• Title/Summary/Keyword: 가솔린 화재

Search Result 23, Processing Time 0.029 seconds

Characteristics of Water Spray for Extinguishment of Gasoline Pool Fire (가솔린 화재의 소화를 위한 수분무의 특성에 관한 실험적 연구)

  • jang, Yong-Jae;Kim, Myung-Bae;Kim, Yu
    • Fire Science and Engineering
    • /
    • v.9 no.2
    • /
    • pp.10-16
    • /
    • 1995
  • This study discribes characteristics of water spray for extinguishment of gasoline fire. Experiments are carried out for the gasoline pool fire nth the atomizing nozzles. Droplet size, spray pressure, amount of water which reaches the flame base and velocity of water spray are measured to find extinguishment conditions. Air entrainment due to the water spray and extinguishing process of gasoline fire by water spray are visualized. Boundary conditions of water spray for extinguishment of gasoline pool fire is quantitatively shown. As the result of experiments, it is found that the velocity of entrainment air and sprayed water are almost same and the water droplets size having small diameter under 40$\mu\textrm{m}$ can not extinguish the fire because too small droplets does not reach the fuel surface.

  • PDF

Analysis on the Results of Measured Concentration of the Combustion Gases Considering Respiration Characteristics in Gasoline Pool Fire (가솔린 풀 화재에서 인체 호흡량 변화를 고려한 연소가스 농도 측정 결과 분석)

  • Choi, Seung Il;Kang, Jung Ki;You, Woo Jun
    • Fire Science and Engineering
    • /
    • v.33 no.4
    • /
    • pp.83-88
    • /
    • 2019
  • This study examined the concentration of combustion gases while considering low ventilation and respiration frequency. A one-quarter-size ISO 9705 room corner test was performed. The concentrations of carbon monoxide and oxygen were measured in each case with the continuous inhalation of combustion gas with low ventilation (2, 6, and 10 LPM) and different respiration frequencies (2 s, 5 s, and infinity). The combustion of a gasoline pool fire in the compartment had a theoretical heat release rate of 5.34 kW. The results show that the deviation of the gas concentrations becomes higher as the low ventilation increases compared to the respiration frequency. In addition, as the respiration frequency increases, the variation in the minimum oxygen concentration is larger than the average value, while in the case of carbon monoxide, the variation in the average value is larger than the maximum value. These results show that the inhalation characteristics of refugees should be considered to investigate fires.

가연성 액체물질 보관용기의 화재예방

  • Park, Il-Geun
    • 방재와보험
    • /
    • s.118
    • /
    • pp.48-51
    • /
    • 2007
  • 본 고에서는 상온일 때 액체상태가 됨에 따라 포화증기압이 1bar 이하가 되는 물질의 보관에 대해 알아보고자 한다. 대체적으로 증류된 석유제품들(가솔린, 나프타, 케로신, 디젤이 그러하다. Zalosh의 '산업화재 예방공학(Indusrtial Fire Protection Engineering)' 과 Crowl의 '폭발의 이해(Understanding Explosions)' 를 통해 많이 다루어져왔던 내용이다.

  • PDF

The Measurement of the Explosion Limit and the Minimum Oxygen Concentration of Gasoline According to Variation in Octane Number (옥탄가 변화에 따른 가솔린의 폭발한계 및 최소산소농도 측정)

  • Kim, Won-Kil;Kim, Jung-Hun;Ryu, Jong-Woo;Choi, Jae-Wook
    • Korean Chemical Engineering Research
    • /
    • v.55 no.5
    • /
    • pp.618-622
    • /
    • 2017
  • Gasoline is a widely used product as a source for energy in homes, the automotive industry, and for industrial power generation, and it is also a product with a high risk of fire and explosion. In this study, to examine the risk for explosion for gasoline, PG, MG and RG, which are categorized according to octane number, were used as test specimens to measure their explosion limit according changes in oxygen concentration. The explosion limit for 21% oxygen concentration in air were confirmed to be 1.5~10.9%, 1.4~8.1%, and 1.3~7.6%, respectively, and the MOC for each of the test sample were confirmed to be 10.9%. The explosion limit measured in the test performed in this study confirmed between a 1.2%~7.6% wider explosion limit for the currently accepted MSDS for gasoline, and therefore it is considered that the results of this study can provide significant reference for preventing fires and explosions for process used gasoline.

A Experimental Study on Characteristics of the Ignition by Cigarette Light (담뱃불 발화특성에 관한 실험적 연구)

  • Yun, lnsu;Kim, Byungseon;Cho, Won Cheol;Lee, Tae Shik
    • Journal of Korean Society of societal Security
    • /
    • v.1 no.1
    • /
    • pp.81-87
    • /
    • 2008
  • The cigarette holds more than 10 percents of the entire fire accidents despite the number of smokers rapidly decreases every year. The purpose of this study is to examine the ignition characteristics of cigarette by experimentation. This study analyzed the cases of fires inferred that they were caused by cigarette in Incheon during 2006. As the representative ignition materials, corrugated board, gasoline, lacquer thinner, tarpaulin, flexible PVC sheet, and poly ethylene were tested. In this experimentation, the corrugated board was ignited by cigarette. However gasoline, lacquer thinner, tarpaulin, flexible PVC sheet, and poly ethylene were seldom ignited. Meanwhile most fire investigators have argued that oils and tents were ignited by cigarette, but this study experimentally proved that such an argument might be ungrounded.

  • PDF

Prediction of sprinkler activation time in compartment fire (구획화재에서의 스프링클러 작동시간 예측 연구)

  • 김명배;한용식
    • Fire Science and Engineering
    • /
    • v.10 no.4
    • /
    • pp.13-18
    • /
    • 1996
  • A general description of sprinkler activation time in compartment-fire-generated smoke layers is made. For calculation of the time hot layer temperature is obtained from two-layer zonal model and time constant of sprinkler is measured. Upper-layer thickness at the instant of sprinkler activation is also presented with changes of opening area. The output of the present study provide inputs for the interaction modeling of sprinkler spray and compartment fire environment, which simulates fire suppression phenomena. Futhermore, experiments are performed in mock-up with gasoline pool fire in order to evaluate the reliability of the model.

  • PDF

A Study of Smoke Spread and Flow in a Long Corridor (복도에서의 연기 확산 및 유동에 관한 연구)

  • 김충익;유홍선;김명배;한용식;김진곤;윤명오;김상욱
    • Proceedings of the Korea Institute of Fire Science and Engineering Conference
    • /
    • 1998.11a
    • /
    • pp.29-39
    • /
    • 1998
  • 복도는 사무실용 건물, 호텔 등 공중이용 건물에서 중요한 피난경로의 일부이다. 화재로 복도에 연기가 확산되면 그 온도, 연층의 높이, 유해물질의 농도 등에 따라 피난에 심각한 장애를 가져올 수 있다. 본 연구는 이러한 복도에서의 연기의 확산 및 유동에 관하여 연구하기 위하여 길이 40m의 복도에서 pool fire로부터의 연기 유동에 관한 실제크기의 실험과 수치해석을 수행하였다. 화재실과 그에 접해있는 긴 복도가 있는 실험장치에 직경 15, 20, 30cm의 가솔린 pool을 화재실 중앙에서 점화 시켰다. 연기의 온도 및 이동을 측정하기 위해 전장 중앙선을 따라 열전대를 설치하였고 연층의 두께를 측정하기 위하여 수직방향으로 세곳에 열전대가 부착된 수직봉을 설치하였다. 아르곤 레이저 sheet 과 비디오 카메라를 이용해 연기의 유동을 가시화 하였다.

  • PDF

The Risk Assessment of Tunnel Fire Through Real Scale Fire Test (실물터널 화재실험을 통한 터널화재 위험도 평가)

  • 최준석;최병일;김명배;한용식;장용재;이유환;황낙순;김필영
    • Fire Science and Engineering
    • /
    • v.16 no.3
    • /
    • pp.71-76
    • /
    • 2002
  • The real scale tunnel fire tests are carried out for the first time in domestic range to assess the extent of risk in the tunnel fire. The tunnel dimension is 465 m in length, 9.2 m in width and 6.5 m in height. Gasoline pools with 0.25 MW∼2.5 MW size and a 1500CC passenger car are used as fire sources. Six jet fans are used to change the flow velocity inside the tunnel. Temperatures at total 86 points in the tunnel are measured to find the temperature distribution and smoke behavior in the real tunnel fire. In the experiment, it is examined that the important parameters to assess the extent of risk in tunnel fire such as back layering of smoke front, descending of smoke layer and the fire size of a real passenger car.

A Study on the Effect of Inflammable Materials on the Control Characteristics of Thermal and Smoke Fluid of Water Curtain System (가연성 물질에 따른 워터커튼 시스템의 열 및 연기유동 제어특성에 관한 연구)

  • You, Woo-Jun;Nam, Jun-Seok;Kim, Dong-Joon;Lee, Jeong-Kyoon;Ryou, Hong-Sun
    • Fire Science and Engineering
    • /
    • v.26 no.2
    • /
    • pp.53-58
    • /
    • 2012
  • In this study fire control characteristics for inflammable materials of water curtain system are experimentally analyzed. Heat release rate for pinewood and gasoline was calculated using Room Corner Tester (RCT) and fire test apparatus for water curtain system is manufactured. Nozzles (180 degree of injection angle, 8.2 mm of orifice diameter) are installed at the nearby ceiling of place at 5 m distance from fire originate and temperature profile as well as transmission are obtained from the fire experiment of pinewood and gasoline in the water curtain system. Based on the results, parameters of engineering importance for fire control characteristics of water curtain system such as generation of high temperature smoke and thermal phenomena of fluid flow by injection nozzle are identified.