DOI QR코드

DOI QR Code

A Experimental Study on the Fire Hazard Analysis For Communication Cable in Buildings

건축물내 통신용 케이블의 화재위험성 분석에 관한 실험연구

  • 홍성호 (한국화재보험협회 부설 방재시험연구원) ;
  • 최문수 (한국화재보험협회 부설 방재시험연구원)
  • Received : 2011.09.26
  • Accepted : 2011.12.12
  • Published : 2011.12.31

Abstract

This study presents on the fire hazard analysis of communication cable in buildings. In order to analyze fire hazards for communication cable IEC 60332-1, UL 94 and cone calorimeter test are conducted. The number of cable used to experiment is 10 communication cable which are generally applied to data communication in buildings. The results show that 9 cables do meet the performance requirement of IEC 60332-1 and 8 cables are V-0 classification. IEC 60332-1 and UL 94 test are inadequate for fire hazard classification. The various parameters obtained by cone calorimeter test such as HRR, peak HRR, smoke production rate and so on. Also it is able to evaluate multiply fire hazard for communication cable with cone calorimeter test results.

Keywords

References

  1. 임혁순, 김두현, "원전 케이블 화재 열속평가 및 열화 진단방법에 관한 연구", 한국안전학회지, Vol. 26, No. 2, pp. 20-25, 2011.
  2. 김성찬, 이성혁, "케이블 화재의 화염전파 해석을 위한 FDS 모델의 격자민감도 평가", 한국안전학회지, Vol. 23, No. 4, pp. 30-35, 2008.
  3. 박양범, 한상옥, "케이블화재 방재대책", 한국화재소방학회논문지, Vol. 9, No. 2, pp.47-56, 1995.
  4. P. Andersson, L. Rosell, M. Simonson, and V. Emanuelsson, "Small and Large Scale Fire Experiments with Electric Cables under Well-Ventilated and Vitiated Conditions", Fire Technology Vol. 40, No. 3, pp. 247-262, 2004. https://doi.org/10.1023/B:FIRE.0000026879.07753.86
  5. IEC 60332-1, Test on Electric Cables Under Fire Conditions, 2002.
  6. UL 94, Test for Flammability of Plastic Materials for Parts in Devices and Appliances, 2000.
  7. ISO 5660-1, Reaction-to-fire tests, Heat release, smoke production and mass loss rate-Part 1: Heat release rate(cone calorimeter method), 2002.
  8. ASTM E 1354, Standard Test Method for Heat and Visible Smoke Release Rates for Materials and Products Using an Oxygen Consumption Calorimeter, 2004.