Abstract
The purpose of this study was to assess the impact by comparing the concentration of indoor radon and look for ways to lower the concentration of indoor radon gas measurements of three variables, the year of completion, volume of the building and ventilation. Measurement target is six classrooms on the sixth floor of building that was constructed in 1973 and was extended in 2011. Selected classroom's volume is different. Four classrooms were selected to compare the radon concentration in accordance with the year of completion, Classrooms that is same year of completion were selected to compare the radon concentration in accordance with the volume, six classroom was performed closure and ventilation to compare radon concentration according to ventilation. Radon concentrations in accordance with the year of building completion showed a high concentration of radon in a building recently built. Also, Radon concentration in volume is high the smaller the volume. Radon concentration change according to ventilation showed a reduction of about 80% when the ventilation than during closing. Especially, The radon concentrations were high detected while the recently year of building completion and the smaller volume. Ventilation of the three variables is considered that can be expected to exposure reduction effect by radon affecting the greatest radon concentration reduction.
본 연구는 실내 라돈 가스의 농도를 낮추기 위한 방법을 찾기 위해 건물의 준공연도, 건물의 용적, 환기 세 가지 변수에 따른 실내 라돈 농도를 비교, 측정하여 그 영향을 알아보고자 한다. 측정은 1973년에 건축이 되었고, 2011년에 증축이 된 건물의 6층을 대상으로 용적이 서로 다르고 준공연도가 1973년과 2011년인 6개의 강의실을 측정하였다. 준공연도에 따른 라돈농도를 비교하기 위해 4개의 강의실을 선정하였고, 용적에 따른 라돈농도를 비교하기 위해 준공연도가 같고 용적이 다른 강의실을 선정하였고, 환기에 따른 라돈농도를 비교하기 위해 6개의 강의실의 폐쇄와 환기를 시행하였다. 결과적으로 준공연도에 따른 라돈농도는 최근에 지어진 건물에서 라돈농도가 최대 4배 높게 나타났으며, 용적에 따른 라돈농도는 용적이 작을수록 높게 나타났다. 환기에 따른 라돈농도의 변화는 폐쇄 시보다 환기를 할 경우 약 80%의 감소율을 보였다. 특히, 준공연도가 최근이면서 용적이 작을수록 라돈농도가 높게 검출되었고, 세 가지 변수 중 환기가 라돈농도 감소에 가장 큰 영향을 끼쳐 라돈에 의한 피폭감소 효과를 기대할 수 있을 것으로 사료된다.