• 제목/요약/키워드: 천장급기 시스템

검색결과 5건 처리시간 0.017초

사무실 공간의 냉방시 천장 및 바닥 급기 공조 방식에 따른 열환경 평가 실험 (Experimental Analysis of Thermal Comfort of an Office Space for Ceiling and Floor Supply Air Conditioning Systems)

  • 조용;권혁승;김성현;김영일
    • 설비공학논문집
    • /
    • 제12권9호
    • /
    • pp.810-816
    • /
    • 2000
  • Thermal comfort plays an important role in modern office buildings. Four major factors affecting thermal comfort are air temperature, velocity, humidity and radiation temperature. Distribution of these thermal factors in indoor space depends largely on the air flow which is related to the method of supplying and extracting air. In this study, an experimental analysis on indoor thermal comfort is conducted to study the difference between a ceiling supply cooling system and a floor supply one. The two cooling systems are applied to an office space during summer season and the distributions of temperature, velocity, radiation temperature and PMV are measured. Results show that the floor supply cooling system is superior in terms of thermal comfort and energy saving. Studies need to be done, however, to reduce the vertical temperature difference of a floor supply air conditioning system.

  • PDF

한국전력공사 신사옥건립 기계분야 기본설계사례

  • 엄태윤;이승주;이병주
    • 대한설비공학회지:설비저널
    • /
    • 제40권6호
    • /
    • pp.40-47
    • /
    • 2011
  • 지중축냉시스템, 흡수식히트펌프, 천장형복사패널+바닥급기 공조방식 등의 획기적 에너지절약 시스템을 반영한 한국전력공사 신사옥건립 기계분야 기본설계 사례를 소개하고자 한다.

  • PDF

실내 부하조건에 따른 바닥공조 시스템의 에너지 성능 평가 (An Energy Performance Evaluation of UFAD System under the Various Conditions of Thermal Load)

  • 윤성훈;장향인;김경아;유기형;서승직
    • 설비공학논문집
    • /
    • 제25권1호
    • /
    • pp.14-19
    • /
    • 2013
  • The present study has been conducted for evaluating and comparing the performance of the underfloor air distribution system(UFAD) and the ceiling based air distribution system(CBAD) under cooling condition. Simulations and experiments were carried out for verifying the model by TRNSYS program about UFAD and CBAD. The results of simulation for various conditions of thermal load are summarized as followings. UFAD had an advantage for making thermal comfort because of lower temperature of the floor surface. Moreover, UFAD showed lower fan power about 30~50% than CBAD under the same conditions of thermal load. The energy saving rates of UFAD were increased to 17.7% in proportion to the thermal load on unoccupied zone(lighting). Ultimately, additional investigations should be done for analyzing optimized operating conditions of UFAD with considering the thermal performance of building envelop and the thermal load.

바닥 급기 공조의 전망

  • 김영일
    • 대한설비공학회지:설비저널
    • /
    • 제30권8호
    • /
    • pp.54-59
    • /
    • 2001
  • 바낙 공기 급기(UFAD, underfloor air distribution)는 사무실과 상업 건물의 공조를 위하여 바닥 하부 공간을 사용하는 혁신적인 기술이다. 북미에서는 UFAD가 기존 천장 공기 급기 방식에 비하여 많은 장점을 지니므로 그 수요가 날로 증가하고 있다. 잘 설계된 UFAD 시스템은 다음과 같은 장점을 지닌다. - 건물의 용도 변경에 따픈 유연성이 우수하므로 건물의 생애 주기 비용을 감소시킨다. - 개별 쾌적성 제어가 가능하므로 온열 쾌적성, 거주자의 만족도 그리고 생산성을 향상시킨다. - 거주자주변에 직접 선선한 공기를 공급하므로 환기 효율, 실내 공기질 그리고 건강 상태를 향상시킨다. - 이코노마이저 운전, 온도 성층화 그리고 낮은 정합 운전에 의하여 에너지 비용을 감소시킨다. - 설비 공간이 축소되고 표준 철골 구조에서는 콘크리트 구조체 변경이 가능하므로 새 건축 공법에서는 충고를 감소시킬 수 있다. 1995년까지만 해도 UFAD는 파격적인 설계 기법이라고 여겨졌지만, 이제 설계자와 건축업자들은 2004년까지 신축되는 사무용 건축품의 35%는 바닥을 높인 기법이 적용되며 이 중 반 정도가 UFAD를 채택할 것이라고 예측하고 있다. 2000년 2억불이라고 추정되던 바닥을 높이는 건축의 시장 규모가 2004년에는 최소 10억불이 되리라고 예측된다. UFAD는 기본 연구에 의한 정립된 표준화된 설계 기법과 지침이 아직 마련되지 않았음에도 불구하고 현재 설계, 시공되고 있다. 이라한 경향은 펄수적인 연구가 수행되어 관련 업계가 지식과 경험을 충분히 쌓기 전까지는 계속될 전망이다. 본고는 시스템 설계와 운영의 주요한 특징, 기존 방식과 비교하여 지니고 있는 잠재적인 장점, 한계와 기술 개발의 필요성, UFAD 기술 개발을 위하여 계속적으로 요구되는 연구 분야 등을 서술함으로써 현재 UFAD 기술에 대한 평가를 한다.

  • PDF