Abstract

In order to improve extinguishing performance of water mist, many studies of additives have been conducted. In this study, viscosity agent which has the ability to improve extinguishing performance by adhering to the surface on fire was used and fluorine-free surfactant was also added to water to enhance water's wetting ability. This study aimed to verify optimal concentration of extinguishing of additives according to fire source and extinguishing performance by comparison with pure water. In case of wood crib fire, the results show that flame suppression and extinguishing time of sodium alginate 0.4 wt.% are 3.4 times and 2.2 times shorter than those of pure water in 0.2 MPa respectively. It seems that large amount of water adhere to surface on fire, thus cooling effect on surface was enhanced. Also water consumption of sodium alginate 0.4wt.% is up to 65% lower than that of pure water. In case of heptane fire, extinguishing time of cocobetaine 0.1 wt.% is 9.7 times shorter than that of pure water in 0.2 MPa. It is thought that because cocobetaine can block oxygen and suppress oil mist by making emulsion film on fire surface due to a low surface tension. On the other hand, water consumption of cocobetaine 0.1 wt.% is 92% lower than that of pure water.

Keywords

References

  1. B. C. Downie, Polymeropoulos and G. Gogos, "Interaction of a Water Mist with a Buoyant Methane Diffusion Flame", Fire Safety Journal, 24, pp. 359-381, 1995. https://doi.org/10.1016/0379-7112(95)00029-1
  2. J. M. Park, "Extinguishing Characteristics of Water Mist Containing Alkail Metal Agent", Doctor of Engineering's Thesis, Chungbuk National University, pp. 1-126, 2006.
  3. D. W. Goo, "Research on the Use of Rain Water during Fire Suppression", Master of Engineering's Thesis, Kangwon National University, pp. 1-81, 2011.
  4. S. Walkinshaw and R. Ault, "Use of Sprinklers and Aqueous Gel for Structure Protection from Wildfire Case Study 2", FP Innovations Advantage, Vol. 11, No. 3, pp. 1-12, 2009.
  5. E. Wilson and A. Ordway, "Tactical Wheeled Vehicle Tire Fire Extinguishing Agent Test Report", Naval Air Warfare Center Weapons Division TM 8565, 2008.
  6. S. Y. Kim and C. S. Shin, "Extinguishing Characteristics of Cooking Oil Fire by Water Mist Added with AFFF Agent", Journal of the KOSOS, Vol. 24, No. 5, pp. 21-27, 2009.
  7. NFPA 750 Standard on Water Mist Fire Protection System, NFPA, MA : Quincy, National Fire Protecion Associaion, 2003.
  8. C. S. Grove, Jr and A. R. Aidun, "Improving the Effectiveness of Water for Fire Fighting", Symposium on Fire Control Research, American Chemical Society, pp. 81-90, 1961.
  9. B. P. Husted, G. Holmstedt and T. Hertzberg, "The Physics Behind Water Mist Systems", Proc. IWMA Conference, pp. 1-15, 2004.
  10. A. K. Kim, B. Z. Dlugogorski and J. R. Mawhinney "The Effect of Foam Additives on the Fire Suppression Efficiency of Water Mist", National Fire Laboratory, Institute for Research in Construction, National Research Council Canada, Ottawa, Canada K1A OR6, pp. 347-357, 1994.