• Title/Summary/Keyword: 급기/배기

Search Result 66, Processing Time 0.02 seconds

A Numerical Simulation of Smoke Control in Daegu Subway Stations I. Smoke Control System (대구 지하철역 제연의 문제점과 대책 I. 제연방식)

    • Fire Science and Engineering
    • /
    • v.17 no.4
    • /
    • pp.98-104
    • /
    • 2003
  • Smoke control in il space 10 m${\times}$3 m floor and 5.4 m high around the stairway of a subway station platform was simulated by using FDS to investigate problems of smoke control in Daegue subway stations. Distributions of temperature and smoke particles, and variation of the number of particles with time for a 200 ㎾ polyurethane fire were compared. It was shown that the purge system fails to remove smoke efficiently and that the extraction system has the highest perfor-mance among the three smoke control systems for the given situations. Simply switching the purge system into extraction mode might improve much the smoke removal performance.

A Numerical Study on Smoke Control for Smoke Control Systems and Air Flowrate (제연방식과 풍량에 따른 제연성능의 수치적 연구)

  • 박외철
    • Fire Science and Engineering
    • /
    • v.17 no.2
    • /
    • pp.56-61
    • /
    • 2003
  • The smoke removal rate from a room with an opening was investigated for different smoke control systems by using the large eddy simulation turbulence model of the Fire Dynamics Simulator. The decreasing rate of the particles randomly distributed in the 2m X 2m X 2.4m room was com-pared for the ventilation system, pressurization system and extraction system, and for the air flowrate of the ventilation system. Difference in the smoke removal rate among the three smoke control systems was small when the opening was closed. The pressurization system showed less smoke removal rate than the other two systems when the opening existed, and hence is not recommended for subway stations with large openings. It was also shown that a less flowrate in the ventilation system leads to a much longer smoke removal time.

A Study on the Effective Smoke Control Method of Large Volume Space Comparted by Smoke Reservoir Screen (제연경계벽으로 구획된 대형공간의 효과적인 제연방안에 관한 연구)

  • Kim, Tae-Hoon;Kwon, In-Kyu
    • Fire Science and Engineering
    • /
    • v.25 no.1
    • /
    • pp.34-41
    • /
    • 2011
  • This research examines problem that can happen in partial smoke control method among contiguity area smoke control system through engineering examination and CFD. And the ultimate purpose of this is to secure safety of a person inhabiting at fire department by presenting improvement plan. Now a days, in large space-area such as department store or mega-mall in which mainly applies "Partial Smoke Control Method", air is suppled from adjacent area and smoke is exhausted in fire room. For various reason, however, it is confirmed through simulation that if air is suppled in one direction, this can cause a fatal result to people of fire area because of the difficulty in securing the evacuation time. As an improvement plan, air is supplied at the same time in surroundings to fire department.

NUMERICAL STUDY OF AIR POLLUTION RATE DEPENDING ON TYPES OF VENTILATION SYSTEM IN UNDERGROUND PARKING LOT (환기방식에 따른 지하주차장 공기오염도의 수치연구)

  • Lim, Soo-Jung;Jang, Choon-Man;Rhee, Gwang-Hoon
    • 한국전산유체공학회:학술대회논문집
    • /
    • 2009.04a
    • /
    • pp.208-214
    • /
    • 2009
  • 지하 복수층 주차장은 도시의 밀집화 및 자동차의 급격한 증가로 인한 토지부족 및 주차난을 해소할 수 있는 좋은 방법이다. 하지만 인체유해 배출가스의 집중으로 환기의 중요성이 대두되는 추세에도 불구하고 실제로는 시공이 완료 된 후에나 오염도 측정이 가능하다. 이러한 이유로 CFD 시뮬레이션으로 시공이전의 지하 복수층 주차장의 공기오염도를 예측했다. CFD 시뮬레이션은 예산과 시간을 절감한 공기오염도 예측이 가능하다. 실제의 당산근린공원의 지하주차장을 대상으로 오염도를 예측했다. 급기에만 강제유동을 일으키는 2종과 배기에만 강제유동을 일으키는 3종 기계환기법, 그리고 급배기에 강제유동을 일으키는 1종기계환기법을 각각 적용하여 공기오염도를 계산했다. 지하1층과 지하2층의 입구 및 출구유속을 10, 15m/s로 하여 실내평균연령과 실내평균환기효율을 살펴보았다. 계산결과는 급기와 배기에 강제유동을 동시에 일으키는 1종 기계환기법의 값과 비교하였다.

  • PDF

Numerical Simulation of Aroma Concentration Distribution in a VR Theater for different Supply and Exhaust Conditions (VR 영상관에서의 급기 및 배기 방식에 따른 향 농도 분포 수치해석)

  • 김영일;김기정;허남건
    • Proceedings of the Korean Society for Emotion and Sensibility Conference
    • /
    • 2000.11a
    • /
    • pp.212-216
    • /
    • 2000
  • 어떤 특정한 환경과 상황을 가상적으로 모의함으로써 그 환경에 있는 사람이 마치 실제적인 환경 또는 상황과 상호 작용을 하고 있는 것처럼 만들어 주는 진보된 기술을 가상현실(virtual reality) 이라고 한다. 가상현실을 실현하기 위해서는 주변의 영상, 음향, 운동감, 열환경, 후각환경 등이 실제처럼 제시되어야 한다. 본 연구에서는 이중 후각환경의 제시를 위하여 급기 및 배기 위치에 따른 향 농도의 분포를 수치해석적으로 예측한다. 수치해석 결과는 VR 영상관의 향 배기 시스템의 설계 자료로 활용된다.

  • PDF

Evaluation of Ventilation Performances for Various Combinations of Inlets and Outlets in a Residential Unit through CO2 Tracer-Gas Concentration Decay Method (CO2 추적가스 농도감소법을 이용한 공동주택의 급·배기구 조합에 따른 환기 성능 분석)

  • Sang Yoon Lee;Soo Man Lee;Jong Yeob Kim;Gil Tae Kim;Byung Chang Kwag
    • Land and Housing Review
    • /
    • v.14 no.4
    • /
    • pp.111-120
    • /
    • 2023
  • Indoor air quality has become increasingly important with the increase in time spent in residential environments, impact of external fine dust, yellow dust, and the post-COVID 19 pandemic. Residential mechanical ventilation plays a key role in addressing indoor air quality. The legal standard for residential air changes per hour in Korea is 0.5 ACH. However, there are no standards for the location of supply and return vents. This study atempts to analyze the impact of ventilation performance based on the location of supply and return vents. An experiment was conducted using the CO2 tracer gas concentration decay method in a mock-up house set inside a large chamber to minimize external influences. The experimental results indicated that the commonly used combination of 2 supply and 2 return vents in living room spaces had a lower mean age of air than the combination of 1 supply and 2 return vents. Using multiple supply and return vents had lower mean age of air than using just 1 supply and 1 return vent.

Smoke Exhaust Performance Prediction According to Air Supply and Exhaust Conditions for Shipboard Fires from a Human Safety Point of View (인명안전 관점에서 선박 화재 시 급·배기조건에 따른 배연성능 예측평가)

  • Kim, Byeol;Hwang, Kwang-Il
    • Journal of the Korean Society of Marine Environment & Safety
    • /
    • v.22 no.7
    • /
    • pp.782-790
    • /
    • 2016
  • When a fire occurs on a ship that has mechanical ventilation facilities, the air supply and exhaust systems directly effect smoke diffusion. And there is a high possibility that occupant's visibility will be harmed because of smoke. In this study, the effects and risks of air supply and exhaust systems with regard to smoke diffusion given a shipboard fire analyzed with a Fire Dynamic Simulator(FDS). Suggested measures are also provided for using air supply and exhaust systems more efficiently. The results showed that, when air supply and exhaust systems were both working at the time of a fire, rather than stopping these systems as previously encouraged, continuing to operate both was an effective measure to gain evacuation time. When a fire occurred and the exhaust system was operating, also starting the air supply system near the origin of the fire was another effective approach to gain evacuation time. However, when only the air supply system was operating and a fire occurred, the air supply system accelerated smoke diffusion, so it was necessary to stop the air supply system to detect smoke diffusion as much as possible.

A study on the program development for area optimizing of damper ports in road tunnels with transverse ventilation system (횡류식 도로터널의 급, 배기구 포트 개구면적 최적화 프로그램 개발 연구)

  • Jo, Hyeong-Je;Chun, Kyu-Myung;Min, Dea-Kee;Kim, Jong-Won;Beak, Jong-Hoon
    • Journal of Korean Tunnelling and Underground Space Association
    • /
    • v.21 no.1
    • /
    • pp.177-188
    • /
    • 2019
  • The purpose of the optimization of the installation of supply/exhaust ports for tunnels with transverse ventilation system is to supply fresh air from outside to inside of tunnels uniformly and exhaust pollutant from tunnels properly for creating safe and clean environment for tunnel users. For this purpose, a ventilation port area optimization program was developed to obtain a uniform supply or exhaust air volume inside a great depth double deck tunnel with transverse ventilation system. In order to area optimize the developed port sizing program, the wind velocity was measured in the duct of the currently operated tunnel with semi-transverse ventilation. Also 3D cfd was performed on the same tunnel and cfd results were compared to the measured value. As a result, the error rate between the predicted value from the program and measured value was 6.72%, while the error rate between the predicted value from the program and 3D cfd analysis value was 4.86%. Both of comparison results show less than 10% of error rate. Thus It is expected that supply/exhaust port optimization design of transverse ventilation tunnel can be possible with using this large exhaust port area optimization program.

큰 개구부가 있는 지하공간의 화재와 제연에 관한 수치적 연구

  • Park, Oe-Chul;Ko, Kyung-Chan;Park, Jun
    • Proceedings of the Korean Institute of Industrial Safety Conference
    • /
    • 2003.05a
    • /
    • pp.121-128
    • /
    • 2003
  • 화재가 발생했을 때 많은 사람이 연기에 질식하여 사망하는 피해가 거의 해마다 일어나고 있다. 특히 올해 2월18일 190여명이 사망한 대구 지하철 중앙로역 화재참사에서는 다량의 유독성 가스를 효과적으로 배출하지 못해 더 많은 사망자가 발생하였다. 당시 지하철역에는 화재가 발생하면 환기용 배기장치가 급기장치로 전환되는 급기방식의 제연설비가 설치되어 있었고, 시계 불량으로 피난 표지판과 유도등이 잘 보이지 않은 것으로 밝혀졌다.(중략)

  • PDF