• 제목/요약/키워드: 계통연계형 태양광 시스템

검색결과 284건 처리시간 0.026초

소규모 계통연계형 태양광 시스템의 최적제어에 대한 연구 (Research about most suitable control of small scale system link type photovoltaic system)

  • 황락훈;장은성;남우영
    • 전력전자학회:학술대회논문집
    • /
    • 전력전자학회 2003년도 추계학술대회 논문집
    • /
    • pp.238-243
    • /
    • 2003
  • The solar cells should be operated at the maximum power point because its output characteristics are greatly fluctuated on the variation of insolation, temperature and load. The output power of solar cell is DC, therefore it is necessary to install an inverter among electric power converts. The inverter have to supply a sinusoidal current and voltage to the load and the interactive utility line. In the paper, the proposes a photovoltaic system designed with a step up chopper and single phase PWM voltage source inverter. Synchronous signal and control signal was processed by microprocessor for stable modulation. The step up chopper operates in continuous mode by adjusting the duty ratio so that the photovoltaic system tracks the maximum power point of solar cell without any influence on the variation of insolation and temperature because solar cell has typical dropping character. The single phase PWM voltage source inverter consists of complex type of electric power converter to compensate for the defect, that is, solar cell cannot be developed continuously by connecting with the source of electric power, from 10 to $20\%$. The single phase PWM voltage source inverter operates in situation that its output voltage is in same phase with the utility voltage. The inverter supplies an ac power with high factor and low level of harmonics to the load and the utility power system.

  • PDF

단상 계통연계형 태양광 발전 시스템의 직류링크 맥동전압 보상 (DC link Ripple Voltage Compensation of a Single-phase Grid-Connected PV System)

  • 이재근;최종우
    • 전력전자학회논문지
    • /
    • 제17권5호
    • /
    • pp.377-387
    • /
    • 2012
  • A single-phase grid-connected PV system is known as suitable for housing of less than 3 kW. The DC link voltage in a single-phase PV system has necessarily twice component of fundamental wave. It makes high THD in the grid current. According to the problem, power quality is lower. Many engineers have studied about this problem. The most simple method is to use low pass filter on DC link voltage control. However it is affected by DC link voltage control bandwidth. If cutoff frequency is reduced to increase the performance of low pass filter, it also lowers DC link voltage control bandwidth. Second method is using band stop filter, it works good on steady state but not good on transient state. This paper proposes the new method for removing ripple voltage to get an exact current reference. It improves the responses on steady state and transient state. The performance was verified through computer simulation using MATLAB and actual experiments.

계통연계형 태양광 발전시스템에서 역충전방지 알고리즘 설계 (Design of Anti-Islanding Algorithm for Utility interactive Photovoltaic System)

  • 고재석;김홍성;최규하;김한성;이유진;유권종;송진수
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1995년도 하계학술대회 논문집 A
    • /
    • pp.440-442
    • /
    • 1995
  • In a recently as renewable energy source photovoltaic(PV) system using solar energy has been very widely researched because of its pollution-free and infinity. Especially many researches are intensively focused on small scale utility interactive PV system which can use dead space and easily make power stabilized from unstable natural energy source. In this system one of the most important matters is islanding protection. Islanding phenomenon appears when power failure occurs. For the safety of utility interactive PV system must has the function of not only system protection but also detection of islanding. This paper describes parallel operating alghorithm using reactive power variation method and twin peak band pass filter. This alghorithm is verified useful by simulation.

  • PDF

단독운전 방지를 위한 능동적 주파수 변환 기법의 검출 성능 및 THD 분석 (Detection Performance and THD Analysis of Active Frequency Drift for Anti-Islanding)

  • 조영민;최주엽;송승호;최익;이영권
    • 한국태양에너지학회 논문집
    • /
    • 제35권2호
    • /
    • pp.11-19
    • /
    • 2015
  • Islanding is a phenomenon that EPS(Electric Power System) is continuously energized by PV PCS(Photovoltaic Power Conditioning System) even when EPS is isolated from the grid. Unintentional islanding will result in safety hazard, power quality degradation and many other issues. So, islanding protection of grid-connected PV PCS is a key function for standards compliance. Nowadays, many anti-islanding schemes are researched. But existing anti-islanding schemes used in PV PCS have power quality degradation and non-detection zone issues. This paper analyses not only detection performance of existed anti-islanding schemes using active frequency drift but also THD of PCS output current according to each value disturbance for anti-islanding. In addition, the lowest value of disturbance in each scheme was tabulated under guarantee of anti-islanding condition.

계통연계형 태양광발전 시스템의 불평형 보상기법 (The unbalance compensation methode of PWM converter in a Utility interactive Photovoltaic Generation System)

  • 이재훈;신철준;전기영;박춘우;전지용;이상집;오봉환;정춘병;한경희
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2006년도 제37회 하계학술대회 논문집 B
    • /
    • pp.1008-1009
    • /
    • 2006
  • There is an application which uses smoothing reacter connecting each of the phases in order to make the system smaller comparison with an application using the insulating transformer in the utility interactive photovoltaic generation system using the PWM converter. In this case, there might be the occurence of the unbalance of output voltage, by the difference of smoothing reactor, connected on each of the lines. Therefore this study proposes that the method which maintains the balance and compensates the unblance which occured by the different volume of the smoothing reactor connected on each of the lines.

  • PDF

계통연계형 태양광발전 시스템이 계통의 전력품질에 미치는 영향 (Effect of the Interconnected Solar Power Generation System on the Power Quality of Power System)

  • 권동철;박중신;이동영
    • 조명전기설비학회논문지
    • /
    • 제26권7호
    • /
    • pp.52-58
    • /
    • 2012
  • In this study, we have investigated the effect of the solar power generation facilities on the power quality of interconnected solar power generation system. When the solar power generation facility was connected to the distribution system, whether the solar power generation is under operation or not, Peak factor of current was increased to 0.033[%], Frequency is deviated from $60{\pm}0.2$[Hz] and also Short term flicker indication($P_{st}$) increased to 0.213[p.u.] compare with the disconnected situation. Harmonic current [%] in orders was 11.42[%] maximum under 11th orders and was 7.861[%] between 11th and 17th orders. These values were about 3 or 4 times compared with "the power system interconnection technique standards" at the same situation above. Therefore, we could confirmed that the solar power generation facility, when it was connected to the existing distribution system, made bad influence on the power qualities such as the peak factor of current, frequency regulation, short term flicker indication($P_{st}$) and harmonic current [%] in orders etc.

리클로져의 동작특성을 고려한 계통연계형 태양광발전시스템의 보호 알고리즘 (A Protection Algorithm of Grid-Interactive Photovoltaic System Considering Operation Characteristics of Recloser)

  • 김슬기;김응상
    • 대한전기학회논문지:전기기기및에너지변환시스템부문B
    • /
    • 제55권5호
    • /
    • pp.280-286
    • /
    • 2006
  • The paper proposes a new protection algorithm for reliable operation of grid-interfaced PV system, which can flexibly interact with conventional protective schemes of power utility grid not only to prevent damages to utility or public persons and utility apparatus caused by malfunction or failure in distribution network protection system, but also to protect a PV system itself from faults or abnormal conditions of the network. The proposed algorithm is based on reclosing characteristics of the distribution system. As a network fault occurs, the new scheme determines whether it is momentary or permanent and responds in a pre-programmed way to the fault. For permanent outage, the proposed algorithm shuts down inverter's operations but monitoring system voltage and frequency at the point of common coupling with grid. When it comes to the momentary outage, Inverter starts stand-by operation mode so that it can be automatically connected to the grid without start-up procedures as soon as the system voltage and frequency returns into the normal operation range. In order to investigate' and evaluate the PV system operation, simulation study based on PSCAD/EMTDC has been carried out to verify the performance of the proposed protection scheme.

3kW급 계통연계형 태양광발전시스템의 성능특성 평가분석 (Performance Analysis and Evaluation of 3kW Grid-Connected PV Systems)

  • 소정훈;정영석;유권종;최주엽;최익
    • 대한전기학회논문지:전기기기및에너지변환시스템부문B
    • /
    • 제53권8호
    • /
    • pp.509-516
    • /
    • 2004
  • The concerns of distributed generations including photovoltaic(PV) system have been increased around the world since PV system is becoming widespread as a clean and gentle energy source for earth. In the future high density grid-connected PV systems will be interconnected with distribution network. As a result, the stability and long-term reliability of PV systems have become more important issues in this area. Grid-connected PV systems have been installed and monitored at field demonstration test center(FDTC) and also data acquisition system(DAS) has been constructed for measuring and analyzing performance of PV system to observe the overall effect of environmental conditions on their operation characteristics. The performance of PV system has been evaluated and analyzed for component perspective (PV array and power conditioning system) and global perspective (system efficiency, capacity factor, and electrical power energy) by field test and loss factors of PV system.

30kW 주택보급계통연계형 태양광발전시스템 운용효율 분석 (The Analysis of Operation Effect for 3kW Utility interactive PV System)

  • 박정민;김기범;임홍우;김동휘;백형래;조금배
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2003년도 춘계학술대회 논문집 전기기기 및 에너지변환시스템부문
    • /
    • pp.231-233
    • /
    • 2003
  • This paper presents experimental operation with utility interactive 3kW photovoltaic generation system. The status of Photovoltaic generation system components and inter-connection and safety equipment will be summarized. This paper discusses property operation state which 3kW utility interactive photovoltaic generation system was analysed from January 2001 to December 2002.

  • PDF

3kW급 일체형 계통연계 태양광발전 시스템 실증연구 (Demonstration Analysis of 3kW Integrated PV System)

  • 조애옥;김지훈;나종덕;최문한;박수강
    • 전력전자학회:학술대회논문집
    • /
    • 전력전자학회 2005년도 전력전자학술대회 논문집
    • /
    • pp.727-729
    • /
    • 2005
  • Solar cell converts sunlight into the electricity that one of the most versatile forms of energy. It has been developed and applied on residental electric power system by urbanized countries as a alternative energy source to overcome energy problem after oil shock. This paper summarizes the results of these efforts by offering a snapshot of the configuration of photovoltaic in residential applications. The status of PV system components and inter -connection and safety equipment will be summarized. Hence this paper discusses only points that might be useful for application.

  • PDF