DOI QR코드

DOI QR Code

A study on the acoustic performance evaluation of heat recovery ventilator with a sound absorbing duct

흡음덕트 부착 열회수형 환기장치의 음향성능 평가에 관한 연구

  • Bae, Myung-Whan (Engineering Research Institute, Department of Mechanical Engineering for Production, Gyeongsang National University) ;
  • Song, Jun-Young (Graduate School, Gyeongsang National University) ;
  • Park, Hui-Seong (Graduate School, Gyeongsang National University)
  • Received : 2016.02.11
  • Accepted : 2016.06.14
  • Published : 2016.07.31

Abstract

The purpose of this study is to investigate the acoustic problems of the conventional heat recovery ventilator and to suggest the methods of noise reduction from a heat recovery ventilator according to the installed location. The noise level, in this study, was measured and discussed as the parameters of size, wind volume and sound absorbing duct length for a heat recovery ventilator based on domestic and international related standards. It is found, as a result, that almost all of noise levels from the small and medium heat recovery ventilators without the sound absorbing duct in the anechoic chamber were higher than the noise standard value of 50 dB(A) regardless of the wind volume, and the noise levels went down when a sound absorbing duct was installed. In addition, the sound pressure level relative to frequency bands according to the length of sound absorbing duct was generally decreased, as the length of sound absorbing duct in the small and medium heat recovery ventilators was big, and the sound pressure level was generally increased, as the wind volume was great.

본 연구에서는 기존 열회수형 환기장치의 음향 문제점을 파악하고, 흡음덕트 설치위치별 열회수형 환기장치의 소음저감 방안을 강구하기 위하여 관련된 국내 외 규격을 기준으로 열회수형 환기장치의 크기, 풍량 및 흡음덕트 길이를 파라미터로 한 발생소음을 측정하여 비교하고 고찰하였다. 그 결과, 무향실에서 열회수형 환기장치에 대한 소음은 흡음덕트를 설치하지 않았을 경우에 소형 및 중형 모두 풍량에 관계없이 거의 대부분 소음기준인 50 dB(A) 보다 높게 나타났고, 흡음덕트를 설치하였을 경우에는 소음도가 감소됨을 알았다. 또한, 흡음덕트의 길이에 따른 주파수 대역별 음압수준은 소형과 중형 열회수형 환기장치에서 흡음덕트의 길이가 클수록 대체적으로 감소하였고, 풍량이 클수록 대체적으로 음압수준이 증가하였다.

Keywords

References

  1. Rules for Equipment Standards for Buildings, Minister of Land, Infrastructure and Transport, 2013.
  2. T. Kamimoto and M. W. Bae, "High combustion temperature for the reduction of particulate in diesel engines," SAE Paper 880423, pp. 1-10, 1988.
  3. T. Kamimoto, M. W. Bae, and H. Kobayashi, "A study on soot formation in premixed constant volume propane combustion," Combustion and Flame, vol. 75, no. 3-4, pp. 221-228, 1989. https://doi.org/10.1016/0010-2180(89)90039-4
  4. M. W. Bae, A Study on Soot Formation in Premixed Combustion at High Pressures, Doctoral Dissertation of Tokyo Institute of Technology, Japan, 1989.
  5. L. M. Anderson, B. E. Mulligan, L. S. Goodman, and H. Z. Regen, "Effect of sounds on preferences for outdoor setting," Environment and Behavior, vol. 15, no. 5, pp. 539-566, 1983. https://doi.org/10.1177/0013916583155001
  6. A. Skanberg and E. Ohrstrom, "Adverse health effects in relation to urban residential soundscape," Journal of Sound and Vibartion, vol. 250, no. 1, pp. 151-155, 2002. https://doi.org/10.1006/jsvi.2001.3894
  7. Heat Recovery Ventilator, Korea, SPS-KARSE B 0030-192, 2008.
  8. S. K. Moon, S. H. Kim, H. A. Mun, H. K. Jung, J. H. Lee, Y. H. Choung, and K. Park, "The Korean hearing in noise test," International Journal of Audiology, vol. 47, no. 6, pp. 375-376, 2008. https://doi.org/10.1080/14992020701882457
  9. B. C. Lee, S. H. Ahn, W. C. Kim, and M. W. Bae, "Characteristics of fluid flow in a circulating fluidized heat exchanger," Journal of Korean Society of Marine Engineering, vol. 25, no. 6, pp. 1291-1297, 2001.
  10. S. G. Son, Y. C. Kim, and D. Y. Lee, "Theoretical analysis of a rotary heat exchanger based on a simplified model," Korean Journal of Air-Conditioning and Refrigeration Engineering, vol. 27, no. 8, pp. 409-417, 2015. https://doi.org/10.6110/KJACR.2015.27.8.409
  11. B. G. Lee, Evaluating Performance of Heat Recovery Ventilators for Residential Buildings, M.S. Thesis, Hanyang University, Korea, 2012.
  12. Ministry of Environment, "Research on development and application of hybrid heat recovery ventilation system," Dong-A University Research Foundation for Industry Academy Cooperation, 2008.
  13. S. S. Kim, "Noise reduction evaluation of airborne noise reduced ventilation system used for ventilation of apartments," Journal of Korean Society for Indoor Environment, vol. 6, no. 3, pp. 190-199, 2009.
  14. J. Y. Song, H. Shin, Y. S. Back, and M. W. Bae, "Evaluation of acoustic performance for ventilation system in heat recovery devices," Proceedings of the 38th KOSME Spring Conference, p. 254, 2014.
  15. C. Y. Jung, "Technology development trends of centrifugal blowers for HVAC," Journal of the Korean Association of Air Conditioning, Refrigerating and Sanitary Engineers, vol. 33, no. 3, pp. 42-49, 2016.
  16. C. Y. Jung, "Introduction of silent ventilation duct system," Journal of the Korean Association of Air Conditioning, Refrigerating and Sanitary Engineers, vol. 33, no. 3, pp. 83-89, 2016.
  17. Y. S. Hong, "A study on the performance of heat recovery ventilators for houses," Proceeding of Annual Conference of the Architectural Institute of Korea, vol. 29, no. 1, pp. 23-24, 2009.