Characteristics on the Neutral Point Potential of Line-to-Ground Voltage according to Line-to-Ground Fault in Resistance Ground System for Ships

선박의 저항접지 시스템에서 지락 고장에 따른 대지전압 중성점 전위 특성

  • Lee, Yun-Hyung (Education Management Team, Korea Institute of Maritime and Fisheries Technology) ;
  • Ryu, Ki-Tak (Offshore Training Team, Korea Institute of Maritime and Fisheries Technology)
  • 이윤형 (한국해양수산연수원 교육운영팀) ;
  • 류기탁 (한국해양수산연수원 해양플랜트교육팀)
  • Received : 2018.02.12
  • Accepted : 2018.05.04
  • Published : 2018.05.31

Abstract

System grounding is applied to the neutral point of a power source to secure the from any abnormal voltage and/or grounding fault. System grounding, which is applied mainly in ships is an ungrounded and resistance grounded system. Vessels using the MV power system with 3.3kV, 6.6kV, and 11kV mainly adopt a high resistance grounding system among the resistance grounding systems. The ground fault accounts for 95% of all faults occurring in the electrical system and when a fault occurs, the line-to-ground voltage of the power system is increased excessively, which adversely affects the onboard insulation system. This study analyzed the variation characteristics of the line-to-ground voltage neutral point according to the degree of ground fault in a resistance ground system applied in vessels. For this purpose, the characteristics of the grounding system were first explained, and the modeling of the neutral point potential of the line-to-ground voltage of the resistance grounding system in the vessels was derived. Finally, this study examined how the line-to-ground voltage, line voltage, and neutral point change according to various variable environments through MATLAB simulations.

계통 접지(system grounding)는 어떤 이상전압 유입이나 지락 고장 등으로부터 전력 계통의 안정성을 확보할 목적으로 전원의 중성점에 적용하는 것이다. 선박에서 주로 적용되는 계통 접지는 비접지 시스템과 저항 접지 시스템이다. 440V 선박은 비접지 시스템을 적용하고, 3.3kV, 6.6kV, 11kV의 MV(medium voltage) 시스템을 사용하는 선박은 저항 접지 시스템 중에서 주로 고저항접지 방식을 적용한다. 지락 고장은 전기시스템에서 발생하는 모든 고장의 95%정도이고, 지락고장 발생 시 전력 계통의 대지전압이 과도하게 증가하여 선내 절연 시스템에 악영향을 주게 된다. 본 논문에서는 선박에서 적용하는 저항접지 시스템에 대해 지락 고장 발생시 지락 정도에 따라 전력 계통의 대지전압 중성점의 변동 특성을 확인하고자 한다. 이를 위해 우선 접지 시스템의 종류에 따른 특성을 알아보고, 선박의 저항 접지 시스템의 대지전압 중성점에 대한 모델링을 유도한다. 최종적으로 다양한 변수환경에 따라서 대지전압, 선간전압, 중성점 전위 등이 어떻게 변동되는지 MATLAB을 이용한 시뮬레이션을 통해 지락고장 발생시 나타나는 선내 전압의 변화특성을 분석한다.

Keywords

References

  1. IEEE Recommended Practice for Grounding of Industrial and Commercial Power Systems, IEEE std. 142-2007.
  2. D. Paul and S. I. Venugopalan, "Low-Resistance Grounding Method for Medium-Voltage Power Systems", in Conf. Rec. IEEE IAS Annu. Meeting, pp. 1571-1579, 1991. DOI: https://doi.org/10.1109/IAS.1991.178070
  3. L. J. Kingrey, R. D. Painter, and A. S. Locker, "Applying High Resistance Neutral Grounding in Mmedium Voltage Systems," IEEE Transactions on Industry Application, vol. 47, no. 3, pp. 1220-1231, 2011. DOI: https://doi.org/10.1109/TIA.2011.2126553
  4. J. R. Dunki-Jacobs, F. J. Shields, and C. St. Pierre, Industrial Power System Grounding Design Handbook. Dexter, MI: Thomson-Shore, 2007.
  5. B. Bridger, "High Resistance Grounding," IEEE Transactions on Industry Applications, vol. IA-19, no. 1, pp. 15-21, Jan./Feb. 1983. DOI: https://doi.org/10.1109/TIA.1983.4504149
  6. NEMA WC5-1992/ICEA S-61-402, Thermal Plastic Insulated Wire and Cable for the Transmission and Distribution of Electrical Energy.
  7. System Grounding for Low-voltage Power Systems, Catalog GET-3548(11-1975), Industrial Power System Engineering Operations, General Electric Company, Schenectady, NY 12345.
  8. 2008 National Electrical Code Handbook, 11th ed., Nat. Fire Protection Assoc., Quincy, MA, 2008.
  9. D. D. Shipp, and F. J. Angelini, "Characteristics of Different Power Systems Grounding Techniques: Fact & Fiction," IEEE Trans. Ind. Appl. Ann. Mtg. Conf. Rec.,vol. 2, pp.1535-1544, 1988. DOI: https://doi.org/10.1109/IAS.1988.25261
  10. B. Bridger, "What To Nnow about High Resistance Grounding," EC&M, pp. 37-46, Jul. 1994.
  11. S. M. Choi, "Characteristics of Neutral Point Loci on Line Voltage to Hull When Insulation Resistance Collapses by Earthing Faults at 3 Phase Power Distribution Systems Onboard Vessels," Journal of the Korean Society of Marine Engineering, vol. 35, no. 8, pp. 1117-1123, 2011(in Korean). DOI: https://doi.org/10.5916/jkosme.2011.35.8.1117