A Study of Performance Characteristics on Portable Air Conditioner by Using Condensation Water

응축수를 이용한 이동식 에어컨의 성능특성에 관한 연구

  • 김재돌 (동명대학교, 공과대학, 냉동공조공학과)
  • Received : 2012.06.13
  • Accepted : 2012.07.05
  • Published : 2012.09.30

Abstract

This study presents the effect which the condensation water affects on performance characteristics of apparatus when the condensation water injects to the condenser. The experimental results are the following. The inlet outlet refrigerant temperature in condenser and outlet air temperature showed a little lower than that of the existing method. Also, the refrigeration capacity and COP(coefficient of performance) increased about 3%, 13~16% and the compressor work decreased about 27% than that of the conventional method. So, these results contribute not only the performance improvement of apparatus but also the solution of problem according to the discharge of periodic condensation water.

본 연구는 실내외기가 일체화된 이동식 에어컨을 대상으로 장치 운전 중 발생되는 응축수를 응축기에 분사한 경우, 응축수가 장치의 성능특성에 미치는 영향을 파악한 연구이다. 연구 결과 응축기 입출구 냉매온도 및 출구 공기온도는 응축수를 이용하지 않는 기존방식에 비해 낮게 유입 및 유출되어 응축수에 의해 상당한 응축부하가 처리되는 것을 알 수 있었다. 또한 동일한 조건에서 장치의 냉동능력과 성능계수는 평균 약 3%, 13~16%정도 높게 나타났으며, 압축기 소비동력 또한 약 27%정도 낮게 나타나응축수를 이용한 경우가 주기적인 응축수 배출에 따른 문제점 해결 이외에도 장치의 성능향상에 크게 기여하는 결과를 얻을 수 있었다.

Keywords

References

  1. W. I. Kang, "History of air conditioner", KARSE, vol. 18, no. 4, pp. 34-43, 2001.
  2. Frank M. White, Fluid Mechanics, McGraw Hill 3th Edition, pp. 361-410, 1995.
  3. ASHRAE, Refrigeration Systems and Applications, pp. 31-325, 1990.
  4. J. I. Yoon and J. D. Kim, Refrigeration Equipment Engineering, Taehoon Pub., 1999.
  5. H. D. Park, "Principles and characteristics of the heat pump", SAREK, vol. 14, no. 3, pp. 242-252, 1985.
  6. Cavallini, A. and Zecchin R., "A dimensionless correlation for heat transfer in forced convection condensation", Proc, 6th Int. Heat Transfer Conf. Tokyo, vol. 3, pp. 309-313, 1994.
  7. M. B. Jung, "Performance of improved device using condensate water on air conditioner", KIPRIS, IPC Cord F24F 1/100, 2000.
  8. H. Sung, "Out door cooling system of split air conditioner using condensate water", KIPRIS, IPC Cord F24F 11/00, 1998.
  9. Kruse, H., "European research and development concerning CFC and HFC substitution", ASHRAE / NIST Refrigerants Conference, pp. 41- 54, 1997.

Cited by

  1. 공랭식 에어컨을 이용한 중앙 집중 공조시스템의 성능 개선에 관한 연구 - 실습선 새누리호를 중심으로 - vol.19, pp.2, 2012, https://doi.org/10.7837/kosomes.2013.19.2.207