DOI QR코드

DOI QR Code

실내 부하조건에 따른 바닥공조 시스템의 에너지 성능 평가

An Energy Performance Evaluation of UFAD System under the Various Conditions of Thermal Load

  • 윤성훈 (한국건설기술연구원 그린빌딩연구실) ;
  • 장향인 (인하대학교 건축공학과) ;
  • 김경아 (한국건설기술연구원 그린빌딩연구실) ;
  • 유기형 (한국건설기술연구원 그린빌딩연구실) ;
  • 서승직 (인하대학교 건축공학과)
  • 투고 : 2012.10.15
  • 발행 : 2013.01.10

초록

The present study has been conducted for evaluating and comparing the performance of the underfloor air distribution system(UFAD) and the ceiling based air distribution system(CBAD) under cooling condition. Simulations and experiments were carried out for verifying the model by TRNSYS program about UFAD and CBAD. The results of simulation for various conditions of thermal load are summarized as followings. UFAD had an advantage for making thermal comfort because of lower temperature of the floor surface. Moreover, UFAD showed lower fan power about 30~50% than CBAD under the same conditions of thermal load. The energy saving rates of UFAD were increased to 17.7% in proportion to the thermal load on unoccupied zone(lighting). Ultimately, additional investigations should be done for analyzing optimized operating conditions of UFAD with considering the thermal performance of building envelop and the thermal load.

키워드

참고문헌

  1. Bauman, F. and Webster, T., 2001, Outlook for underfloor air distribution, ASHRAE Journal, Vol. 43, pp. 18-25.
  2. Webster, T., Bauman, F., and Reese, J., 2002, Underfloor air distribution : Thermal stratification, ASHRAE Journal, Vol. 44, pp. 28-36.
  3. Research group of underfloor HVAC system, 1993, Design and practice of underfloor HVAC system, Gizutsushoin Inc., Tokyo.
  4. Bauman, F., 2003, Underfloor Air Distribution (UFAD) Desing Guide, ASHRAE Inc.
  5. Ali Alajmi and Wid El-Amer, 2010, Saving energy by using underfloor-air-distribution (UFAD) system in commercial buildings, Energy conversion and management, pp. 1637-1642.
  6. Yu, K. H., Cho, D. W., Yu, J. Y., Lee, J. Y., and Lee, S. Y., 2004, Comparative evaluation of indoor environment of office buildings with an underfloor air distribution system and a ceiling based air conditioning system, Journal of AIK, pp. 185-192.
  7. Cho, Y., Kwon, H. S., Kim, S. H., and Kim, Y. I., 2000, Experimental analysis of thermal comfort of an office space for ceiling and floor supply air conditioning systems, Journal of SAREK, pp. 810-816.
  8. Chung, J. D., Hong, H. K., and Yoo, H. S., 2010, Analysis on the impact of MRT for the thermal comfort of UFAD, Energy and Buildings, pp. 2353-2359.
  9. Chae, Y. T., Moon, H. J., Sohn, J. Y., Ahn, B. W., and Park, B. Y., 2000, Comparative Evaluation of Indoor Thermal Environment and Energy Consumption between Ceiling-Based System and Floor-Based System in Cooling Period, Journal of AIK, pp. 101-108.
  10. Yu, K. H. and Song, K. D., 2007, A Study on Design Techniques and Effectiveness in Energy Saving of Occupied Zone in UFAD System, Journal of the Korean Solar Energy Society, pp. 127-133.
  11. Kim, J. H., Kim, D. E., Aum, T. Y., and Hong, M. H., 2011, Load Estimation and Energy Saving Potential in Underfloor Air Distribution( UFAD), Proceeding of SAREK Summer Annual Conference, pp. 198-201.
  12. ISO 7730-2005, Ergonomics of the thermal environment-Analytical determination and interpretation of thermal comfort using calculation of the PMV and PPD indices and local thermal comfort criteria.

피인용 문헌

  1. Influence of Lighting Loads upon Thermal Comfort under CBAD and UFAD Systems vol.8, pp.6, 2015, https://doi.org/10.3390/en8066079