope(SEM) and energy dispersive x-ray spectroscopy(EDX). The surface of phenol resin showed network structure and void. The spectra shown in EDX analysis are composed not only of the corresponding elements but also of several new spectra, as CK. OK$\alpha$. MgK, SiK. and CaK, which were absent in original material.

  • PDF

IEC60947-2에 따른 누전차단기의 순시단락시험 과도현상에 대한 연구 (The Transient Analysis of Instant Short-Circuit Test Equipment For Earth Leakage Circuit Breaker)

  • 류행수;김명석;한규환
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2003년도 하계학술대회 논문집 A
    • /
    • pp.357-359
    • /
    • 2003
  • This paper is for the transient analysis of instant short-circuit test equipment according to the test of tripping limits and characteristics under IEC 60947-2. The in-rush current is harmful to almost equipments and the exact testing is not made because of it. LGIS has a instant short-circuit test equipment, but it is not suitable for carrying out instant short-circuit test on ELB(Earth Leakage Circuit breaker) by reason of that. Now, I am going to show a solution for that problem. After applying this method, manufacturer is going to acquire the exact testing result according to the IEC standard. Moreover, Testing laboratory will be trusted by clients.

  • PDF

공장전기설비에서의 누전차단기 오동작과 전력품질 분석 (Power Quality Analysis and Failure of Earth Leakage Breakers in Plant)

  • 이상의;유재근;전정채;전현재;허혜성;최규하
    • 전력전자학회:학술대회논문집
    • /
    • 전력전자학회 2007년도 하계학술대회 논문집
    • /
    • pp.479-481
    • /
    • 2007
  • This paper presented a actual conditions on a false-tripping of ELB(Earth Leakage Breakers) and an assessment of the harmonics due to non-linear electronic equipment such as personal computers, rectifier, electric furnace and test equipments in plant installations. Actual conditions on a failure of ELB were surveyed and analyzed by making up a question to safety managers of plant installations. Also, power quality measurements such as harmonic currents, voltage and current waveform and current imbalance were made at various plant installations where nuisance tripping of ELB is often occurred. The results of this study can be used in making decisions regarding cause of ELB trip and operating and tripping characteristics test of ELB when subjected to distorted current waveform.

  • PDF

병렬아크에 대한 누전차단기의 트립특성 분석 (Analysis of Tripping Characteristics of Earth Leakage Circuit Breakers against Parallel Arcing)

  • 김일권;박대원;최수연;조영진;길경석
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2007년도 추계학술대회 논문집
    • /
    • pp.478-479
    • /
    • 2007
  • Many electrical fires are occurred by leakage currents and sparks generated by a short circuit. Earth leakage circuit breakers (ELCBs) should be tripped at the moment of the faults mentioned above. In this paper, we described the tripping characteristics of ELCBs against parallel arcing faults. A diesel engine generator with the capacity of 375 kVA source was adopted to provide enough large current when a parallel arcing occurred. The experimental results showed that most ELCBs we experimented were not tripped against short-duration pulse currents produced by parallel arcing because the ELCBs are designed to be tripped by a large current with long duration similar to power frequency.

  • PDF

누전차단기 하우징의 내후성에 관한 연구 (A Study on the Weathering of RCD'S Housing)

  • 김창환;신진용;강병철;김상명
    • 한국표면공학회지
    • /
    • 제47권6호
    • /
    • pp.335-340
    • /
    • 2014
  • This study selected an outdoor RCD'S and verified behavior of change in the housing with time. Weathering tests were carried out as outdoor exposure test (90 degrees, 37 degrees) and laboratory test (xenon lamp), and the results were evaluated based on color difference, gloss, contact angle, and optical microscope. This study can provide basic data for standardization of development and performance evaluation on RCD'S housing products.

반도체 스위칭 소자를 이용한 고속 고정밀의 전기화재 방재장치 (A Electrical Fire Disaster Prevention Device of High Speed and High Precision by using Semiconductor Switching Devices)

  • 곽동걸
    • 전력전자학회논문지
    • /
    • 제14권5호
    • /
    • pp.423-430
    • /
    • 2009
  • 최근 저압 배전계통에서 사용되고 있는 과부하겸용 누전차단기 즉, RCD의 저조한 응답특성으로 인한 전기화재 원인의 대부분을 차지하는 단락사고 및 과부하사고에 대한 대응이 매우 미흡한 실정이다. 이에 본 논문에서는 기존 RCD에 대한 모의 사고실험을 통하여 그 비신뢰성을 확인하고, 이러한 RCD의 단점을 개선하고자 내구성과 속응성이 우수한 반도체 스위칭 소자들과 고정밀 전류센서를 이용한 "전기화재 방재장치(EFDPD : Electrical Fire Disaster Prevention Device)"를 제안하여 저압 배전계통에서의 단락 및 과부하사고로 인한 전기재해를 방지하고자 한다. 제안한 장치의 고정밀 전류센서로 사용된 리드스위치는 각종 전기사고에서 수반되는 단락전류 및 과전류에 의한 배전선로의 상승된 자속을 정밀 감지한 후, 자체 차단장치를 동작시키는 원리를 가진다. 다양한 동작특성 분석을 통하여 기존의 차단기와 비교하여 차단동작 응답속도와 그 신뢰성이 입증된다. 이로써 제안한 전기안전 제어장치는 기존 RCD들의 빈번한 오동작과 비신뢰성, 저조한 응답특성으로 인한 각종 전기사고 및 전기화재의 발생을 방지하고자 한다.

아크 발생에 따른 고장 및 화재를 보호하기 위한 직류 아크 Generator 개발 (Development of DC Arc Generator to protect against Malfunctions and Fires caused by Arcing)

  • 윤용호
    • 한국인터넷방송통신학회논문지
    • /
    • 제21권6호
    • /
    • pp.123-128
    • /
    • 2021
  • 직류 배전시스템의 보급이 증가됨에 따라 이에 따른 고장 발생 및 화재 사고도 증가하고 있고 특히 스마트 그리드의 구성 요소인 ESS 화재 사고, 직류 시스템인 태양광 발전 시스템의 화재 사고는 신재생에너지의 보급이 급격하게 증가하고 동시에 사용 연수 10년 이상의 노후 시설이 많아짐에 따라, 시스템 구성 요소 간의 전기적인 접속의 문제들로 발생하고 있다. 이로 인해 유발된 빛과 열을 방출하여 직접적인 화재의 원인이 될 수 있는 아크가 화재의 한 원인으로 지적되고 있다. 따라서 이러한 아크 결함의 문제는 기존의 과전류차단기와 누전차단기로는 아크사고를 사전에 차단할 수 없는 실정이며 대규모 유틸리티 시스템뿐만 아니라 소규모 주거 시스템에서도 인간의 안전에 중대한 위협이 될 수 있기에 아크사고에 대한 대책이 필요하다. 본 논문에서는 국제표준화에 만족하는 시험장비 개발과 아크 발생에 따른 고장 및 화재를 보호하기 위한 직류 아크 Generator를 개발 하고자 한다.

전기안전에 대한 초.중.고등학교 전기시설물의 현장조사 연구 (Research on Investigation on the Spot in Relation to Electrical Safety of Electrical Installation in Elementary.Middle.High School)

  • 길형준;최충석;이기연;문현욱
    • 조명전기설비학회논문지
    • /
    • 제21권5호
    • /
    • pp.99-105
    • /
    • 2007
  • 본 논문에서는 초 중 고등학교 전기시설물을 대상으로 전기안전에 대한 현장조사를 하였다. 현장조사는 수전설비, 교실, 과학실 및 음악실 등을 대상으로 연구원, 경력 15년 이상의 전기기술자 및 기타 관련 전문가에 의해 전국적으로 수행하였다. 41개 학교를 대상으로 현장조사를 실시한 결과, 수전설비의 접지방식은 공통접지방식이 지배적이었다. 위험요소로는 선풍기 조절기함의 부재, 실험대 전원의 인체보호용 누전차단기의 미설치, 비접지 콘센트의 사용 등으로 나타났다.