DOI QR코드

DOI QR Code

A Development and Performance Test of Voltage Measurement Accuracy Assessment System for Distribution Equipment

배전기기 전압계측 정밀도 평가시스템 개발 및 성능시험

  • 조진태 (한국전력공사 전력연구원) ;
  • 김주용 (한국전력공사 전력연구원) ;
  • 이학주 (한국전력공사 전력연구원) ;
  • 김재한 (한국전력공사 전력연구원)
  • Received : 2013.06.23
  • Accepted : 2013.09.06
  • Published : 2013.09.30

Abstract

Power distribution system has been changed from radial system to closed loop or mesh system due to connection of distributed generation growth. Data from distribution equipments which are installed at distribution line is required to be accurate for the performance of DMS(Distribution Management System). This paper analyzes the voltage measurement data from distribution equipment. However, the results of the analysis are confirmed to have some errors in voltage measurement data from distribution equipment. These errors come from aging of voltage sensor in distribution equipment and inaccurate data transfer to FRTU(feeder remote terminal unit) through the controller. The main problem is that the voltage measurement data of distribution equipment can not be assessed after it's first installation at the distribution line. The voltage measurement accuracy assessment system is to assess the voltage measurement data from distribution equipment on hot-line. This study had a field test to verify the performance of system.

Keywords

References

  1. S.Y. Yun, S.C. Kwon, C.M. Chy, J.Y. Kim, "Development of Load Estimator and Power Flow Program for Smart Distribution Management System," ICEE 2011, 2011.
  2. D.M. Parker, N.D. McCollough, "Medium-voltage Sensors for the Smart Grid: Lessons learned," IEEE Power and Energy Society General Meeting, pp. 1-7, 2011.
  3. A.H. Luxa, A.B. Mueller and T.J. Noble, "Sensors and Non-conventional VT and CT for Medium Voltage Switchgear," IET Trends in Distribution Switchgear, pp. 173-180, 1998.
  4. Live working - Voltage detectors - part 2: Resistive type to be used for voltages of 1kV to 36kV a.c., IEC std. 61243-2, 2002.
  5. Live working -Portable phase comparators for use on voltages from 1kV to 36kV a.c., IEC std. 61481, 2004.
  6. Live working -Insulation foam-filled tubes and solid rods - Part 1: Tubes and rods of a circular cross-section, IEC std. 60855-1, 2009.