DOI QR코드

DOI QR Code

Digital Negative Sequence Relay Algorithm for Detection of Unbalanced State in a Generator

발전기의 불평형 검출을 위한 디지털 역상 계전 알고리즘

  • 박철원 (강릉원주대학교 전기공학과)
  • Received : 2013.11.11
  • Accepted : 2013.11.26
  • Published : 2013.12.01

Abstract

There are conditions that can be unbalanced three phase currents in a large generator by untransposed lines, unbalanced loads, unsymmetrical faults, and open phases. The unbalanced conditions can producing negative sequence components of current that induce two times frequence current in the surface of the rotor, the retaining rings, the slot wedges in the field windings. These rotor currents make the rotor rapidly overheat, so the rotor can cause substantial damage in a very short time. This paper presents the digital negative sequence relay algorithm for unbalanced protection in a generator. The proposed algorithm was tested by using collected current signals on PSCAD/EMTDC considering a hydro turbine based generator control system. It can be seen that the proposed relaying by negative sequence current is useful for detection of unbalanced state of large generator.

Keywords

References

  1. Muhammad Mohsin Aman, Ghauth Bin Jasmon, Qadeer Ahmed Khan, Ab. Halim Bin Abu Bakar, Mohd Noor Abdullah, "Modeling and Simulation of Digital Negative Sequence Relay for Unbalanced Protection of Generator", 2012 IEEE International Power Engineering and Optimization Conference(PEOCO 2012), Melaka, Malaysis, 6-7 June 2012, pp. 72-77.
  2. IEEE Power System Relaying Committee, "IEEE Standard AC Generator Protection", IEEE Std. C37.102-2006, pp. 1-167.
  3. 박철원 외, "대형 발전기 내부사고 보호를 위한 다기능 IED 시제품 기술 개발", 지식경제 기술혁신사업 3차년도 최종보고서, pp. 1-217, 2013.5.
  4. GE Multilin, "G60 Generator Protection System UR Series Instruction Manual", pp. 1-C4, 2011.
  5. ABB, "Generator protection REG670, Application manual", Vol 1.2, pp. 1-608, 2011.
  6. T. Bach, et al., "Determining negative sequence currents of turbin e generator rotors," in Electrical Machines and Systems, ICEMS 2009 International Conference on 2009, pp. 1-6.
  7. ABB Automation Products, "Negative sequence overcurrent relay and protection assemblies", 1999.
  8. A. F. Elneweihi, et al., "Negative-sequence overcurrent element application and coordination in distribution protection", IEEE Trans. on Power Delivery, Vol. 8, pp. 915-924, 1993. https://doi.org/10.1109/61.252618
  9. 임수생, 이은웅, 손홍관, 김석곤, 김준호, "불평형보상용 STACOM의 역상분 전류 검출을 위한 디지털 버터워쓰 필터", 2000년도 대한전기학회 추계부문학술대회 논문집, pp. 333-335, 2000.11.25.
  10. 강용철, 정태영, 국경수, 강해권, 이병은, 김연희, "역상 전류를 이용한 풍력발전기 보호 방법", 2010년도 대한전기학회 하계학술대회 논문집, pp. 560-561, 2010.7.14-16.
  11. 박철원, 오용택, 김윤상, 석광호, 고준호, "발전소의 사고방지를 위한 발전기 보호계전기법에 관한 연구", 2011년도 대한전기학회 전력기술부문회 추계학술대회 논문집, pp. 311-312, 2013.10.
  12. 박철원 외, "발전기의 불평형 보호를 위한 역상계전기법", 2013년도 대한전기학회 산업전기위원회 추계학술대회 논문집, pp. 39-41, 2013.10.
  13. 박철원, 오용택, "발전기의 사고 시뮬레이션과 분석", 대한전기학회 논문지 Vol. 62P, No. 3, pp. 151-158, 2013.9. https://doi.org/10.5370/KIEEP.2013.62.3.151