DOI QR코드

DOI QR Code

Accelerated Thermal Aging Measurement and Analysis of CSPE Cable for Condition Monitoring

CSPE 케이블의 상태감시를 위한 가속열화 측정 분석

  • Received : 2014.12.22
  • Accepted : 2015.01.15
  • Published : 2015.03.31

Abstract

The accelerated thermal aging of CSPE(Chloro Sulfonate Polyethylene) was carried out for 40.41, 121.22, 202.04 days, 16.82, 50.45, 84.09 days and 7.32, 21.96, 36.59 days at 100, 110, and $120^{\circ}C$, respectively, which are equivalent to 20, 60, 100 years of aging at $50^{\circ}C$. The permittivities and the apparent densities of the accelerated thermally aged CSPE samples are increased with accelerated thermal aging year but EAB(Elongation at Break) is decreased with that. The dielectric strength and the electric breakdown of the non-accelerated and accelerated thermally aged CSPE samples do not depend on accelerated thermal aging year and applied voltage rising time. density and EAB measures.

Keywords

References

  1. Jung-Hoon Lee, Myeong-Kyun Kang, Jun-Soo Jeon, Seung-Hoon Lee, In-Yong Kim, Hyun-Shin Park and Yong-Deok Shin "A Study on the Properties of CSPE According to Accelerated Thermal Aging Years" J Electr Eng Technol Vol. 9, No. 2: 643-648, 2014. https://doi.org/10.5370/JEET.2014.9.2.643
  2. US NRC NUREG/CR-7000, "Essential Elecments of an Electric Cable Condition Monitoring Program", Brookhanven National Lavoratorl Upton, NY, 2010.
  3. K. T. Gillen, R. Assink, R. Bernstein, and M. Celina, "Condition Monitoring Methods Applied to Degradation of Chlorosulfonated Polyethylene Cable Jacketing Materials", Polymer Degradation and Stability, 2006.
  4. Z. Gu, G. Song, W. Liu, J. Gao, W. Dou, and P. Lu, "Preparation and Properties of Chlorosulfonated Polyethylene / Organomontmo-rillonite Nanocomposites", Journal of Applied Polymer Science, 2010.
  5. In-Yong Kim, Cheol-Soo Goo, Jung-Hoon Lee, Yong-Deok Shin, "Condition Monitoring of Cable Used in Nuclear Power Plant through Volume Electrical Resistivity", The International Conference on Electrical Engineering, 2011.
  6. In-Yong Kim, Cheol-Soo Goo, Jung-Hoon Lee, Beom-Soo Jin, Myeong-Kyun Kang and Yong-Deok Shin "A Study of Validation of Condition Monitoring Method of NPPs Cable through Volume Electrical Resistivity", ICHVE pp76-79, 2012.
  7. Patent Number 10-1328994, Patentee: Korea Institute of Nuclear Safety, Inventor: Cheol-Soo Goo, In-Yong Kim, Young-Hwan Choi, Yong-Deok Shin, and Jung-Hoon Lee, 2013.
  8. Y. D Shin, J. h Lee, C. S Goo, I. Y Kim and B. S Jin, "Effects on Measuring Temperature of Volume Electrical Resistivity of the Accelerated Thermal Aging CSPE", KIEE summer conference, 2012.
  9. Kim Jeong Tai, "Theory and Applications of High Voltage Engineering", KYOWOO, 1997.
  10. Jeong Seong Gyu, "High Voltage Engineering", MUNUNDANG, 1996.
  11. Lee Cherl ho, "Characteristics and Evaluation of Polymer Insulation Materials II", Journal of the Electrical World/Monthly Magazine, August, pp. 42-52, 2011.
  12. Lee Sang Woo, "A Study on the DC High Voltage Method XLPE Power Cable" 2005.
  13. International Standards ASTM D 149-09, "Standard Test Methods for Dielectric Breakdown Voltage and Dielectric Strength of Solid Electrical Insulating Materials at Commercial Power Frequencies" 2009.
  14. American National Standard J2.1-1969 "Designation : D" 412-68.