• Title/Summary/Keyword: 가스차단기

Search Result 110, Processing Time 0.037 seconds

Development of High Speed Circuit Breaker using Electromagnetic Repulsion Actuator (전자기 반발 구동장치를 사용한 고속 차단기 개발)

  • Hwang, Kwang-Soo;Kim, Young-Il;Moon, Chae-Joo
    • The Journal of the Korea institute of electronic communication sciences
    • /
    • v.17 no.3
    • /
    • pp.441-448
    • /
    • 2022
  • In the distribution system, there are multiple power protection systems such as circuit breakers at substations, and reclosers, minimum circuit ampacities, fault interrupters on distribution lines. They are widely used to prevent partial outages, cascading power failure or blackout so that other healthy systems could maintain the integrity in case of the instant fault or permanent failure on the power lines. However, when a fault happens, it could cause a major black out due to the lack of the protection cooperation between the protection relay of the circuit breaker at a substation and a protection system on the distribution lines. To achieve the power system integrity better, it is required to develop the circuit breaker which can be operational within 1 cycle(16ms). In this study, the high speed circuit breaker which is filled up with eco-friendly gas is developed. This equipment achieved an excellent test results based on IEC 62271-111 standard. It is respected that this equipment would contribute to prevent the wide area blackout by isolating a fault area quicker and faster.

The Inspection Procedure and Method of GIS to Guarantee the Safety of Power Facility (전력설비 안전성 확보를 위한 GIS(가스절연개폐장치) 검사수행 절차 및 방법)

  • Park, Jun-Sung;Hwang, Kwang-Soo;Kim, Jin-Seok
    • Proceedings of the KIEE Conference
    • /
    • 2015.07a
    • /
    • pp.361-364
    • /
    • 2015
  • 본 논문은 전기사업법 제61조의 공사계획인가 및 신고대상인 차단기에 대하여 동법 제63조에 의거해 실시하는 사용전검사의 항목 및 검사수행 방법에 대하여 서술하였다. 차단기는 전력계통을 이상전압에서 보호하기 위한 밀폐형 개폐장치로서 전기사업용 전기설비인 변전소에 설치되는 차단기는 대부분 GIS(Gas Insulated Switchgear)화 되고 있는 실정이다. GIS는 정상전류의 차단, 설비사고의 억제 및 파급사고 확산방지에 중추적인 역할을 수행하고 있기 때문에 그 중요성은 더욱 더 높아지고 있다고 볼 수 있다. 이에 핵심 전력설비인 GIS의 사용전 검사항목 및 검사수행 방법을 고찰함으로써 안정적인 전력공급과 전력계통의 신뢰도 제고에 기여하고자 한다.

  • PDF

Modeling for arc characteristics of DC circuit breaker (직류차단기의 아크특성 모델링)

  • Kim, Yong-Jung;Kim, Hyosung
    • Proceedings of the KIPE Conference
    • /
    • 2017.07a
    • /
    • pp.54-55
    • /
    • 2017
  • 배전계통에서 병렬아크는 전선이나 노후된 설비의 절연파괴에 따른 합선에 의하여 발생하고 직렬아크는 차단기, 소켓-플러그, 커플러 등 접속기에서 부하와 전원이 분리되는 경우에 발생한다. 이러한 아크현상에 대응하기 위해서는 아크의 특성을 해석하고 그에 따른 아크소호방법이 제시되어야 한다. 병렬아크는 1889년 발견된 Paschen의 법칙에 따르며, 평행한 금속판 사이에 아크방전이 시작되는 항복전압이 매질가스의 종류 및 압력과 개리거리에 따른 함수로 규정된다. 반면, 직렬아크는 아직까지 명확한 해석방법이 제시되어있지 못하다. 본 논문에서는 직류 차단기에서 발생하는 직렬 차단 아크의 촉발과 지속적인 발생, 소호에 대한 특성을 분석하여 3가지 특성을 기반으로 하는 직렬 차단아크전류 모델을 제안하고 실험을 통하여 검증하였다.

  • PDF

초고속 무선 데이터 전송을 위한 홈 네트워킹 기술 비교

  • 박지우;조성언;김재영;강희조;오창헌
    • The Magazine of Kiice
    • /
    • v.5 no.1
    • /
    • pp.57-64
    • /
    • 2004
  • 홈 네트워킹(home networking)이란 용어는 가정(home)과 장비들 간의 통신이 가능하도록 하는 망구성(networking)이란 두 가지 용어가 합쳐진 말이다. 가정에 있는 모든 장비들을 연결해 서로 통신할 수 있도록 함으로써, 가족 구성원이 현재 위치에 관계없이(가정 내의 위치 또는 가정 밖의 위치에 무관하게) 가정 내 장비를 제어하거나 통신할 수 있도록 해주는 기술이다. 예를 들어, 거실에 앉아서 잠자리에 든 아이들 방의 불을 끈다거나, 외출하다가 도시 가스 밸브를 열어놓은 것이 생각나면 휴대폰으로 가스차단기를 작동시키는 등 일상생활에 즉시 적용할 수 있는 기술이다[1]. (중략)

  • PDF

Fundamental Study on the Maintenance Technology for SF6 Gas Condition using Pressure and UHF Sensors (UHF 및 가스센서를 이용한 SF6 가스 상태 감시기술 기초연구)

  • Ahn, Hee-Sung;Cho, Sung-Chul;Eom, Ju-Hong
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.21 no.2
    • /
    • pp.20-27
    • /
    • 2007
  • [ $SF_6$ ] gas for compacted power facilities has a important role as an insulation gas. It is very blown well that $SF_6$ gas has the superior characteristics as an insulation gas. For reliable operation of SF6-gas-based high and medium voltage equipment it is very important to keep the insulation ability within a safe range. And the experimental and measuring system were implemented. The test chamber designed to endure up to 3 atmospheric pressure. The analysis results of the experimental data shows that positive partial discharge can be detected by discharge current and UHF signal. Additionally it is shown the possibility that $CO_2$ gas sensor of semiconductor type can be detect the variation of $SF_6$ gas condition. The UHF sensor shows good feature to detect the variation of $SF_6$ gas condition for partial discharge and breakdown discharge.

Ablation Property of Nozzles for a High Voltage Gas Circuit Breaker (초고압 가스 차단기용 노즐 용삭 특성)

  • Bae, Chae-Yoon;Jung, Yong-Woo
    • Proceedings of the KIEE Conference
    • /
    • 2009.07a
    • /
    • pp.846_846
    • /
    • 2009
  • 노즐의 용삭은 초고압 가스 차단기의 압력 상승에 중요한 역할을 한다. 기존의 연구는 총 아크 에너지와 용삭량과의 관계에 집중되어 왔으며 아크 에너지 대신 전류의 제곱등을 사용하기도 했다. 본 논문에서는 반복 시험을 통해 노즐 용삭 특성을 구하였으며, 이를 통해 아크의 전류, 전압과 용삭량과의 상관관계를 구하였다. 또한 계단형 노즐을 사용하여 노즐 반지름과 용삭량과의 관계에 대해서도 살펴보았다.

  • PDF

A Study on A Gas Circuit Breaker Development Using Simplified Synthetic Testing Facility (간이합성시험설비를 이용한 가스차단기 개발에 관한 연구)

  • Chong, Jin-Kyo;Kim, Gyu-Tak
    • Proceedings of the KIEE Conference
    • /
    • 2007.07a
    • /
    • pp.902-904
    • /
    • 2007
  • A $SF_6$ gas circuit breakers are widely used for short circuit current interruption in EHV or UHV power system. During a $SF_6$ gas circuit breaker development, Simplified synthetic testing facility is used. This paper shows how simplified synthetic testing facility is used for a SF6 gas circuit breaker development.

  • PDF

Study on the Mechanical Characteristics of the Eco-Solid Insulator due to the thermal stress (열응력에 의한 친환경 고체 절연체의 기계적 특성에 관한 연구)

  • Byeon, Jeong-Mu;Lee, Jea-Gul;Kim, Young-Geun;Lee, Seog-Won
    • Proceedings of the KIEE Conference
    • /
    • 2011.07a
    • /
    • pp.1264-1265
    • /
    • 2011
  • 본 논문은 가스 절연 차단기를 대체하는 고체 절연체의 성형 시 발생하는 집중 열응력에 의한 고체 절연체의 기계적 특성에 관한 연구 결과이다. 친환경 문제가 대두되고 전기 산업에서 고객은 좀 더 안정적이고 안전한 전기 공급이 필요시 됨에 따라서 고체 절연 개폐기 및 차단기의 수요가 늘어남에 따라 고체 절연체의 생산 불량률이 이슈화가 되고 있다. 특히 성형 시 발생되는 열응력 및 거동으로 인하여 절연체의 균열 및 내부 진공 인터럽터의 파손 등으로 경제적 비용 손실의 문제가 발생하게 되어 집중 응력을 피할 수 있는 합리화 구조에 대한 연구가 진행되었다.

  • PDF

Analysis of Switching Overvoltage for GIL System between Overhead Transmission Lines by EMTP (GIL-가공송전선로 연계시 개폐과전압 검토)

  • Park, H.S.;Kang, J.W.;Jang, T.I.;Kim, H.H.;Suk, K.H.;Choi, K.K.;Oh, J.M.
    • Proceedings of the KIEE Conference
    • /
    • 2009.07a
    • /
    • pp.264_265
    • /
    • 2009
  • 최근 국내에서 가스절연송전선(GIL : Gas Insulated Transmission Line)의 실계통 도입을 위하여 345kV급 GIL의 개발 및 적용을 위한 연구 및 검토가 수행되고 있다. 가공선로의 일부구간을 GIL로 대치하는 데 있어서, 변전소측이 원거리일 경우에는 변전소 내부의 차단기나 단로기 등 개폐 써지에 의한 과전압의 영향은 감쇄효과로 인하여 그다지 크지 않지만, 현재 설치 예정선로와 같이 변전소 측과의 거리가 약 2.6[km]로 짧을 경우 차단기 동작에 의한 개폐써지의 영향을 무시할 수 없게 된다. 따라서 본 논문에서는 GIL 시스템이 가공송전선로와 연계된 경우 근접한 변전소단에서 개폐를 가정하였을 때, GIL 시스템과 가공송전선로에서 발생할 수 있는 개폐과전압에 대하여 과도해석 프로그램인 EMTP를 이용하여 검토하였다.

  • PDF

Prediction of Performance considering Ablated PTFE in High Voltage Self-blast Circuit Breaker (PTFE 용삭을 고려한 초고압 복합소호 차단기의 성능 예측)

  • Kim, Jin-Bum;Kweon, Ki-Yeoung;Lee, Hahk-Sung
    • 한국전산유체공학회:학술대회논문집
    • /
    • 2008.03b
    • /
    • pp.695-698
    • /
    • 2008
  • Self-blast circuit breakers utilize the energy dissipated by the arc itself to create the required conditions for arc quenching during the current zero. During the arcing period, high pressure, temperature and radiation of the arc could burn in pure SF6 gas and PTFE nozzle. Ablated nozzle shape and $SF_6$-PTFE mixture vapor affect the performance of an self-blast circuit breaker. After a number of tests, nozzle in circuit breaker is disassembled, a section of ablated nozzle is investigated precisely. Using computational fluid dynamics, the conservation equation for the gas and temperature, velocity and electric fields within breaker is solved. Before applying a section model, developed program is verified with experimental data. Performance of ablated nozzle shape is compared with original model through analysis program.

  • PDF