A Comparison of Operating Characteristics for Industrial Water Cooler with Variation of Control Methods

제어방식에 따른 산업용 수냉각기의 운전 특성 비교

  • Baek, Seung-Moon (Department of Refrigeration and Airconditioning Engineering, Pukyong National University)
  • 백승문 (부경대학교 냉동공조공학과)
  • Received : 2014.11.01
  • Accepted : 2014.12.01
  • Published : 2014.12.31

Abstract

This paper presents a comparison of operating characteristics for industrial water cooler with variation control methods. The performance analysis regarding the characteristics of condensation capacity, evaporation capacity, compressor load, COP of an on-off type cooler, a hot gas-bypass control type cooler and an inverter control type cooler with respect to the system load is reviewed, respectively. The primary results are as following: the variation of required compressor load of an on-off type cooler with respect to load is 5%, that of hot gas-bypass type is 18% and 66% for an inverter control type cooler. As the result shows, an inverter control type yields relatively huge difference of required compressor load compared to other types of control system. In terms of partial load, COP of an inverter control type cooler presents the highest value, and is considered as the optimized type for the used of the system involving frequent partial load.

Keywords

References

  1. H. W. Kim, S. M. Baek, C. G. Moon, E. Kim, and J. I. Yoon, 2010, "The Characteristics on the Capacity Control of Inverter Type in an Industrial Water Cooler," ICCHT2010-5th Indonesia, pp. 016-1-016-6.
  2. Hua. Li, J. I. Yoon, and S. K. Jeong, 2004, "Dynamic Characteristics of Refrigeration System for Control Evaporator Superheat and Compressor Capacity", The Korean Society for Power System Engineering, KSPSE The 2004 Spring Conference, pp. 170-174.
  3. S. M. Beak, J. H. Choi, J. Y. Byun, C. G. Moon, H. S. Lee, S. K. Jeong, and J. I. Yoon, 2009, "Characteristics of Temperature Control by Hot-gas Bypass Flow Rate on Industrial Water Cooler", Journal of the Korean Society of Marine Engineering Vol.33, No. 8, pp. 55-62.
  4. S. M. Beak, 2014, "The Characteristic of Inverter Control by Variation of Refrigeration Load and Outdoor Temperature on Industrial Cooler", The Korean Society for Power System Engineering Vol.18, No. 5, pp. 150-155. https://doi.org/10.9726/kspse.2014.18.5.150
  5. Yaqub. M, Zubair S. M., Khan S. H., 1995, "Second-law-based Thermodynamic Analysis of Hot-gas Bypass, Capacity-control Schemes for Refrigeration and Air-conditioning Systems," Energy-The International Journal 20(6), pp. 483-493. https://doi.org/10.1016/0360-5442(94)00091-G
  6. Yaqub. M, Zubair S. M., Jameel-ur-Rehman Khan., 2000, "Performance Evaluation of Hot-gas Bypass Capacity Control Scheme for Refrigeration and Air-conditioning Systems," Energy 25, pp. 543-561. https://doi.org/10.1016/S0360-5442(00)00004-9
  7. S. W. Lee and C .W. Lee, 2007, "Assessment Capability of Oil Cooler with Hot-gas," Korean society for precision engineering, No. 6, pp. 459-460.