DOI QR코드

DOI QR Code

국가지정입원격리병상의 시설별 면적구성에 관한 연구 - 2016년 국가지정입원격리병상 확충사업대상을 중심으로

A Study on the Area Composition Analysis of the National Designated Isolation Unit Wards(NDIUs) - Focused on the NDIU wards issued in 2016

  • 투고 : 2017.04.15
  • 심사 : 2017.05.10
  • 발행 : 2017.06.15

초록

Purpose: Since the facility guidelines for National Designated Isolation Unit wards(NDIUs) had been edited since 2016, all hospital who want to expand or install NDIU should adapt the new guidelines. Instead of providing area requirement, by the way, only essential or optional facility requirements are suggested except patient bedroom in the guidelines. So, as analyze area and area composition of the NDIUs, it could be expected that this study has a role as an area planing reference for not only NDIU but also another airborne infection isolation room. Methods: For the area analysis, 18 sample hospitals are selected among 2016 year applicants. All rooms in NDIUs are grouped as zones whether those are negative air pressurized or not and programed room or not. At the end, area of the zones are summarized and analysed a relationship between area increase and bed number by both correlation analysis and regression analysis. In addition, department usable and gross area per bed, N/G ratio, G/N ratio, and average area ratio of each zone is calculated. Results: First of all, rooms in none negative air pressurized zone of the NDIUs haven't shown a regular installation so that only those in negative air pressurized zone are targeted for the area analysis. Second of all, patient room unit(0.92) and support area(0.79), by correlation analysis, are correlated with total net area. Patient room unit(0.94) and total net area(0.79) are also shown a correlation with bed number. Department usable area($R^2=0.63$, y=36.278x + 102) and patient room unit area($R^2=0.89$, y= 27.993x - 0.8924) has a relationship with bed number by regression analysis. Average N/G is shown as 0.85 and G/N 1.36. Average area ratio of circulation, doffing area, patient room unit, and support area are 25.4%, 9.1%, 50.9%, and 14.6% in order. Implications: This study is a basic research for exploring the NDIUs guidelines to find resonable evidence to develop it for its practical use. Still, it is possibly expected that the guideline is to be developed by post occupancy evaluation in the area of where minimum requirement or facility grade needs to be defined, and by further studies with various perspectives.

키워드

참고문헌

  1. Building Owners and Managers Association International (BOMA),american national standard Institute(ANSI) "Standard Method for Measuring Floor Area in Office Buildings",1996, pp5-25
  2. Centers for Disease Control and Prevention(CDC), 2003, Guidelines for Environmental Infection Control in Health-Care Facilities, 2003, p6
  3. Centers for Disease Control and Prevention(CDC), Guidance on Personal Protective Equipment(PPE) To Be Used By Healthcare Workers during Management of Patients with Confirmed Ebola or Persons under Investigation (PUIs) for Ebola who are Clinically Unstable or Have Bleeding, Vomiting, or Diarrhea in U.S. Hospitals, Including Procedures for Donning and Doffing PPE, Updated on 2015, 8, 27
  4. Facility Guidelines Institute (FGI), 2011, Guidelines for design and construction of Health Care Facilities, 3.2.2.4, p43 http://www.cdc.gov/vhf/ebola/healthcare-us/ppe/guidance.html
  5. 권순정, 국가지정입원치료병동 및 거점병원의 시설기준 개선, 2014, pp 13-20
  6. 법제처, 건축법시행령 제2조 2항, 개정 2016.7.19.
  7. 법제처, 응급의료에 관한 법률 시행규칙, 제17조의 2, 개정 2014.5.1.
  8. 법제처, 의료법시행규칙, 제34조, 개정 2017.2.3.
  9. 조준영, 김은석, 양내원, 종합병원의 G/N비 산정에 관한 건축계획적 연구, 의료.복지 건축, Vol.16 No.4, 2010, pp36-37
  10. 질병관리본부, 국가지정입원치료(격리)병상 운영과 관리, 2011, p4
  11. 질병관리본부, 국가지정입원치료(격리)병상 운영과 관리 지침, 2017, p3-16

피인용 문헌

  1. 거주 후 평가를 통한 국가지정 입원치료병상 시설 개선 방향 도출에 관한 연구 vol.27, pp.3, 2017, https://doi.org/10.15682/jkiha.2021.27.3.39