DOI QR코드

DOI QR Code

탄소접지극이 병설된 접지그리드의 접지임피던스의 해석

Analysis of the Ground Impedance of Ground Grids Combined with the Carbon Ground Electrodes

  • 이복희 (인하대학교 IT공대 전기공학부) ;
  • 엄상현 (인하대 대학원 전기공학과) ;
  • 김유하 (인하대 대학원 전기공학과) ;
  • 이강수 (인하대 대학원 전기공학과) ;
  • 전병욱 (인하대 대학원 전기공학과) ;
  • 최종혁 (인하대 대학원 전기공학과)
  • 투고 : 2012.10.26
  • 심사 : 2012.12.21
  • 발행 : 2013.03.31

초록

This paper deals with the frequency-dependent ground impedance of ground grids combined with the carbon ground electrodes. Ground grids are generally valid for multipurpose grounding systems as well as lightning protection systems. The carbon ground electrodes may be supplementarily used to reduce the high frequency ground impedance and to improve the transient response to surge currents. The frequency-dependent ground impedances of ground grids combined with or without the carbon ground electrodes were measured and their simulations with due regard to frequency-dependent soil resistivity were implemented by using EMTP program and Matlab modeling. As a consequence, the ground impedance of ground grids combined with the carbon ground electrodes is significantly reduced when the test current is injected at the terminal of the carbon ground electrode. The measured and simulated data for the test ground grids fairly agree with each other. It was found that the proposed method of simulating the frequency-dependent ground impedance is distinguished. The simulation techniques of predicting accurately the ground impedances without actual measurements can be used in the design of grounding systems based on ground grids and the carbon ground electrodes.

키워드

참고문헌

  1. B. H. Lee, J. H. Kim and J. H. Choi, "Analysis for the Grounding Impedance of Vertical Grounding Electrodes using the Distributed Parameter Circuit Model" , T. KIEE, Vol.59, No 6, pp.1103-1108, 2010.
  2. P. Llovera, J. A. LLiso, A. Quijano, V. Fuster, "High frequency measurements of grounding impedance on resistive soils", 28th ICLP, PP.727-729, 2006.
  3. B. H. Lee, H. K. Shin and C. H. Seong, "A Method of Simulating the Frequency-dependent Ground Impedance of Counterpoises" J. KIIEE, Vol.26, No.3, pp.73-79, 2012.
  4. S. Visacro, "A comprehensive approach the grounding response lightning currents", IEEE Transactions on Power Delivery, Vol.22 No.1, pp381-386, 2007. https://doi.org/10.1109/TPWRD.2006.876707
  5. M. I. Lorentzou, N. D. Hatziargyriou, and B. C. Papadias, "Time domain analysis of grounding electrode impulse response," IEEE Trans. Power delivery, Vol. 18, No. 2, pp.517-524, 2003.
  6. Y. Liu, N. Theethayi, R. Thottappillil, "An Engineering Model for Transient Analysis of Grounding System Under Lightning strikes: Nonuniform Transmission-Line Approach", IEEE Trans. Power Del., Vol. 20, No.2, 2005.
  7. IEEE Std. 81.2-1991, "IEEE Guide for Measurement of Impedance and Safety Characteristics of Large, Extended or Interconnected Grounding Systems", pp.12-17. 1991.
  8. J. H. Choi, Y. Choi and B. H. Lee, "Evaluations of Errors due to Earth Mutual Resistance in Measuring Ground Impedance of Vertically-driven Ground Electrode", T. KIEE, Vol.58, No. 9, pp.1778-1783, 2009.
  9. B. H. Lee, S. C. Cho and C. H. Seong, "An Analysis of the Frequency-Dependent Resultant Ground Impedance of Veritcal Ground Electrodes Installed in Parallel" J. KIIEE, Vol.26, No.2, pp.99-105, 2012.
  10. S. H. Um, Y. H. Kim, K. S. Lee, B. W. Jeon, and B. H. Lee, "Effect of carbon ground electrodes on ground impedance reduction", Proc. KIIEE Autumn Annual Conference 2012, pp.150-151, 2012.
  11. B. H. Lee, K. S. Lee, S. H. Um and, Y. H. Kim, "Analysis of transient response behaviors and frequency-dependent ground impedances of the carbon ground electrodes", J. KIIEE, Vol.27, No.1, pp.000-000, 2013.
  12. S. Visacro and R. Alipio, "Frequency Dependence of Soil Parameters: Experimental Results, Predicting Formula and Influence on the Lightning Response of Grounding Electrode", IEEE Trans. Power Delivery, Vol. 27, No. 2, pp.931, 2012. https://doi.org/10.1109/TPEL.2011.2158853