An Experimental Study on a Heat Pump with Dehumidification Function that Utilizes Underground Air Heat

지하공기열 히트펌프 제습기에 관한 실험적 연구

  • Ko, Ji-Woon (Department of Mechanical Engineering, Graduate School, Jeju National University) ;
  • Park, Youn Cheol (Department of Mechanical Engineering, Jeju National University) ;
  • Ko, Gwang-Soo (Department of Mechanical Engineering, Graduate School, Jeju National University)
  • 고지운 (제주대학교 일반대학원 기계공학과) ;
  • 박윤철 (제주대학교 기계공학과) ;
  • 고광수 (제주대학교 일반대학원 기계공학과)
  • Received : 2013.10.21
  • Accepted : 2013.11.29
  • Published : 2014.02.10

Abstract

The present study has been conducted to develope a heating system for a green house with heat from underground air at Jeju Island. The temperature of the air deposited in the underground is $16{\sim}18^{\circ}C$ throughout the year, and it also has a large amount of moisture. Therefore, the air could not directly used for the heating of a green house. In this study, a heat pump with dehumidification function has been developed, which consisted of three evaporators, where the moisture removal occurs, accompanied by temperature drop. The dropped temperature is recovered, while passing through a series condenser. The air temperature increased from $17^{\circ}C$ to 35 with a 2.1 kg/h of moisture removal rate. The developed system moisture removal performance shows 0.91 kg/kWh.

Keywords

References

  1. Smith, G., White, S., and Han, J. C., 1984, Heat transfer and friction in channels with two opposite rib-roughened walls, ASME J. Heat Transfer, Vol. 106, pp. 774-781. https://doi.org/10.1115/1.3246751
  2. Taslim, M. E. and Spring, S. D., 1988, An investigation of heat transfer coefficients in duct, Proceedings, ASME 25th Heat Transfer Conference, Houston, pp. 461-479.
  3. Mills, A. F., 1992, Heat Transfer, 4th ed., McGraw-Hill, New York, pp. 333-351.
  4. Martin, T. J., 1990, Compact Condenser and Evaporator Design, GE Report A-1-20.
  5. Jacobi, A. M., 1992, The Intertube Falling Film, Ph.D. thesis, University of Minnesota, Minneapolis, MN, U.S.A.
  6. Hong, M. K., 1995, Study on turbulent flow in a duct, Korean Journal of Air-Conditioning and Refrigeration Engineering, Vol. 18, No. 6, pp. 507-514.
  7. Lee, M. R. and Park, M. K., 1997, Heat transfer characteristics in a ribbed duct, Proceedings of the SAREK, pp. 110-117.
  8. Kim, C. K., 1992, Heat and Mass Transfer, 6th Ed., Hankuk Inc., p. 542.
  9. Im, K. J. and Hong, K. D., 1997, Study on compact condensers and evaporators, Report of Hankuk Inc., RP 97-001.
  10. Lee, Y. S., 1992, Study on heat transfer characteristics of R-22, MS thesis, Hankuk University, Seoul, Korea.
  11. Seo, J. N., Kim Y. G., and Park, S. T., 2010, A cycle analysis for studying of the effect of inlet condition regeneration condition and rotor rate on hybrid dehumidifier, Proceedings of SAREK 2010 Summer Annual Conference, pp. 1018-1022.

Cited by

  1. Study on the performance of a heat pump system with serial dehumidification function vol.38, pp.6, 2014, https://doi.org/10.5916/jkosme.2014.38.6.609
  2. Recent Progress in Air-Conditioning and Refrigeration Research: A Review of Papers Published in the Korean Journal of Air-Conditioning and Refrigeration Engineering in 2014 vol.27, pp.7, 2015, https://doi.org/10.6110/KJACR.2015.27.7.380
  3. Performance of the Heat Pump with a Air-Water Direct Contact Heat Exchanger for Greenhouse Heating vol.13, pp.3, 2017, https://doi.org/10.7849/ksnre.2017.9.13.3.058