Abstract
This study presents on the fire hazard analysis of communication cable in buildings. In order to analyze fire hazards for communication cable IEC 60332-1, UL 94 and cone calorimeter test are conducted. The number of cable used to experiment is 10 communication cable which are generally applied to data communication in buildings. The results show that 9 cables do meet the performance requirement of IEC 60332-1 and 8 cables are V-0 classification. IEC 60332-1 and UL 94 test are inadequate for fire hazard classification. The various parameters obtained by cone calorimeter test such as HRR, peak HRR, smoke production rate and so on. Also it is able to evaluate multiply fire hazard for communication cable with cone calorimeter test results.