A Study on the Method of Resistance Analysis of Water Stream During Fire Supperession

화재진압 시 발생하는 주수 기둥의 저항분석 방법 연구

  • Jung, Byeong-Sun (Intergis Co. Ltd.) ;
  • Kim, Eung-Sik (Division of Safety and Fire Protection Engineering, Hoseo University) ;
  • Park, Jong-Yeol (Department of Convergence Technology for Safety and Environment Graduate School, Hoseo University)
  • 정병선 (인터지스(주)) ;
  • 김응식 (호서대학교 안전소방학부) ;
  • 박종열 (호서대학교 안전환경기술융합 대학원)
  • Received : 2018.10.22
  • Accepted : 2018.11.21
  • Published : 2018.12.31

Abstract

Fire fighters are exposed to the risk of many accidents during fire suppression, especially near the high voltage circuit. In order to prevent and analyze the electric shock accidents, measurement of water resistance is crucial. However, this has been one of the overlooked research areas and it has been very difficult to measure the mixed up resistance components separately. In this paper, we measured a total resistance of apparatus and regarded it as a serial resistance of contact resistance and length dependant resistance. Measuring the resistance by varying the length of water stream, the variable resistance and fixed contact resistance appear, which are used to calculate the both components of resistances. In addition, the resistance of fire hose can be calculated from the parallel circuit which is formed by grounding the fire hose with the resistance of water stream. Results show that we can successfully measure the resistance per unit length of water stream and fire hose, thereby proving that this method is a facile way to measure water and fire hose resistance. However, many experiments are still required to obtain the precise contact resistance of ground under various condition and the resistance between the human body and fire hose.

Keywords

HOJHB0_2018_v33n6_22_f0001.png 이미지

Fig. 1. Electrocutions during fire suppression.

HOJHB0_2018_v33n6_22_f0002.png 이미지

Fig. 2. Modeling of accident circuit.

HOJHB0_2018_v33n6_22_f0003.png 이미지

Fig. 3. Test apparatus and equivalent circuit.

HOJHB0_2018_v33n6_22_f0004.png 이미지

Fig. 4. Fire hose nozzle with electrode.

HOJHB0_2018_v33n6_22_f0005.png 이미지

Fig. 5. Average resistance according to length of the stream.

HOJHB0_2018_v33n6_22_f0006.png 이미지

Fig. 6. Resistance of fire hose according to length.

Table 1. Average resistance according to length of water stream with hose ungrounded

HOJHB0_2018_v33n6_22_t0001.png 이미지

Table 2. Parallel resistance value according to length of water stream with hose grounded

HOJHB0_2018_v33n6_22_t0002.png 이미지

Table 3. Resistance of grounded fire hose according to length

HOJHB0_2018_v33n6_22_t0003.png 이미지

Table 4. Resistance of fire hose per unit length and contact resistance

HOJHB0_2018_v33n6_22_t0004.png 이미지

Table 5. resistances of water stream and fire hose per unit length

HOJHB0_2018_v33n6_22_t0005.png 이미지

References

  1. The Kyunghyang Shinmun "Pajoo Furniture Factory Fire, 1 Missing 3 Wounded", 2015. 05. 28.
  2. https://www.youtube.com/watch?v=xozVqUg_2b8&t=3s, "Fire Fighter Bearing Their Own Treatment", SBS8 News, 2015. 10. 04.
  3. "Volunteer Fire Fighter is Electrocuted while Fighting a Grass Fire-California", Cincinnati, OH: U.S. Department of Health and Human Service, Public Health Service, Centers for Disease Control and Prevention, National Institute for Occupational Safety and Health, DHHS (NIOSH), No. 99F-26, 1999a.
  4. "Downed Power Line Claims the Life of One Volunteer Fire Fighter and Critically Injures Two Fellow Fire Fighter-Missouri", Cincinnati,OH: U.S. Department of Health and Human Service, Public Health Service, Centers for Disease Control and Prevention, National Institute for Occupational Safety and Health, DHHS(NIOSH), No. 99F-37, 1999b.
  5. Doug Leihbacher, "Electrical Safety on the Fireground", Fire Engineering Magazine, Vol. 159, Issue 6, 2006.
  6. Y. J. Lee, S. H. Hyun, J. M. Cha, Y. S. Song, H. S. Kim and Y. S. Ahn, "A Study on the Safety Accident of Firefighters", Proceedings of 2010 Spring Annual Conference, Korean Institute of Fire Science & Engineering, pp. 126-132, 2010.
  7. J. S. Kim and S. P. Kwon, "A Study on the Risk of Electric Shock from the Sprayed Water for Fire Suppression of the PV Installed Building", Fire Science and Engineering, Vol. 28, No. 6, pp. 47-51, 2014. https://doi.org/10.7731/KIFSE.2014.28.6.047
  8. R. T. Long Jr, A. F. Blum, T. J. Bress and B. R. T. Cotts, "Best Practices for Emergency Response to Incidents Involving Electric Vehicles Battery Hazards: A Report on Full-Scale Testing Results", Fire Protection Research Foundation 2013.
  9. "Firefighter Electrocuted in Kentucky Ice Bucket Challenge Accident has Died", The Washington Post, 22. 09. 2014.
  10. Mohamed EL-harkawi, "Electrical Safety Practice and Standard", CRC Press, pp. 106-107, 2013.